USER GUIDE
FALCON
69
EN2Z-0962GE51 R0715
Input pulses from utility meters (gas, water, heat, etc.) transmitted via LonWorks can
be connected to pulse converter inputs using the property "Scaling Factor". The
pulses supplied by the meters are multiplied by the scaling factor and are then ready
to be read as pure consumption values. The "Scaling Factor" thus always indicates
the value of each pulse received.
The adjustable range is 0.0 through 100,000,000.0,
The number of decimal places depends on the selected engineering unit.
Example: A heat meter supplies 10 pulses per kWh "consumed". Accordingly, the
scaling factor (= value of a pulse) is 0.1 kWh/pulse.
State Text
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
x
Equivalent
State Texts
Multistate datapoints allow switching 256 states (stages) including the “off stage" of
physical digital inputs or outputs. For each state, a state text can be created and
assigned to the point in CARE. The state text is displayed on the Excel Web HTML
Interface when the point switches the input or output to the corresponding state
(stage).
Example: Multi-stage fan with state texts: stage 1, stage 2, stage 3, etc.
States
See "#States and State Text" sections.
#States
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
x
Equivalent
States
Shows the number of states of a multi-state datapoint.
Time Delay
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
x
x
Equivalent
Alarm Delay
The time delay determines how long a ´To-Off-Normal` or a ´Back-To-Normal`
transition must exist before an event enrollment alarm is sent to the recipient.
Entering a time delay of 10 seconds means that the limit value must be exceeded
for at least 10 seconds before this event enrollment sends an event notification to
the recipient. If the limit value only lasts for 7 seconds, then no event notification is
sent.
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...