CM67/61NG Chronotherm controls a single heating system compo-

nent such as a boiler, a pump or zone valve. The factory confi gured RF 
link between the room unit and receiver makes the installation process 
fast and easy.

1. START UP

The  CM67/61NG room unit is factory bound with the HC60NG relay 
box. Therefore no initial binding between the room unit ( CM67/61NG) 
and receiver (HC60NG) is required.

1.  Follow the installation diagrams to install and connect the 

power supply to HC60NG relay box. The RF system will com-
mence normal operation immediately.

NOTE:

 If the red LED is fl ashing or if you install a replacement 

relay box or room unit, please follow the procedure described in 
section 

8. BINDING 

before system 

START UP

.

2.  To check the RF communication move the  CM67NG slider into 

OFF 

position (for  CM61NG press the 

OFF 

button) then press the 

TEMP 

 , 

 and 

PROG 2 

buttons for 3 seconds.  The unit will 

display 

tESt 

and it will send test signals to the receiver switching 

the green LED on and off every 5 seconds (relay output will remain 
off) for a maximum of 10 minutes. When the green LED fl ashes 
on/off every 5 seconds proceed to the next step.

NOTE:

 If the green LED is not switched at specifi ed intervals follow the 

procedures described in section 

8. BINDING

.

2. LOCATING THE CM67/61RF ROOM UNIT

1.  Locate the room unit using the same test mode as described in

1. START UP.

 Review the  CM67/61NG location guidelines (see 

installation diagram 

10

) and fi nd a suitable location where the 

signal transmission is reliable. Reliable transmission is indicated 
when the HC60NG relay box is switching the green LED every 5 
seconds. (if the accessory module is applied the room unit must be 
located with the module attached).

2. Install 

the CM67/61NG on the wall using the wall bracket or fi t it 

on the table stand as shown in installation diagram 

11

.

 

NOTE: 

The HC60NG relay will be off.

3.  Exit the TEST mode by moving the  CM67NG slider to the 

MAN 

or 

AUTO 

position (for  CM61NG press 

MAN 

or 

AUTO 

button).

3. SYSTEM CHECK

1.  Switch the boiler on

2. Move 

the CM67/61NG slider to 

AUTO 

or 

MAN 

position(for 

CM61NG press the 

AUTO 

or 

MAN 

button)

3. Adjust 

the CM67/61NG setpoint up to the maximum (30°C) by 

pressing the 

TEMP  

button. The boiler should come on a few 

seconds after the on ‘fl ame’ symbol appears Check the system 
operation changing the setpoint several times, bearing in mind the 
switching delay already referred to.

4. FAIL-SAFE MODE SETUP

The failsafe mode selected defi nes the HC60NG output relay status 
if the RF communication is lost (e.g. when room unit stops to com-
municate due to discharged batteries). The factory setting keeps the 
relay permanently off when communications is lost. If the factory setting 
needs to be changed follow the instructions below:

1. Move 

the CM67NG slider into 

OFF 

position (for  CM61NG 

press the 

OFF 

button). Press and hold the   and 

PROG 3 

4

 

buttons together.

Specifi c Application

Heating

Air-
conditioning

What do I need to change?

 
Note: 
a.  To change Cycle/Hour, please go to parameter n. 9 in the installer set-up mode.
b. 

To change Minimum ON Time, please go to parameter n. 2 in the installer 
set-up mode

No action required

1.  Set Minimum ON Time to 4 minutes.
2.  Set Cycle/Hour to 3.

Set Cycle/Hour to 12.

No action required

Set Cycle/Hour to 12

Gas Boilers (<30KW)

Oil Boiler

Thermal Actuator

Zone Valve

Electric Heating

Heat Pump/Air condi-
tioner

Fan Coil

Move the  CM67NG 
slider into the 

OFF 

position (for  CM61NG 
press the 

OFF 

button).

Press and hold the   
and 

PROG 3

 & 

4

 but-

tons together.

