Honeywell E-Mon Class 1000 and or 2000 Meter Connections to IDR 

 
 

E-Mon Class 1000 & 2000 meters include two modular jacks located at the top of the main circuit board. 
The jack on the left (RJ-45, 8-pin) is used to connect the meter to the IDR ports 1 

– 8 or 1 – 16 (500 feet 

maximum cable length.)  The jack on the right is for factory use only. 
 

 

IDR is available in two RJ configurations IDR-8 and IDR-16 

 

Connecting the Class 1000 and 2000 Meter to the IDR 

 
NEVER USE THE 

JACKS LABELED “PORT 0” OR “PORT 2 or ETHERNET” TO CONNECT A METER TO 

THE IDR.  

Connect Class 1000 and 2000 meter’s to the IDR meter input jacks #1-8 using 8 conductor RJ-

45 patch cables (500 foot maximum length.) 
 
IDR-16 - If the IDR is an IDR-16, connect the additional meters to the IDR jacks #9- 16 on the circuit board 
using 8-conductor RJ-45 patch cable (500 foot maximum length.) Wiring for all E-Mon cables must be 
straight through.  See Appendix A for correct cable configuration. 

Содержание E-Mon Class 1000

Страница 1: ...only IDR is available in two RJ configurations IDR 8 and IDR 16 Connecting the Class 1000 and 2000 Meter to the IDR NEVER USE THE JACKS LABELED PORT 0 OR PORT 2 or ETHERNET TO CONNECT A METER TO THE IDR Connect Class 1000 and 2000 meter s to the IDR meter input jacks 1 8 using 8 conductor RJ 45 patch cables 500 foot maximum length IDR 16 If the IDR is an IDR 16 connect the additional meters to the...

Страница 2: ...nd of the cable 1 Plug the 4 wire RJ 11 cable plug assembly into either PORT 0 or PORT 2 of the IDR 2 The unused RS 485 port is used to connect another cable to the next IDR This is called a daisy chain connection The daisy chain may be repeated to connect as many as 52 individual IDRs smart meters or combinations of both 3 NOTE The total combined RS485 cable length must be no more than 4 000 feet...

Страница 3: ...erminals together The SH terminals are not used as the third wire ground is a floating ground This requires putting two wires into each of the 2 terminals RS 485 Terminal Block Ethernet jack requires an Ethernet drop and static IP address for TCP IP communications Note The RS 485 on the IDR does not pass through to the Ethernet port like the Class 3400 and 5000 smart meters do You may daisy chain ...

Страница 4: ...G 1H Set to 1I uses 1I 1J 1K 1L Set to 1M uses 1M 1N 1O 1P Set to 1Q uses 1Q 1R 1S 1T Set to 1U uses 1U 1V 1W 1X Combinations above repeat with 2A through 8U may be used Important The EZ7 ID code referred to on the previous page and meter input port 1 to 8 or 1 to 16 determines the software s meter ID code 1A1 1A2 1A3 through 1A8 Carefully document the IDR EZ7 ID s cables to the IDR meter input po...

Страница 5: ...x A Cable Configurations Four conductor cables for the IDR RS 485 communication 4 000 foot maximum RJ11 Plug Pinout Pin 1 Not Used Pin 2 Black Pin 3 Red Ground Pin 4 Green High Pin 5 Yellow Low Pin 6 Not Used ...

Страница 6: ...through 16 500 foot maximum NOTE All cables are wired pin to pin straight through as shown above Example supplier of RJ 45 patch cables http www staples com Belkin 10 Cat6 RJ45 RJ45 Patch Network Cable Black product_IM1QZ4626 See the IDR installation manual for complete instructions ...

Отзывы: