background image

FL-300-000 

I56-3255-003R

D355PL Duct Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

NOTE

: The D355PL come with the sensor head factory installed, part number SD355R.

Table of Contents 

Page

[1] Limitations of Duct Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . .1
[2] General Description  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
[3] Contents of the Duct Smoke Detector Kit . . . . . . . . . . . . . . . . . . . . . .1
[4] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
[5] Sampling Tube Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
[6] Measurement Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
[7] Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
[8] Verification of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
[9] Dectector Cleaning Procedures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
[10] Sensor Replacement  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
[11] Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Warranty 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

BEfORE INSTALLINg

Read the System Sensor Guide for 

Proper Use of Smoke Detectors in Duct Appli-

cations

 (A05-1004), which provides detailed information on detector spacing, 

placement,  zoning,  wiring,  and  special  applications.  Copies  of  this  manual 
are available online at www.systemsensor.com. NFPA Standards 72 and 90A 
should also be referenced for detailed information. 

NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following 
NFPA 72 requirements. The detector should be cleaned at least once a year.

[1]LIMITATIONS Of DUCT SMOkE DETECTORS 

WARNING

The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR 
PROTECTION as a means of providing life safety. Nor are they a substitute for 
early warning in a building’s regular fire detection system.

System Sensor supports this position and strongly recommends that the user 
read NFPA Standards 90A, 72, and 101. The D355PL Air Duct Smoke Detectors 
are listed per UL 268A.

This  device  will  not  operate  without  electrical  power.  Fire  situations  may 
cause an interruption of power. The system safeguards should be discussed 
with your local fire protection specialist.

This device will not sense smoke unless the ventilation system is operating 
and the cover is installed.

For this detector to function properly, it MUST be installed according to the in-
structions in this manual. Furthermore, the detector MUST be operated within 
ALL electrical and environmental specifications listed in this manual and the 
sensor  head  installation  manual.  Failure  to  comply  with  these  requirements 
may prevent the detector from activating when smoke is present in the air duct.

[2]gENERAL DESCRIPTION

Smoke introduced into this air duct system will be distributed throughout the 
entire building. Smoke detectors designed for use in air duct systems are used 
to sense the presence of smoke in the duct. 

Model D355PL Air Duct Smoke Detector utilizes photoelectric technology for 
the detection of smoke. This detection method, when combined with an ef-
ficient housing design, samples air passing through the duct and allows detec-
tion of a developing hazardous condition. When sufficient smoke is sensed, 
an alarm signal is initiated at the fire control panel monitoring the detector, 
and appropriate action can be taken to shut off fans, blowers, change over air 
handling systems, etc. These actions can facilitate the management of toxic 
smoke and fire gases throughout the areas served by the duct system.

The D355PL incorporates a sensor cover tamper feature that provides a trou-
ble signal at the panel immediately if the cover is removed or improperly in-
stalled. Proper installation of the sensor cover removes the trouble condition.

If programmed with the system control panel, two LEDs on each duct smoke 
detector light to provide local visible indication. 

The  D355PL  provides  a  remote  alarm  output  for  use  with  auxiliary  devices, 
such as the RA400Z/RA100Z remote LED annunciator, as well as remote test ca-
pability with the RTS451/151 or RTS451KEY/RTS151KEY Remote Test Stations.

[2.1] DETECTOR fEATURE SET

– Utilizes plug-in head, part number SD355R
– Sampling tubes install from front and rear
– Compatible with existing accessories
– Able to address detector per code switches on sensor head.

[3]CONTENTS Of ThE DUCT SMOkE DETECTOR kIT

1. Sensor/power board assembly and covers sensor head is factory installed
2. Three #10 sheet metal screws for mounting
3. One test magnet
4. Drilling template
5. One sampling tube end cap
6. One plastic exhaust tube
NOTE: A sampling tube must be ordered to complete the installation. It must 
be the correct length for the width of the duct where it will be installed. See 
Table 1 on page 3 to determine the inlet tube required for different duct widths. 

[4]DETECTOR INSTALLATION 
[4.1]VERIfy DUCT AIR fLOw DIRECTION AND VELOCITy

Model D355PL detectors are designed to be used in air handling systems hav-
ing air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 
12 feet can be accommodated. Be sure to check engineering specifications to 
ensure that the air velocity in the duct falls within these parameters. If neces-
sary, use a velocity meter (anemometer) to check the air velocity in the duct.

[4.2]DETERMINE MOUNTINg LOCATION AND CONfIgURATION

On  ducts  wider  than  18  inches  it  is  recommended  that  the  detector  be 
mounted  downstream  of  a  bend,  obstruction  in  the  duct,  or  the  supply  or 
return air inlet. 

I56-3255-00

3R

SPECIfICATIONS 

Operating Temperature: 

–4° to 158°F (–20° to 70°C)

 

32° to 120°F (0° to 49°C) with module installed in the D355PL

Storage Temperature: 

–22° to 158°F (–30° to 70°C)

Humidity: 

0% to 93% Relative Humidity Non-condensing

Air Velocity: 

100 to 4000 ft./min. (0.5 to 20.3 m/sec.)

Rectangular Footprint Dimensions: 

14.38 in L×5 in W×2.5 in D (37 cm L×12.7 cm W×6.36 cm D)

Square Footprint Dimensions: 

7.75 in L×9 in W×2.5 in D (19.7 cm L×22.9 cm W×6.35 cm D)

Weight: 

1.8 pounds; 0.82 kg

Operating Voltage Range: 

15 to 32 VDC

Standby Current: 

300

µ

A @ 24 VDC (one communication every 5 seconds with LED blink enabled)

Max. Alarm Current (LED on): 

6.5 mA @ 24 VDC

ACCESSORY CURRENT LOADS AT 24 VDC

DEVICE

STANDBY

ALARM

RA400Z/RA100Z

0mA

12mA Max.

RTS451/RTS151

0mA

12mA Max.

RTS451KEY/

RTS151KEY

12mA

12mA Max.

One FireLite Place

Northford, CT 06472

Phone: 203.484.7161 

Содержание D355PL

Страница 1: ...e fire control panel monitoring the detector and appropriate action can be taken to shut off fans blowers change over air handling systems etc These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system The D355PL incorporates a sensor cover tamper feature that provides a trou ble signal at the panel immediately if the cover is removed o...

Страница 2: ...ers and cut two 1 375 inch diameter holes using a 13 8 inch hole saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target C centers If desired drill an additional 156 inch hole at the location of one of the mounting tabs on the lower housing 4 4 Secure the Duct Detector to the Duct Use two rectangular configuration or three square configuration of the pro vided sheet metal scre...

Страница 3: ...the housing connection that meets the air flow first Position the tube so that the arrow points into the airflow as shown in Figure 3 Per NFPA sampling tubes over 3 feet long should be supported at the end opposite of the duct detector In ducts wider than 8 feet work must be performed inside the duct to couple the other section of the sampling tube to the section already installed using the inch c...

Страница 4: ... service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 9 1 Detector Sensor 1 Remove the sensor to be cleaned from the system 2 Remove the sensor cover by pressing firmly on each of the four removal tabs that hold the cover in place 3 Vacuum the screen carefully without removing it If further cleaning is re quired continue ...

Отзывы: