background image

6

DACT-E3 Product Installation Document —

 P/N 9000-0581:J6  12/16/2019

2.4 Specifications

The following list the electrical specifications for the DACT-E3 sub-assembly.

Section 3:  Wiring Connections

Table 3.1 lists the field wiring connections for the DACT-E3. 

Operating Voltage:

24 VDC non-resettable 

Operating Current:

0.018 amp

Alarm Current:

0.018 amp

Operating Temperature:

32° to 120° F (0° to 49° C)

Relative Humidity:

0 to 93%, non-condensing at 90° F (32° C)

Supervised
Class 2 Power-Limited

Designation

Description

Comments

TB1-1

COM A IN

COM A from ILI-MB-E3/ILI95-MB-E3 TB3-1 or SLP-E3 TB3-1

TB1-2

COM B IN

COM B from ILI-MB-E3/ILI95-MB-E3 TB3-2 or SLP-E3 TB3-2

TB1-3

COM A OUT

COM A OUT to other devices

TB1-4

COM B OUT

COM B OUT to other devices

TB1-5

+24 V IN

+ 24 VDC from PM-9/PM-9G TB4-1, TB4-3, TB4-5 or SLP-E3 TB2-3                          

TB1-6

GND

GND from PM-9/PM-9G TB4-2, TB4-4, TB4-6 or SLP-E3 TB2-4

TB2-1

T1 Tip

Line 1 Tip IN from street Non power-limited*

TB2-2

T1 Ring

Line 1 Ring IN from street Non power-limited*

TB2-3

P1 Tip

Line 1 Tip OUT to phone Non power-limited*

TB2-4

P1 Ring

Line 1 Ring OUT to phone Non power-limited*

TB2-5

T2 Tip

Line 2 Tip IN from street Non power-limited*

TB2-6

T2 Ring

Line 2 Ring IN from street Non power-limited*

TB2-7

P2 Tip

Line 2 Tip OUT to phone Non power-limited*

TB2-8

P2 Ring

Line 2 Ring OUT to phone Non power-limited*

*Non power-limited

Table 3.1   DACT-E3 Installation Wiring Terminals

NOTE: 

For additional information on the DACT-E3, refer to the following document:

- E3 Series

®

 (Expandable Emergency Evacuation System) Control Panel UL Listing Document, P/N: LS10080-051GF-E

Содержание DACT-E3

Страница 1: ...EQUIPMENT THIS EQUIPMENT IS SENSITIVE TO STATIC ELECTRICITY IT MAY BE DAMAGED IF NOT PROPERLY HANDLED TRANSPORT AND STORE THIS UNIT IN A STATIC SHIELDING BAG FAILURE TO OBSERVE THIS REQUIREMENT COULD CAUSE LATENT DAMAGE TO THE EQUIPMENT WHICH MIGHT NOT MANIFEST ITSELF UNTIL AFTER THE EQUIPMENT IS PLACED IN SERVICE CAUTION 2 DISCONNECT ALL POWER REMOVE ALL SOURCES OF POWER BEFORE SERVICING REMOVING...

Страница 2: ...e to be indoors only in dry locations protected from rain water and rapid changes in temperature that could cause condensation Equipment must be securely mounted on rigid permanent walls Operating temperature shall not exceed the range of 32 to 120 F 0 to 49 C Operating humidity shall not exceed 93 non condensing at 90 F 32 C There should be adequate space around the installation to allow easy acc...

Страница 3: ...abinets P N LS10083 000GF E 2 3 1 DACT E3 Installation Assembly Options Table 2 3 1 1 lists the systems cabinets and mounting plates that use the DACT E3 E3 Series is a registered trademark of Honeywell International Inc Ademco is a registered trademark of Ademco Inc 2020 Copyright by Honeywell International Inc All rights reserved E3 Series Fire S3 Series Retrofit Cabinet A1 Backbox SLP BB Cabine...

Страница 4: ...the ILI MB E3 ILI95 MB E3 as shown in Location 1 of Figure 2 3 1 1 1 2 Align and place the DACT E3 on the left side and above the ILI MB E3 ILI95 MB E3 3 Insert and secure four screws 4 40 x 1 4 into the four standoffs as shown in Location 2 of Figure 2 3 1 1 1 Figure 2 3 1 1 1 illustrates the DACT E3 installed to the Cabinet C E3 INCC CAB C plate Figure 2 3 1 1 1 DACT E3 Circuit Board Installed t...

Страница 5: ...3 3 To mount the DACT E3 to the SLP E3 insert and secure four screws 4 40 x 1 4 into the four standoffs as shown in Location 2 of Figure 2 3 1 2 1 Figure 2 3 1 2 1 DACT E3 to S3 Mounting Plate Installation Figure 2 3 1 2 2 illustrates the DACT E3 installed in the SLP BB cabinet Figure 2 3 1 2 2 DACT E3 Installed in the SLP BB Cabinet SLC PM SLC95 PM SLC PM SLC95 PM DACT E3 SLP E3 S TA N D O FF M F...

