FALCON
USER GUIDE
EN2Z-0962GE51 R0715
68
Equivalent
Defines the value that will be written to the present value, if the priority list is empty
which means that no other value is present in the priority list. The relinquish default
value allows starting up a control system with a defined status/value. The relinquish
default value is predefined in the application in CARE and can be changed in the
Excel Web HTML Interface.
For further information on priority levels and command priorities, please refer to the
"Priority Level" section.
Reporting
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
x
x
Equivalent
Transition Events
Defines, which transition type will be reported, that is, which transition should be
saved in the alarm buffer and in the alarm list in the HTML Interface.
See also "Transition Events" section.
Reset to
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
x
Equivalent
Resets the current value of the pulse converter or the runtime counter of a binary
output to a specific value. The counting will restart.
See also "Current Value" section.
Runtime (Active Time)
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
"Reset to"
Equivalent
Shows the runtime of the connected device. The runtime (active time) can be
changed by reset.
The runtime can be reported as follows:
In CARE, use the IDT statement to read the ´Elapsed Active Time` property of a
datapoint. Compare this value to a limit value and use an additional point to report
an alarm.
Scaling Factor
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
x
Equivalent
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...