Press 

TEMP 

 or 

 to change factory 

setting.

The display will fl ash 
indicating that a 
change has been 
made.

Press INFO   button 
to confi rm the 
change is ok.

The display will stop 
fl ashing indicating 
that the new value 
has been stored.

Adjust other settings using the Installer 

Set-Up Mode - 

Settings Table

 on the next page.

To exit the 

Installer Set-Up Mode

 move the  CM67NG slider 

to the 

AUTO 

or 

MAN 

position (for  CM61NG press the 

AUTO 

or 

MAN 

button).

Installer Set-Up Number

(Press 

 

+

 or 

-

 to change)

e.g. 

= Optimisation

Abbreviated Set-Up Description

e.g. 

OP

 = Optimisation

Factory Setting or New Choice

(Press 

TEMP 

 or 

 to change)

e.g. 

= optimisation disabled

e.g. 

= optimisation enabled

Installer Set-Up Mode 

Selected

Category 1 Installer Set-Ups

3. PARAMETERS SETTING

Press 

 

+

 or 

-

 to go 

to the next parame-
ter and follow steps 
3 & 4 to make 
changes.

Setting

 Cycle/  Minimum
 Hour  ON 

Time

 6 

1

 3 

4

 12 

1

 6 

1

 12 

1

 3 

4

 6 

1

1

2

3

4

5

6

7

NOTE:

2. Press 

the 

PROG 2

 button to enter the category 2 parameters. 

Select the parameter 16:LC by pressing 

 

+

 or 

-

 button.

3.  Select the fail-safe mode by pressing 

TEMP 

 or 

  buttons.

 

0 - when RF communication is lost the relay will be held in OFF 
position.

 

1 - when RF communication is lost the relay output will cycle at 
20% on 80% off. 

 

IMPORTANT:

 

- To enable the frost protection when RF communication is lost 
select the fail-safe mode 1.

 

- For systems with separate frost protection thermostat or where 
frost protection is not required select fail-safe mode 0 .

4. Confi rm the selected value by pressing the   button.

5.  Attach appropriate label to the HC60NG relay box to indicate the 

selected fail-safe mode.

5. AUTOMATIC OPERATION

HC60NG receives the heat (or cool) demand (0-100%) signal from 

CM61/67NG. The room unit will display the   symbol whenever more 

heat is required. Depending on the demand the HC60NG will switch 
the heating (or cooling) device on to match the current requirements 
of the system.

The green LED indicates status of the relay output.

Green LED on - relay on

Green LED off - relay off

6. TEMPORARY MANUAL OVERRIDE

Pressing the HC60NG button will override the current relay position. As 
soon as next signal is received from the room unit the HC60NG will 
return back to automatic operation as the automatic control has higher 
priority than manual operation

7. COMMUNICATION LOSS

When the RF communication is lost for a period of 1 hour the red 
LED will be switched on to indicate that no RF messages have been 
received during the last hour.

The HC60NG will also enter the failsafe mode as selected in Installer’s 
Mode (see 

4. FAIL-SAFE MODE SET UP

).

To allow manual control of the HC60NG output manual override is 
available in fail-safe mode. When RF communication is restored the 
HC60NG will automatically return to normal operation.

8. BINDING

The binding operation described below is required if:

 

- any of the system components (room unit or relay box) are 
replaced

 

- HC60NG has incorrect or no binding data stored (e.g.  when 
pre-bound system pack components have been mismatched)

During the binding procedure keep approximately 1m distance 
between the room unit and the relay box.

1.  Press and hold the HC60NG push button for 15 sec to reset 

previously stored data. The red LED will start to fl ash at 0.1 s 
on/0.9 s off. Release the push button.

2.  Press and hold the HC60NG push button for 5 sec to enter the 

binding mode. Red LED fl ashing at 0.5s on/0.5 s off confi rms the 
binding mode has been entered.