Страница 6: ...evices TB1 4 COM B OUT COM B OUT to other devices TB1 5 24 V IN 24 VDC from PM 9 PM 9G TB4 1 TB4 3 TB4 5 or SLP E3 TB2 3 TB1 6 GND GND from PM 9 PM 9G TB4 2 TB4 4 TB4 6 or SLP E3 TB2 4 TB2 1 T1 Tip Line 1 Tip IN from street Non power limited TB2 2 T1 Ring Line 1 Ring IN from street Non power limited TB2 3 P1 Tip Line 1 Tip OUT to phone Non power limited TB2 4 P1 Ring Line 1 Ring OUT to phone Non p...

Страница 7: ...ED3 STANDBY LINE2 STATUS LINE1 STATUS DACT E3 MUST BE THE FIRST DEVICE TO THE TELCO LINES IMPORTANT FROM ILI MB E3 OR ILI95 MB E3 TB3 1 OR FROM SLP E3 TB3 1 FROM ILI MB E3 OR ILI95 MB E3 TB3 2 OR FROM SLP E3 TB3 2 RS485 COM A OUT TO NEXT DEVICE RS485 COM B OUT TO NEXT DEVICE FROM ILI MB E3 OR ILI95 MB E3 TB3 6 OR FROM SLP E3 TB2 3 FROM ILI MB E3 OR ILI95 MB E3 TB3 7 OR FROM SLP E3 TB2 4 TELCO LINE...

Страница 8: ... and off hook status to phone lines Listen for dial tone 440 Hz tone typical in most networks Dialing the Central Station phone number Programmable ACK and Kiss off Tone Discern proper Central Station ACK and Kiss off tone Transmits data Transmit data to the Central Station Data verification Verify that data has been accepted by the Central Station Phone line options Hang up and release phone line...

Страница 9: ...G GGT 8 T 8 Disable Restored FU GGT 3 571 0G GGT 7 T 7 Disable Waterflow AMM PID SB GGT 1 570 0G GGT 8 T 8 Disable Restored Waterflow AMM PID SU GGT 3 570 0G GGT 7 T 7 Disable Special AMM PID UB GGT 1 570 0G GGT 8 T 8 Disable Restored Special AMM PID UU GGT 3 570 0G GGT 7 T 7 AC Fail AT 0 1 301 0G 000 80 8 AC Fail Restored AR 0 3 301 0G 000 70 7 Phone Line 1 Fault LT 1 1 351 0G 000 81 8 Phone Line...

Страница 10: ... Device Non latching 4 Supervisory Device Latching 5 Waterflow Non silenceable 6 Smoke Alarm 7 Non reporting Device 8 Multi level Device 9 CO Gas Alarm Device Note Special AMM PIDs include the following functions Reset Switch Silence Switch Drill Switch Alarm Acknowledge Switch Trouble Acknowledge Switch NOTE To use the Custom DACT Reporting Feature all ILI MB E3 ILI S E3 and SLP E3 nodes on the n...

Страница 11: ...FB UUU 1 571 NN UUU 8 U 8 Disable Restored FU UUU 3 571 NN UUU 7 U 7 Disable Waterflow AMM SB UUU 1 570 NN UUU 8 U 8 Disable Restored Waterflow AMM PID SU UUU 3 570 NN UUU 7 U 7 Disable Special AMM PID UB UUU 1 570 NN UUU 8 U 8 Disable Restored Special AMM PID UU UUU 3 570 NN UUU 7 U 7 AC Fail AT 0 1 301 NN UUU 80 8 AC Fail Restored AR 0 3 301 NN UUU 70 7 Phone Line 1 Fault LT 1 1 351 NN UUU 81 8 ...

Страница 12: ...INI 7100 INI VGC INI VGX INI VGE and NGA nodes Note 5 The DACT E3 reports the node number and 000 as the UUU digits if an event occurs on an SLC device that does not have a user configured code assigned to it and the system is configured to report custom DACT codes Note 6 ZZZ indicates the Releasing Zone affected It ranges from 943 to 950 representing Releasing Zones 1 8 Note 7 When Z is used for ...

Страница 13: ...easing Zone 1 944 Releasing Zone 2 945 Releasing Zone 3 946 Releasing Zone 4 947 Releasing Zone 5 948 Releasing Zone 6 949 Releasing Zone 7 950 Releasing Zone 8 951 981 Cross Zone 1 31 Cross Zone 31 981 is used to report Group Cross Zone Events 982 Node Missing Any Node Missing Trouble does not indicate a specific node 983 Node Extra Any Node Extra Trouble does not indicate a specific node 984 LCD...

Страница 14: ...LI S E3 Intelligent Loop Interface Expansion Board Installation Instructions 9000 0579 ILI MB E3 Intelligent Loop Interface Main Board Installation Instructions 9000 0580 RPT E3 UTP Repeater E3 Unshielded Twisted Pair Installation Instructions 9000 0582 LCD E3 Liquid Crystal Display E3 Installation Instructions 9001 0017 ILI95 MB E3 Intelligent Loop Interface 95 Main Board Installation Instruction...

Отзывы: