Introduction
9/11
DirectLine® DL423 Sensor Module User Manual
1
1. Introduction
1.1 Overview
The DirectLine® Sensor consists of an
electronics module
connected to a
Conductivity Cell.
The electronics module is contained in a NEMA Type 4x sealed weatherproof,
corrosion/impact-resistant polysulfone housing that can be mounted at the end of an
immersion tube or in a sample line. The sealed plastic housing has plug-in
connections for the conductivity cells and 4-20 mA cordset.
1.2 Electronics Module
The electronics module is loop-powered by 16-42 Vdc and will modulate its supply
current from 4 mA to 20 mA, depending upon the conductivity value that is sensed
by the cell. The transmitted loop current is compensated for temperature internally
using the standard Honeywell 8550 thermistor.
For submersion or special wiring applications, the remote electronics module is
compatible with a remote cable/connector that allows the electronics module to be
Wall. Pipe, or DIN Rail mounted.
A 4-20 mA output connection is provided via a 6m cordset or a customer supplied
cable used in combination with a field wiring connector.