41
Component
Type
Comments
connects to UOC. All device IP addresses must be statically assigned.
For further information, see
EtherNet IP User's Guide_EPDOC-X399-
en-510A.pdf
.
Allen Bradley
OPC Server
from
MatrikonOPC
The Rockwell Allen Bradley OPC Server from MatrikonOPC can be
installed on the Experion Server in systems which incorporate UOC.
The Matrikon OPC Server enables one of two methods whereby
ControlLogix tag names can be used to make UDT references in a
UOC strategy. For further information, see
EtherNet IP User's Guide_
EPDOC-X399-en-510A.pdf
.
Studio 5000
Logix
Designer
Software
Studio 5000 Logix Designer Software from Rockwell Allen Bradley is
used in conjunction with UOC configurations to configure IP
addresses of Rockwell Allen Bradley EtherNet/IP devices. It can also
be used to export a file which defines ControlLogix tag names so that
they can be used in Control Builder to construct UDT data references
from UOC. For further information, see
EtherNet IP User's Guide_
EPDOC-X399-en-510A.pdf
.
While using DLR (Device Level Ring) on Stratix 5700 Switch, DO NOT
CONNECT a DLR network to a Non-DLR port on the Switch. DLR
should be connected only to the DLR ports on the switch. Doing this
will result in the entire down link network going down. The recovery is
to only remove the DLR connection from the switch.
Non-Redundant Star to 900 I/O and EIP Devices
In addition to the DLR ring topology, the UOC can also connect to a
non-redundant star EtherNet/IP network through its ETH3 downlink
port. This allows it to communicate simultaneously with ControlEdge
900 I/O as well as EtherNet/IP-capable I/O, devices and PLCs.
Installation and maintenance of a downlink EtherNet/IP network
must be done in accordance with the best practices of Ethernet
networking in general and EtherNet/IP in particular.
In this topology, CPMs connect through their ETH3 downlink port
with ETH4 port disconnected. EPMs connect through their ETH1 port
with ETH2 port disconnected. An example is shown in the diagram
below.
Содержание ControlEdge 900 platform
Страница 6: ...6 Contents ...
Страница 12: ...12 Chapter 1 About this guide ...
Страница 52: ...52 ...
Страница 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Страница 59: ...59 One Slot Rack ...
Страница 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Страница 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Страница 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Страница 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Страница 125: ...125 Figure 5 33 Analog Input Wiring Eight TCs Figure 5 34 Analog Input Wiring Eight Resistance Inputs ...
Страница 136: ...Settings using input 1 as example Single ended factory setting Differential Figure 5 46 Pulse Counting Wiring 136 ...
Страница 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Страница 138: ...Figure 5 49 Quadrature Differential External Power Wiring Figure 5 50 Quadrature Single Ended External Power Wiring 138 ...
Страница 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Страница 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Страница 148: ...148 ...
Страница 168: ...168 ...
Страница 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Страница 221: ...Appendix A Installing RTP RTP Internal schematic Applies to UAI Figure A 13 Analog Input RTP Internal schematic 221 ...
Страница 222: ...Appendix A Installing RTP 222 ...
Страница 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...