CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
73
CGW-MB Active Event Code
Modbus Communications
7.29 CGW-MB Active Event Code
All events are mapped into Modbus event categories which are stored in the Modbus
register.
0x0A
Unit ID specified in the request packet is not configured
for monitoring.
CLSS Gateway
mainboard path
failed
0x0B
FACP is off line or there is a communication problem on
the panel and/or NFN.
CLSS Gateway
mainboard
target failed
Table 7.37: Exception Codes
Table 7.38: Event Type Categories
Event
Modbus
Register
Value
No Active Status (see note)
00H
Mass Notification Alarm, High Priority
05H
Fire Alarm
10H
Security Alarm (Life)
11H
Critical Process Alarm (Life)
12H
Medical Emergency (Life)
13H
CO Alarm
14H
Mass Notification Alarm, Low Priority
15H
Security Alarm (Property)
20H
Critical Process (Property)
21H
Mass Notification Supervisory, High Priority
25H
Supervisory Signal (Guard’s Tour)
30H
Supervisory Signal (Equipment)
40H
Mass Notification Supervisory, Low Priority
45H
Disabled Alarm (AFP2800 Panel Only)
52H
Disabled Active (AFP2800 Panel Only)
55H
Non-Fire Activation
71H
Non-Fire Activation (no acknowledgment
required)
72H
CO Alarm & Fire Alarm
EAH
CO Supervisory
EBH
CO Supervisory & Photo Supervisory
ECH
CO Supervisory & Fire Alarm
EDH
CO Alarm & Photo Supervisory
EEH
Device Not Present
FFH
For Gamewell-FCI
General Alarm
18H
Gas Alarm
22H
CO Supervisory
42H