DVC100 (M) MK2 
Termination Unit

Installation Guide

Содержание DVC100 (M) MK2

Страница 1: ...DVC100 M MK2 Termination Unit Installation Guide ...

Страница 2: ... for the Searchpoint Optima or Optima Plus gas detector The unit features three cable entries one 12 way terminal block a voltage clamp and a communications link entry socket When used with an Optima or Optima Plus the large M25 entry is used to mount the gas detector directly to the box All types of attached gas detector output a 4 20mA signal that is sent via the Termination Unit and field wirin...

Страница 3: ... M MK2 Termination Unit must be properly earthed to protect against electrical shock minimise electrical interference and comply with IS Safety Requirements 5 Dismantling or repair of equipment should be carried out in the safe area only 6 Do not drill holes in the housing as this will invalidate the explosion protection 7 In order to maintain electrical safety the unit must not be operated in atm...

Страница 4: ...ES This section identifies the main features of the Termination Unit and also details important dimensions for the unit when installing Optima Plus M20 Blanking Plug M20 Blanking Plug Handheld Interrogator Socket 3 ...

Страница 5: ...tion for the associated control system for details about external network connection information field wiring interconnections etc 4 Refer to the associated handbook for details about the gas detector MECHANICAL INSTALLATION Mechanical Installation Guidelines 1 Identify a suitable location where the Termination Unit can be mounted The unit should be fitted to a flat surface 2 When fitting a Termin...

Страница 6: ...located at the bottom This fulfils the requirement to position the Optima sensor horizontally so that the risk of fouling the gas detector s optical surfaces is reduced 2 Remove the Termination Unit lid 3 Fit the Optima detector to the left hand M25 entry 4 Fit ATEX approved cable glands to the Termination Unit cable entries as required 5 Fit the external field wiring through the cable glands and ...

Страница 7: ... the Termination Unit mounting holes marked G on the diagram below The box uses different holes depending on the plate s orientation 2 Remove the Termination Unit lid 3 Attach the Searchline Excel gas detector s cable to the Termination Unit Fit to the bottom left entry 4 Fit approved certified cable glands to the Termination Unit cable entries as necessary 5 Fit the external field wiring through ...

Страница 8: ...7 ...

Страница 9: ...n Unit lid 3 Attach the two cables from the Searchline Excel Cross Duct gas detector to the Termination Unit Fit the transmitter s cable to the bottom left entry after removing the 3 4 NPT blanking plug Fit the receiver s cable to the right hand entry see diagram Use suitably approved certified glands adaptors 4 Fit an approved certified cable gland to the Termination Unit cable entry as necessary...

Страница 10: ...9 INSTALLATION CONT 322mm 310mm ...

Страница 11: ...ation Unit must be earthed using the internal earth terminal 7 Suitable crimps and or ferrules must be fitted when connecting more than one wire to a Termination Unit terminal 8 The field terminals of the Termination Unit accept single or multi stranded wire up to 2 5mm2 14AWG Cables should be routed carefully to avoid physical and environmental hazards such as mechanical stress and high temperatu...

Страница 12: ...11 7 NOTES ...

Страница 13: ...eld Wiring Function Colour 1 24V Red 2 24VDC SUPPLY 3 0V Black 4 0V Supply 5 6 7 RS485 A Orange 8 RS485 B Blue 9 Modbus Drain 10 Modbus A 11 Modbus B 12 Earth Terminal Earth Green Yellow Earth Barrier Earth INSTALLATION CONT Searchpoint Optima ...

Страница 14: ...85 A Orange Terminal 7 RS485 B Blue Terminal 8 Earth Terminal Green Yellow Earth Terminal 24VDC IN Terminal 2 0V Terminal 4 4 20mA OUT Terminal 6 Field Wiring Note Modbus wiring may share field wiring entry Modbus Wiring Modbus B Terminal 11 Modbus A Terminal 10 Modbus Drain Terminal 9 ...

