Honeywell DT900 Скачать руководство пользователя страница 1

MODEL 

RANGE 

Switch S4 

MIRROR
Selector

DT-906 

61 m (200')

OPEN* 

200' *

DT-906 

37 m (120') CLOSED 120' 

DT-900 

27 m (90') 

OPEN* 

90' * 

DT-900 

15 m (50') 

CLOSED 

50' 

SENSITIVITY 

S3 

HIGH

H

NORMAL 

N* 

LOW 

L** 

 

DT·900 Series  DUAL TEC

® 

Motion Sensor for Commercial and 

Light Industrial Applications - Installation Instructions

 

Step 1 

Select mounting height. 

 

Step 2 

Carefully push screwdriver into slots  to 
disengage latches and open top  cover. 

 

Step 3 

Firmly insert screwdriver into slot in  arrow 
and rotate PIR Mirror Selector  to the 
correct range. 

 

Step 4 

Set switch S4 to establish microwave 
range. 

 

 
 

 

 
 
 

 
 
 

 
 
 

 
 

Step 5 

Locate correct sensor range scale  and 
rotate Vertical Adjustment Screw  until the 
diamond corresponds to the  sensor 
mounting height (coarse  adjust). 

 
 
 
 
 
 
 

 

 

NOTE

:  Fine adjust may be needed during 

walk-test. See Supplemental Information. 

Step 6 

Set switch S3 to establish the sensitivity 
best suited to your application. 

 

 

 

 
 
 
 
 
 
 

 

*Factory default setting.   **Not connected 

**Not recommended for DT-906 

Step 7 

Select  INFORMER

®

 

 

mode with switch 

S2 if desired. (See 

Supplemental 

Information

). 

Step 8 

Carefully push screwdriver into slot  to 
disengage latch and remove  bottom 
cover. 

 

 

Step 9 

Unfasten screws and remove mounting 
plate from sensor. 

 

 

Step 10 

Attach mounting plate to wall at  desired 
height, using four fasteners  (not 
supplied). 

 

Step 11 

Install M5 (#10) screw in wall 1.9 cm 
(3/4") below mounting screw, as  shown, 
for tamper activation. 

 

 

 

1.9 cm (3/4") 

Step 12 

Pull about 30 cm (12") of wire from  wall 
through the opening in the  mounting 
plate and route wire to the  terminal strip. 

Step 13 

Hang the sensor on the mounting  plate 
hooks and fasten with the two  mounting 
plate screws. 

 

 

Step 14 

Wire the unit 
as shown.  

 

 

Use 2.0 - 0.3 mm

(14 – 22 AWG) 
 
 
 
 
 

NOTE

: Secure 

wires to  
mounting plate with  
tie wraps. 

  

Step 15 

Loosen horizontal locking screw in 
sensor support base. 

 

 

 

Step 16 

Grasp housing and rotate it to the  desired 
position (coarse adjust).  If  fine adjust is 
needed see Steps 20 -  22. 

 
 
 

 

 

 
 

 
 

 

 
 

NOTE: Reference marks = 5° change. 

Step 17 

Apply power to sensor and prepare  for 
walk-test. 
 

 Wait 90 seconds for power-up self-test 

to run.  All LEDs will flash. 

 

PIR   ALARM    MW 

(Green)  (Red)    (Yellow) 

 

 
 
 
 

 

 

NOTE

:  LEDs flashing after 90 sec. = defective 

Step 18 

Turn the microwave potentiometer 
counterclockwise to decrease the 
microwave range to minimum. 

 

During walk-test, gradually turn the 
potentiometer clockwise increasing 
microwave sensitivity until the  desired 
range is obtained. 

Step 19 

Walk-test the sensor to check for 
adequate detection coverage and to 
verify the sensor is fully functional.  Two to 
four normal steps should  make the LEDs 
light and trigger an  alarm. 

 

NOTE

: If an on-going self-test problem, mask 

condition or an INFORMER condition occurs, the 
LEDs display a pattern that identifies the trouble. 
See 

Supplemental Information

 (Table 3). 

 

NOTE

:  When there is no motion in the 

detection area, all three LEDs should be off. 

Step 20 

For finer horizontal adjustments,  loosen 
the PIR horizontal fine locking  screw on 
PCB. 

 
 
 
 
 
 
 

 

 

Step 21 

Rotate horizontal fine adjust knob to  the 
desired position. 

NOTE

:  Fine adjustment allows for small 

changes (3 degrees right or left) between 
coarse settings. 

 

Step 22 

Tighten horizontal fine locking screw  on 
PCB. 

 

 

Step 23 

Tighten horizontal locking screw in 
sensor support base. 

 

Step 24 

Remove jumper at J5, on the PCB,  to 
disable the LEDs after walk-testing. 
 
 
 
 
 
 
 
 
 
 

Step 25 

Complete installation by closing top 
cover and replacing bottom cover. 

 

 

 

 

DT

906

 
 
 
 

DT

900

 

 

 

30 cm (12”) minimum

4 m (12’)

2 m (6’)

Optimal 

Optimal 

Mounting 

Mounting 

Height 

Height 

 

Mounting Location Guidelines 

 Avoid direct or reflected sunlight, infrared light. 

 Aim sensor away from windows, heating/cooling devices or 

large moving objects. 

 Sensor must have a clear line-of-sight to protected area. 

 Keep at least 1 meter (3’) of space in front of sensor clear. 