DISPLAY MODULE OPERATION

This section describes the layout and operation of the 
ControLinks™ Display Module. See Fig. 5.

Fig. 5. Identification of S7999 ControLinks™ 

Display Module display items.

Mode

The MODE item shown in Fig. 5 is the current operating mode 
of the R7999. The two primary modes are Auto and Manu, 
which correspond to the R7999 Auto/Manual input switch. 
Additionally, when the system is firing, other modes may be 
shown as described below. Possible MODE values are:

Auto—the R7999 is in automatic operating mode, in which 
the firing rate is (or will be, when the system is firing) 
provided by the CmA input. Auto will be shown even when 
the system is not firing or is getting ready to fire, when the 
R7999 Auto/Manual switch  is in the Auto position.

Manu—the R7999 is in manual operating mode in which 
the firing rate is (or will be, when the system is firing) 
provided by the manual potentiometer. Manu will be shown 
even when the system is not firing or is getting ready to 
fire, when the R7999 Auto/Manual switch is in the Manual 
position.

Lim—the Maximum Firing Rate Limiting feature is enabled 
(a commissioning option) and the R7999 manual 
potentiometer setting is currently limiting the firing rate to a 
value that is less than the CmA input currently requested 
rate.

Hold—the Low Fire Hold feature is enabled (a 
commissioning option) and a Low Fire Hold is currently 
active and is limiting the firing rate, because the XmA input 
is (or has been) below the Enforce threshold and has not 
yet crossed the Release threshold.

HFOn—the system is firing and the firing rate would nor-
mally be provided by either the CmA input (Auto) or the 
Manual Potentiometer input (Manu); however the HF input 
is on so the normal rate request is overridden, and the 
system is, instead, firing at the Purge rate.

LFOn—the system is firing and the firing rate would 
normally be provided by either the CmA input (Auto) or the 
Manual Potentiometer input (Manu); however the LF input 
is on so the normal rate request is overridden, and the 
system is firing at the Lightoff rate.

Rate

The RATE item shown in Fig. 5 is the current firing rate 
request that is driving the R7999. Possible values are shown 
below using dashes to represent the positions where digits 
would appear:

C--%—shows the CmA input current requested rate as a 
percentage of its full scale: 4 mA (0%) to 20 mA (100%) 
range, effective during Auto mode.

M--%—shows the Manual potentiometer currently 
requested rate (0% to 100%), effective during Manu 
operation.

X--%—shows the XmA input current value as a percentage 
of full scale range: 4 mA (0%) to 20 mA (100%), effective 
during a Low Fire Hold when this value is (or has been) 
less than the Enforce threshold and has not yet crossed 
the Release threshold.

P--%—shows the Purge rate (a commissioning setting), 
effective during purging and also when the normal firing is 
overridden because the HF input is on during modulation.

L--%—shows the lightoff rate (a commissioning setting), 
effective during ignition and also when the normal firing is 
overridden because the LF input is on during modulation.

Stop—shows that the system is currently idle and the 
motors have been commanded to their stop positions (as 
set during commissioning).

Status

The STATUS item shown in Fig. 5 shows the R7999 operating 
state. The following are status displays and descriptions:

Startup—the R7999 is starting up.

Initialize—the R7999 is in the initialization stage of its 
startup procedure.

Lockout—a fault has occurred, the Alarm output is 
energized, and the LCO has been turned off. Manual 
intervention is required; the R7999 must be manually reset 
before normal operation will continue.

Alarm-Hold—a fault condition is currently present, the 
Alarm output is energized, and the LCO has been turned 
off. Normal operation will continue if and when the fault 
condition clears (without requiring a manual reset) but the 
R7999 will continue to hold as long as the fault condition 
persists.

Standby—the R7999 is idle, waiting for a demand input at 
the LCI terminal.

