CHAPTER
9
SPECIAL CONDITION OF USE AND
APPROVED STANDARDS
Approval Rating
Certification
Approval Rating
FM
Nonincendive for use in Class I, Division 2, Groups A, B, C & D
Class I, Zone 2, IIC T*
CSA
Class I, Division 2, Groups A, B, C & D T*
ATEX
II 3 G Ex nA IIC T* Gc
Temperature class
(T*):
Module
T3C
900G03
T5
900G32
T4
900H03, 900P01, 900P24, 900RR0, 900CP1, 900SP1, 900U01
T6
900A01, 900H32, 900PSM, 900R04, 900R08, 900R12,
900R08R, 900R12R
Table 9-1: Approval Rating
Special Condition of Use for Division 2/Zone
2 Hazardous Location Installation
For the United States
n
The installer shall provide transient over-voltage protection
external to the apparatus such that the voltage at the supply
terminal of the apparatus does not exceed 140% of the voltage
rating of the equipment.
n
The equipment shall be mounted in an enclosure providing a
minimum degree of protection of IP54 in accordance with
ANSI/IEC 60529., and in a tool-secured enclosure which meets
the requirements of ANSI/ISA 60079-0 and ANSI/ISA 60079-15.
179
Содержание ControlEdge 900 platform
Страница 6: ...6 Contents ...
Страница 12: ...12 Chapter 1 About this guide ...
Страница 52: ...52 ...
Страница 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Страница 59: ...59 One Slot Rack ...
Страница 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Страница 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Страница 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Страница 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Страница 125: ...125 Figure 5 33 Analog Input Wiring Eight TCs Figure 5 34 Analog Input Wiring Eight Resistance Inputs ...
Страница 136: ...Settings using input 1 as example Single ended factory setting Differential Figure 5 46 Pulse Counting Wiring 136 ...
Страница 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Страница 138: ...Figure 5 49 Quadrature Differential External Power Wiring Figure 5 50 Quadrature Single Ended External Power Wiring 138 ...
Страница 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Страница 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Страница 148: ...148 ...
Страница 168: ...168 ...
Страница 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Страница 221: ...Appendix A Installing RTP RTP Internal schematic Applies to UAI Figure A 13 Analog Input RTP Internal schematic 221 ...
Страница 222: ...Appendix A Installing RTP 222 ...
Страница 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...