3. Move 

the CM67NG slider to the 

OFF 

position (for  CM61NG 

push the 

OFF 

button) and press the 

TEMP 

 , 

 and 

PROG 

buttons together

4. Press 

the  button to send the binding signal. The red LED is 

switched off to confi rm successful binding operation. If red LED 
still fl ashes push the   button again until binding is successful.

5. Follow 

the 

START UP

 and other procedures to commission the 

single zone RF system.

A. SINGLE ZONE RF SYSTEM

B. INSTALLER SET-UP MODE

Honeywell

CM67/61NG Room Unit

& HC60NG Relay Box

INSTALLATION GUIDE

1

2

3

8

9

10

11

Once you have inserted the battery compartment, 
after a pause the unit will display information. If this 
does not happen or the display shows the 

 

symbol please refer to the ‘trouble shooting’ section 
in the  CM67NG or  CM61NG user guides.

HC60NG is a Radio Frequency (RF) device. For the 
best performance install in an open space. Leave at 
least 30cm distance from any metal objects including 
wall boxes and boiler housing.

Do not mount on metal wall boxes.

The  CM67/61NG is a radio frequency device and for the best performance should 
be installed in an open space.  Leave at least 30cm distance from any metal objects 
including wall boxes and at least 1 metre from any other electrical equipment eg. 
radio, TV, PC etc. 

Do not mount on metal wall boxes.

It is recommended that the HC60NG relay box is installed before commencing with 
the Room Unit installation.

NG

5

Optional Accessory

Automatic Time Setting (ATS) 
Module

Description

The ATS module picks up daily the radio fre-
quency time signal so you never need to set or 
adjust the time

What do I need to do if I wish to use this feature

1.  Fit the ATS module

2.  Set the parameter 4:At in the installer set-up 

mode to 1

3. Repeat 

the 

SYSTEM CHECK

 procedure 

1.  For cooling application only, set the Chronotherm to cooling (set parameter n.6 in the installer set-up mode to 0)
2.  For heat/cool application, set the Chronotherm accordingly to required mode of operation by changing parameter n.6 

in the installer set-up mode.

 

Explain to the end-user how to implement the change-over and ensure that the appropriate time and temperature 
profi le is established for heating and cooling

3.  CM67/61NG can only be used for single zone cooling applications (no zoning for cooling allowed)

1.  Set Minimum ON Time to 4 minutes.
2.  Set Cycle/Hour to 3.

No action required

1. SPECIFIC APPLICATION GUIDELINES

2. ADD-ON MODULE

IMPORTANT NOTE 1:

CM60RFNG room unit and HC60NG receiver operate 
on 868MHz frequency. They will not communicate with 
other RF products using different frequency or com-
munication protocol

NOTE:

HC60NG contains no user serviceable parts. It should 
be opened and installed by qualifi ed installer only.

WARNING:

Electrostatic sensitive device! Do not touch the circuit 
board.

Installer Set-Up Mode allows changing the controller parameters so it can meet specifi c application requirements or customer’s needs. See 

4. 

INSTALLER SET-UP MODE TABLE

 for detailed list of confi gurable parameters.

42010477-001 R1

4

6

7

NOTE:

 Install in accordance with local wiring regulations

CAUTION:

 Observe ambient temperature and current limits (see HC60NG wiring label)

> 7mm Ø

< 7mm Ø

a

b

a

b

max. 2.5mm²

a. Burner (direct control)

b. Combi boiler

c. Thermal actuator

d. Zone valve

g. Electric actuator

h. Cooling device

f. Electric heater

e. Zone valve

IMPORTANT NOTE 2:

CM67/61NG can be used for two different applications

1. to control stand alone heating device (e.g. boiler, 
pump, zone valve).
or
2. as a part of multi-zone control system.

If you intend to use it as defi ned in point 1 - read part 

A. 

SINGLE ZONE RF SYSTEM

 fi rst

If you intend to use it as defi ned in point 2 - read part 

D. 

MULTI-ZONE RF SYSTEM

 fi rst