4.3 Reporting Codes for Non-SLC-Devices
For events that do not originate on SLC devices, the DACT-E3 reports extended codes in the range 900-999. These
codes are not user-configurable. Table 4.3.1 lists the extended codes.
Event
SIA
(See Note 2)
Contact ID
4/2
(See Note 3)
3/1
Contact ID and SIA Formates
For Contact ID and SIA Formats:
NN
= In standalone systems, the group number assigned to the device (00-99).
= In networked systems, the node number where the device is located, (00-65).
= In multi-ring systems, the node number where the device is located, (000-122).
Note: Node numbers greater than 99 are truncated.
UUU
= User-configured ID code (events originating from SLC devices using custom codes 001 = 899, if configured) or event type
code (used only for non-SLC device events). For details, see “Non-SLC Device Event Reporting Codes”.
NOTES
Note 1:
Special AMM/PIDs include the following functions: Reset Switch, Silence Switch, Drill Switch, Alarm Acknowledge Switch, Trouble
Acknowledge Switch.
Note 2:
In SIA format, two reports transmit the extended codes (if configured). See Notes 4 & 5.
Note 3:
In 4/1 format, the “one’s” digit of the user-assigned code is reported (if configured). See Notes 4 and Note 5.
Note 4:
The UUU digits will always be 000 for events originating on the INI-7100, INI-VGC, INI-VGX, INI-VGE and NGA nodes.
Note 5:
The DACT-E3 reports the node number and 000 as the “UUU” digits if an event occurs on an SLC device that does not have a user-
configured code assigned to it and the system is configured to report custom DACT codes.
Note 6:
[ZZZ] indicates the Releasing Zone affected. It ranges from 943 to 950 (representing Releasing Zones 1-8).
Note 7:
When [Z] is used for the 4/2 format, it may range from 3 to 0 (representing Releasing Zones 1-8). Releasing Zone 1 reports as 3, while
Releasing Zone 8 reports as 0.
Code
Event
Comment
000
Phone Line Test
Automatic DACT test OK
001 - 899 SLC Device Codes
User-defined in device configuration
900
Programming Mode
Programming
901
SLC 1
Loop Break, Short, or Disconnect
902
SLC 2
Loop Break, Short, or Disconnect
903
NAC 1
Fault, Short, or Disconnect
904
NAC 2
Fault, Short, or Disconnect
905
Municipal Circuit
Master Box Trouble
906
Aux Power Fault
Resettable or Non-Resettable B+ Fault
907
Municipal Circuit Supervision
908
Positive Ground Fault
909
Negative Ground Fault
910
RS-232 Supervision Fault
911
Annunciator Fault
912
PM-9/PM-9G Supervision Fault
913
Battery Low
914
Battery Fault
915
AC Fault
916
DC Fault
917
Reserved
918
Battery Charger Fault
919 NAC 3, SLP Only
920
NAC 4, SLP Only
921
Access Fail
922
Silent Walk Test
923
Audible Walk Test
924
MNS Reset
925
DACT Account 1 Fault
926
DACT Missing
Table 4.3.1 Non-SLC Device Events Reporting Codes
Table 4.2.2.1 DACT-E3 Contact ID Event Reporting Codes for Custom Formats (Continued)