W
innox · Edition 12.20
EN-11
Packaged blower nominal (60 Hz)
Maximum input, kBtu/h (kW)
*)
, depending on the chamber
pressures, "wc (mbar)
chamber pressures "wc (mbar)
Model
-5
(-12.5)
-3
(-7.5)
-0
(0)
1
(2.5)
2
(5)
WX0050
620
(181)
580
(171)
550
(161)
510
(149)
470
(137)
WX0100
1,130
(333)
1,080
(316)
1,000
(293)
970
(284)
940
(275)
WX0200
2,270
(667)
2,170
(634)
2,000
(586)
1,940
(568)
1,880
(551)
WX0300
3,360
(980)
3,220
(940)
3,000
(880)
2,930
(860)
2,850
(830)
WX0400
4,460
(1310)
4,290
(1260)
4,000
(1170)
3,910
(1150)
3,810
(1120)
WX0500
5,560
(1630)
5,340
(1560)
5,000
(1470)
4,880
(1430)
4,760
(1390)
WX0600
6,690
(1960)
6,430
(1880)
6,000
(1760)
5,870
(1720)
5,720
(1680)
WX0850
9,700
(2840)
9,200
(2694)
8,500
(2490)
8,200
(2416)
7,980
(2337)
*) Maximum inputs for packaged blower versions are given for the
standard combustion air blower without an inlet air filter.
Minimum input on-Ratio, Btu/h (kW)
*)
Model
Minimum, kBtu/h (kW)
WX0050
75 (22)
WX0100
143 (42)
WX0200
300 (90)
WX0300
WX0400
340 (100)
WX0500
570 (170)
WX0600
550 (160)
WX0850
Natural gas
Propane, Butane
500 (146)
600 (175)
*) All imperial inputs based upon gross calorific values (HHV): one
atmosphere, 70°F (21°C). All metric inputs based upon net
calorific values (LHV). For lower inputs, contact Honeywell
Eclipse.
Gas inlet pressure
*)
Fuel pressure at ratio regulator inlet
Model
Maximum
"w.c. (mbar)
Minimum
"w.c. (mbar)
WX0050,
WX0100
27.7 (70)
22.0 (55)
WX0200
40 (100)
23 (58)
WX0300
55 (137)
30 (75)
WX0400
60 (150)
35 (87)
WX0500
55 (138)
38 (95)
WX0600
61 (152)
33 (83)
WX0850
82 (207)
27.7 (69)
*) For proper performance, this pressure must be kept constant
across the burner operating range.
Packaged blower motor power (60 Hz)
Model
hp (Ps)
kW
WX0050
0.75
0.37
WX0100
1.5
1.1
WX0200
3
2.2
WX0300,
WX0400
5
3.7
WX0500,
WX0600
7.5
5.5
WX0850
15
11
Input remote blower
All information is based on laboratory testing. Different chamber
conditions will affect the data.
Eclipse reserves the right to change the construction and/or config-
urations of our products at any time without being obliged to adjust
earlier supplies accordingly.
WX0050: Pressure at air inlet 9" w.c. (22.5 mbar)
WX0100–WX0600: Pressure at air inlet 1 psig (70 mbar)
WX0850: Pressure at air inlet 1.5 psig (100 mbar)
Maximum input, kBtu/h (kW), depending on the chamber
pressures, "wc (mbar)
chamber pressures "wc (mbar)
Model
-5
(-12.5)
-3
(-7.5)
-0
(0)
1
(2.5)
2
(5)
WX0050
650
(190)
630
(183)
590
(173)
560
(163)
520
(152)
WX0100
1,300
(381)
1,260
(371)
1,200
(352)
1,180
(346)
1,150
(338)
WX0200
2,610
(765)
2,520
(740)
2,400
(703)
2,350
(690)
2,310
(677)
WX0300
4,080
(1200)
3,910
(1150)
3,630
(1060)
3,540
(1040)
3,430
(1010)
WX0400
5,520
(1620)
5,280
(1550)
4,900
(1430)
4,760
(1400)
4,620
(1350)
WX0500
6,720
(1970)
6,440
(1890)
5,990
(1760)
5,830
(1710)
5,670
(1660)
WX0600
8,280
(2420)
7,920
(2320)
7,340
(2150)
7,140
(2090)
6,930
(2030)
WX0850
13,600
(3985)
13,200
(3868)
12,500
(3660)
12,200
(3575)
12,000
(3516)
Minimum input on-Ratio, kBtu/h (kW)
*)
Model
Minimum, Btu/h (kW)
WX0050
75 (22)
WX0100
143 (42)
WX0200
300 (90)
WX0300
WX0400
340 (100)
WX0500
570 (170)
WX0600
550 (160)
WX0850
Natural gas
Propane, Butane
500 (146)
600 (175)
*) All imperial inputs based upon gross calorific values (HHV): one
atmosphere, 70°F (21°C). All metric inputs based upon net
calorific values (LHV). For lower inputs, contact Honeywell
Eclipse.
Gas inlet pressure
*)
Fuel pressure at ratio regulator inlet
Model
Maximum
"w.c. (mbar)
Minimum
"w.c. (mbar)
WX0050,
WX0100
27.7 (70)
26.0 (65)
WX0200
40 (100)
30 (75)
WX0300
70 (175)
45 (112)
WX0400
80 (200)
55 (137)
WX0500
69 (172)
42 (103)
WX0600
75 (186)
47 (117)
WX0850
82 (207)
55.4 (138)
*) For proper performance, this pressure must be kept constant
across the burner operating range.