Страница 15: ...ec Transmitter 3 0V Supply 4 0V Black Rec Transmitter 5 4 20mA Output 6 4 20mA White Receiver Only 7 RS485 A Orange Receiver Only 8 RS485 B Blue Receiver Only 9 Modbus Drain 10 Modbus A 11 Modbus B 12 Earth Terminal Earth Green Yellow Rec Transmitter Earth Barrier Earth INSTALLATION CONT Searchpoint Excel Cross Duct ...

Страница 16: ...al 9 MOD BUS A Terminal 10 MOD BUS B Terminal 11 Earth Terminal 24V Terminal 2 0V Terminal 4 Cross Duct Transmitter Wiring Cross Duct Receiver Wiring R5485 B Blue Terminal 8 R5485 A Orange Terminal 7 4 20mA White Terminal 6 Earth Green Yellow Earth Terminal 24VDC Red Terminal 2 0V Black Terminal 4 15 ...

Страница 17: ... Gas Detector Wiring Field Wiring Function Colour 1 24VDC SUPPLY 2 24V Red 3 0V Supply 4 0V Black 5 4 20mA Output 6 4 20mA White 7 RS485 A Orange 8 RS485 B Blue 9 Modbus Drain 10 Modbus A 11 Modbus B 12 Earth Terminal Earth Green Yellow Earth Barrier Earth ...

Страница 18: ...l 5 Earth Terminal MOD BUS Drain Terminal 9 MOD BUS A Terminal 10 MOD BUS B Terminal 11 Field Wiring Excel Receiver Wiring Earth Terminal 24VDC Red Terminal 2 0V Black Terminal 4 4 20mA White Terminal 6 RS485 A Orange Terminal 7 RS485 B Blue Terminal 8 ...

Страница 19: ...CERTIFICATION Certification Label 18 ...

Страница 20: ...11 12 A B 0V COMMUNICATION LINK SOCKET 24V 0V 4 20mA MODBUS DRAIN MODBUS A MODBUS B EARTH FIELD WIRING SUPPLY TERMINATION UNIT DVC 100 M MK2 EARTH 24V 0V TRANSMITTER SENSOR CONNECTED VIA SUITABLE Ex e OR Ex d CABLE GLANDS EARTH 24V 0V 4 20mA A B SENSOR DETECTOR OR REMOTE SENSOR DETECTOR CONNECTED VIA SUITABLE Ex e OR Ex d GLANDS ...

Страница 21: ...MITTER SENSOR ENTRY OPTIONAL TRANSMITTER SENSOR ANY SUITABLE ATEX APPROVED SENSOR DETECTOR SENSOR ENTRY SENSOR DETECTOR ANY SUITABLE ATEX APPROVED SENSOR DETECTOR SUPPLY ENTRY OPTIONAL TERMINATION UNIT DVC100 M Baseefa 03ATEX0287 HANDHELD CALIBRATOR TYPE SHC 1 Baseefa 03ATEX0073 COMMUNICATIONS SOCKET I S OUTPUT TO CALIBRATOR FACTORY FIXED 20 ...

Страница 22: ... C to 65 C Enclosure Entry Socket One IS protected Communications Link Entry Socket for connecting the SHC1 Honeywell Analytics Handheld interrogator Cable One M25 sensor entry and three M20 cable entries Entries two fitted with ATEX approved blanking plugs Size 150mm 6 wide x 160mm 6 high x 104mm 41 16 deep Add approximately 30mm 13 16 to the height for the Communications Link Entry Socket Weight...

Страница 23: ... 41 0 44 943 4398 gasdetection honeywell com Americas Honeywell Analytics Inc 405 Barclay Blvd Lincolnshire IL 60069 USA Tel 1 847 955 8200 Toll free 1 800 538 0363 Fax 1 847 955 8208 detectgas honeywell com www honeywell com Technical Services ha emea service honeywell com Asia Pacific Honeywell Analytics Asia Pacific 508 Kolon Science Valley 1 187 10 Guro Dong Guro Gu Seoul 152 050 Korea Tel 82 ...