Configuration
8/05
DC1010/1020/1030/1040 Product Manual
25
Displays
Default Value
Shown
Parameter
Description
SET
SET
Main Control (OUT 1)
Cycle of Control Output
Output Type (SSR
→
1, 4-20mA
→
0, Relay
→
10)
Range: 0 to 150 seconds
SET
SET
Main Control (OUT 1)
Actuation of Hysteresis
For On/Off Control (P1=0)
(Range
0-1000)
ON: PV<= (SP – HYS1)
OFF: PV> (SP + HYS1)
SET
SET
Sub Control (OUT 2) *
P Value (Proportional Band)
SET
SET
Sub Control (OUT 2) *
I Value (Integral Value)
Same as I1 Configuration
SET
SET
SET
Sub Control (OUT 2) *
D Value (Derivative Time)
Same as D1 Configuration
SET
SET
SET
Sub Control (OUT 2) *
Cycle of Control Output
Same as CYT1 Configuration
SET
SET
SET
Sub Control (OUT 2) *
Actuation of Hysteresis
Same as HYS1 Configuration
SET
SET
Main Control (OUT 1)
Gap
Control Output is turned off before reaching setpoint
Turning Point = SP – GAP 1; Off = (OUT 1 = Heat)
SET
SET
Sub Control (OUT 2) *
Gap
Control Output is turned off before reaching setpoint
Turning Point = SP + GAP 2; On = (OUT 2 = Cool)
SET
SET
Function Lock
Refer to Section 4.4 for Mode access designations.
* Will only appear in models with “OUT2” option.