Compact unit_HON.doc    

 07/2011   

1/5 

Installation Instructions for 
Honeywell COMPACT Air Sampling Smoke Detection System 

 

5

5

5

2

5

1

1

5

5

4

Abb.:A
Fig.: A

3

3

3

 

 

 

1 Connection 

terminals 

Connection pipe system 

3 Filter 

element 

Connection for air return 

Pre-punched cable entries 

 

Installation of the device 

General information: 
 

-  When mounting the device basis make sure the displays of the aspirating smoke detection system are clearly visible. 
-  The air outlet of the device basis must not be blocked (the distance between the air outlet and adjacent objects (e.g. wall) is to be at least 10 cm). 
-  The device basis can be mounted with the aspiration pointing upwards or downwards. The connection for the air sampling pipe is marked with a 

“V” (see fig. A). If the aspiration comes from downwards, make sure no impurities enter the air outlet which then points upwards.  

 

Procedure: 
 

1.  First, clearly mark the fixing points for mounting the device basis at its position. If necessary, use the provided drilling jig.  
2.  Fix the device basis by means of four screws (max. 

 of 4mm) safe to the underground. Make sure the device is not fixed under mechanical 

tension and the screws are not tightened too much.  

 

Содержание compact asd

Страница 1: ...be blocked the distance between the air outlet and adjacent objects e g wall is to be at least 10 cm The device basis can be mounted with the aspiration pointing upwards or downwards The connection for the air sampling pipe is marked with a V see fig A If the aspiration comes from downwards make sure no impurities enter the air outlet which then points upwards Procedure 1 First clearly mark the fi...

Страница 2: ...connection cable s max 2 5 mm2 into the prepared cable entries and wire the devices according to the circuit connections described at the following page Note If the detection unit of Honeywell COMPACT is to be installed at a later stage the mounted device basis can be protected against excessive con tamination by using the bottom of the supplied card box In order to use the bottom of the card box ...

Страница 3: ...pply voltage 2b 0 V Supply voltage 3b Alarm element line fire alarm 4b Alarm element line fire alarm 5b Termination element line fault 6b Termination element line fault 7b Data bus A 8b Data bus B connection for accessories 24V 0V 1a 2a 3a 4a 5a 6a 7a 8a 1b 2b 3b 4b 5b 6b 7b 8b Data bus 24V 0V Data B Data A L1 L1 L1 L1 Reset Data B 24V 24V 0V RA RE RE RA RE Alarm element Termination element Elemen...

Страница 4: ...of conformity has been issued by notified product certification body ID no 0786 VdS The CE designation according to DIN EN 54 20 has been carried out 0786 WAGNER Group GmbH Schleswigstrasse 1 5 30853 Langenhagen 07 Nr 0786 CPD 20322 EN 54 20 2006 Air sampling smoke detector for fire detection and fire alarm systems in buildings 0 1 light obscuration m Class A B and C 0 5 light obscuration m Class ...

Отзывы: