USA-2

USA

CAN

MEX

D

Type label

DG       T

Approval and type: see 

type label.

For detailed information on the adjusting range, mean 
switching differential, max. inlet pressure, lock-off, 
medium and switching properties, see page  5 
(Technical data) and the table on page  3 (Ad-
justment).

Installation

 CAUTION

Please observe the following to ensure that the 
DG..T is not damaged during installation and op-
eration:

–   Continuous operation with gases containing 

more than 0.1 %-by-vol. H

2

S or ozone con-

centrations exceeding 200 µg/m

3

 accelerate 

the ageing of elastomer materials and reduce 
the service life.

–   Use approved sealing material only.
–   Dropping the device can cause permanent dam-

age. In this event, replace the entire device and 
associated modules before use.

–   Check max. ambient temperature  – see 

page 5 (Technical data).

–   When using silicone tubes, only use silicone 

tubes which have been sufficiently cured.

–   Vapours containing silicone can adversely affect 

the functioning of electrical contacts.

–   Condensation or vapours containing silicone 

must not be allowed to get into the housing. 

At subzero temperatures, malfunctions/failures 

due to icing can occur.

–  

When installing outdoors, place the DG..T in 
a roofed area and protect from direct sunlight 
(even IP 65 version).

–   Avoid strong impact on the unit.

 

Installation position as required, preferably with 
vertical diaphragm. Then the switching point p

S

 

corresponds to the scale value SK set on the 
hand wheel. In other installation positions, the 
switching point p

S

 will change and no longer 

correspond to the scale value SK set on the 
hand wheel. Check the switching point.

ps = SK

ps =SK + 0,08 "WC ps = SK - 0,08 "WC

 CAUTION

If port 

4

 is at the top, IP 65 will not be satisfied.

4

IP 65

 

The DG..T must not be in contact with masonry. 

Minimum clearance 1" (25 mm).

 

Ensure that there is sufficient installation space.

 

Ensure unobstructed view of the hand wheel.

 1 

  Disconnect the system from the electrical power 

supply.

 2 

 Shut off the gas supply.

 3 

 Ensure that the pipeline is clean.

Ports

2 *

1

4

or

 2 

for

positive pressure (¼" NPT)

for

negative pressure (

1

/

8

" NPT)

Connect

Free

Positive 
pressure 
DG..T

or

 2*

4

Negative 
pressure 
DG..T

4

1

 or 

2*

Differential 
pressure 
DG..T

1

 or 

2*

 for higher absolute pressure. 

4

 for lower absolute pressure.

* Port 

2

 only on DG..T..2 with 2x ¼” NPT connections..

 CAUTION

Port 

4

 connects the upper diaphragm chamber 

with the micro switch. Do not connect port 

4

 to 

pipes carrying gas.

 

The pressure switches are supplied with an inte-

grated vent limiter. In the event of a diaphragm 
tear, the vent limiter limits the escape of gas 
to less than 1.0 CFH of natural gas at 2.8 psi 
(DG..6T) or 7 psi (DG..10T – DG..500T). If neces-
sary, port 

4

 (1/8" NPT) can be used to connect 

the venting line.

 

 A filter pad at port 

4

 protects the electrical contacts 

in the DG..T from dirt particles in the surrounding 
air or in the medium.

 

Filter pad for port 

4

, see PartDetective.

Содержание DG T Series

Страница 1: ...th socket IP 65 1 2 1x NPT connection 2x NPT connections K2 T2 N Red green pilot LED for 24 V DC AC Red green pilot LED for 110 to 230 V AC Blue pilot lamp for 120 V AC A External adjustment If none this specification is omitted DG T switches with rising pressure Part designations 1 2 3 5 4 1 Upper housing section with cover 2 Lower housing section 3 Hand wheel 4 NPT conduit coupling 5 Manual rese...

Страница 2: ...rtical diaphragm Then the switching point pS corresponds to the scale value SK set on the hand wheel In other installation positions the switching point pS will change and no longer correspond to the scale value SK set on the hand wheel Check the switching point ps SK ps SK 0 08 WC ps SK 0 08 WC CAUTION If port 4 is at the top IP 65 will not be satisfied 4 IP65 The DG T must not be in contact with...

Страница 3: ...0 0 4 0 4 WC 1 cm 1 mbar 6 Apply pressure In doing so monitor the ohm meter and the pressure gauge Pressure switches without manual reset DG T DG FT DG ST Type Adjusting range WC mbar Mean switching differential at min and max setting WC mbar Max inlet pressure pmax psi mbar No venting line With venting line1 DG 6T 0 2 2 4 0 5 6 0 08 0 12 0 2 0 3 2 4 psi 165 8 5 psi 600 DG 10T 0 4 4 1 10 0 1 0 16 ...

Страница 4: ...tching point minus the pressure differential between the switching pressure and possible lock off For details of the pressure differential between the switching pressure and possible reset see table on page 3 Adjustment Tightness test 1 Shut off the downstream gas pipeline close to the valve 2 Open the valve and the gas supply Check all used ports for tightness N2 13 psi max 29 psi 15 min 3 4 Main...

Страница 5: ... medium and ambient temperatures 40 to 140 F 40 to 60 C Long term use in the upper ambient temperature range accelerates the ageing of the elastomer ma terials and reduces the service life please contact manufacturer The set switching point may palpably change in me dia and ambient temperatures below 22 F 30 C Storage temperature 4 to 104 F 20 to 40 C Diaphragm pressure switch silicone free Diaphr...

Страница 6: ...omplete see page 1 Part designa tions Report any transport damage immediately Storage Store the product in a dry and clean place Storage temperature see page 5 Technical data Packaging The packaging material is to be disposed of in accordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Directive on the restriction o...

Отзывы: