n
The secondary controller of a redundant controller pair is
configured with the even Device Index that is consecutive with its
primary partner’s Device Index (i.e. primary controller Device Index
plus 1)
Set the Device Index (FTE DEVICE INDEX) by turning the three rotary
decimal switches (range 001 to 509). The leftmost switch on top is
used for setting the hundreds digit, the right switch on top is used for
setting the tens digit, and the bottom switch sets the ones digit.
Example: For a redundant pair, the primary and secondary indexes
respectively could be 001, 002; 111, 112; 507, 508 and so on. In a
non-redundant setup, the index could be: 001 or 111 or 507 and so
on.
Failure to replicate the UOC Device Control Index according to their
Control Builder configured Device Indexes will lead to failure in
establishing Control Builder - controller communication thereby
preventing configuration load.
For in-rack redundancy, the left controller is recommended to be
configured as the odd device index and the right controller as the
event device index (of the consecutive device index pair).
Redundancy communication between a pair of redundant UOC is not
possible if their device indices are not set to a consecutive odd/even
pair.
UOC-CPM Indicators
For detailed information on UOC CPM firmware, on how to convert a
PLC CPM into a UOC CPM and on the behaviors of UOC CPM LEDs,
refer to the UOC User’s Guide.
Hardware Configuration of UOC EPM
Refer to the common
section.
Hardware configuration of I/O
Installation and Wiring
Currently, only the ControlEdge 900 UIO is supported. Refer to the
I/O Installation & Wiring section.
46
Содержание ControlEdge 900 platform
Страница 6: ...6 Contents ...
Страница 12: ...12 Chapter 1 About this guide ...
Страница 52: ...52 ...
Страница 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Страница 59: ...59 One Slot Rack ...
Страница 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Страница 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Страница 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Страница 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Страница 125: ...125 Figure 5 33 Analog Input Wiring Eight TCs Figure 5 34 Analog Input Wiring Eight Resistance Inputs ...
Страница 136: ...Settings using input 1 as example Single ended factory setting Differential Figure 5 46 Pulse Counting Wiring 136 ...
Страница 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Страница 138: ...Figure 5 49 Quadrature Differential External Power Wiring Figure 5 50 Quadrature Single Ended External Power Wiring 138 ...
Страница 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Страница 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Страница 148: ...148 ...
Страница 168: ...168 ...
Страница 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Страница 221: ...Appendix A Installing RTP RTP Internal schematic Applies to UAI Figure A 13 Analog Input RTP Internal schematic 221 ...
Страница 222: ...Appendix A Installing RTP 222 ...
Страница 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...