M20037

SCROLL

ControLinks™

MODE

RATE

STATUS

Air --  Fuel --  FGR --

LINE 2

Содержание ControLinks S7999

Страница 1: ...ating Status Source of demand control Actuator positions Hold status Total cycles Total hours of operation Run time Fault history of six most recent faults Fault code Fault message Cycles at time of fault Diagnostic information Input Output status Demand control input and position Fuel selection Fuel position Motor settings Light off position of fuel air and FGR purge position of fuel air and FGR ...

Страница 2: ...ating 40 F 40 C to 140 F 60 C Storage 60 F 51 C to 150 F 66 C Humidity 85 percent relative humidity continuous noncondensing Vibration 0 5G environment Mechanical Dimensions See Fig 1 Weight 4 ounces 124 grams unpacked Display 40 character 2 rows by 20 columns Approvals Underwriters Laboratories Inc Component Recognized IRI Acceptable Federal Communications Commission Part 15 Class B emissions EN6...

Страница 3: ...r reaches the saturation point The S7999 ControLinks is designed to operate in a maximum 85 RH continuous noncondensing moisture environment Vibration Do not install the S7999 where it can be subjected to vibration in excess of 0 5G continuous maximum vibration Weather The S7999 is not designed to be weather tight If installed outdoors the S7999 must be protected by an approved weather tight enclo...

Страница 4: ...ting a Display Module 1 Do not route the Display Module wiring in conduits that carry line voltage circuits 2 Avoid routing the Display Module wiring close to ignition transformer leadwires 3 Route the Display Module wiring outside of conduit if properly supported and protected from damage 7 Maximum wire lengths a DM The maximum length interconnecting wire is 4000 ft 1219m 8 Install all electrical...

Страница 5: ...he Manual Potentiometer input Manu however the LF input is on so the normal rate request is overridden and the system is firing at the Lightoff rate Rate The RATE item shown in Fig 5 is the current firing rate request that is driving the R7999 Possible values are shown below using dashes to represent the positions where digits would appear C shows the CmA input current requested rate as a percenta...

Страница 6: ...nd line of the display however when the display is first powered up this area is used to indicate the progress of the initialization of the S7999 display itself Fig 6 Display module LINE2 area during display initialization After the display is first energized or connected it must wait to receive 15 different configuration information records from the R7999 before it is fully functional Although th...

Страница 7: ...entifier for the submenu to appear in the LINE2 area in the top right corner of the display Each submenu item has a left pointing arrowhead to indicate that the change level pushbutton may be used to exit the submenu and return to the top level menu In the top level menu the LINE2 area is blank The toggle button cycles the second line of the display between the main display and whichever second li...

Страница 8: ... Input On Off ON indicates Manual is selected OFF indicates Auto is selected FSelect1 T5 Fuel 1 Input On Off FSelect2 T6 Fuel 2 Input On Off Alarm T7 Alarm Output On Off HFP T8 High Fire Proven Output On Off LFP T9 Low Fire Proven Output On Off HF T10 High Fire Input On Off MV T11 Main Valve Input On Off LF T12 Low Fire Input On Off LCI T13 Limit Control Input On Off LCO T14 Limit Control Output O...

Страница 9: ... XmA Hold is configured as None Purge FGR FGR Actuator position during PURGE On curve Closedb Man Limit Manual Limit configuration setting Enabled Disabledb Indicates if the R7999 was commissioned to enable the Manual Potentiometer to limit the maximum firing rate CL Rev M NvV BBB ControLinks R7999 software revision and build code M major N minor V version BBB build code Display Rev BBB Display S7...

Страница 10: ... Fig 7 through 9 show a lockout condition that illustrates the three display module messages Pressing the scroll or toggle buttons will suspend the cycling of the fault messages until either the buttons are used to return to the main display or 60 seconds elapse with no buttons pressed Special Condition Displays Seven special condition display can be shown that preclude normal system operation as ...

Страница 11: ...NKS DISPLAY MODULE 11 65 0262 Fault Blink Codes and Actions The Fault Blink Codes and respective corrective actions are found in form 65 0238 Fig 10 Display module flush mounting outline M5082B 1 8 in DIA 2 3 175 mm ...

Страница 12: ... Control Home and Building Control Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: