Configuration
8/05
DC1010/1020/1030/1040 Product Manual
27
Displays
Default Value
shown except for
examples
Parameter
Description
SET
SET
Time set for Alarm 2
* Range: 0-99 min, 59 seconds
0= flickering alarm, 99:59= continual alarm
Other = Time delay for alarm
SET
SET
Alarm Code for Alarm 3
* Refer to Table 4-3 for Alarm Codes.
SET
SET
Time set for Alarm 3
0= flickering alarm, 99:59= continual alarm
Other = Time delay for alarm
SET
SET
Hysteresis for alarms
Sets the hysteresis for alarm actuation
(Range=0 to 1000)
ON: PV<=(SPHYS1)
OFF: PV>(SP+HYS1)
example
SET
SET
Main Control (OUT1) **0
Lower Limit of linear output
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
example
SET
SET
Main Control (OUT1) **
Upper Limit of linear output
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
example
SET
SET
Sub Control (OUT2) **
Lower Limit of linear output
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
example
SET
SET
Sub Control (OUT2) **
Upper Limit of linear output
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
example
SET
SET
Auxiliary Output
Lower Limit of Aux. output
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
example
SET
SET
Auxiliary Output
Upper Limit of Aux. output
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
SET
SET
Motor Time
Three Position Step Control - This is the time it takes the
motor to travel from 0 to 100% (fully closed to fully
open). This time can usually be found on the nameplate
of the motor.
Range: 5 – 200 seconds