Priority Level
Value
16
-
Relinquish Default
20,0 °C
The priority list can include max. 16 values and will be continuously updated by
written values caused by the command-issuing entities.
The value of the highest priority level is always written to the present value as long
as the priority list is not empty. If the list is empty, the user-definable relinquish
default value is written to the present value.
For the example in the table, Critical Equipment Control has the highest priority and
is written to the present value. As soon as the priorities 5 and 8 are relinquished e.g.
via BACnet service, the relinquish default of 20,0°C will be valid for the present
value.
Polarity
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
x
Equivalent
The polarity indicates the relationship between the physical state of the input and
the logical state represented by the present value. If the polarity is NORMAL, then
the ACTIVE state of the present value is also the ACTIVE or ON state of the
physical input. If the polarity is REVERSE, then the ACTIVE state of the present
value is the INACTIVE or OFF state of the physical Input.
Polarity
Present Value
Physical State of Input
Physical State of Device
NORMAL
INACTIVE
OFF or INACTIVE
not running
NORMAL
ACTIVE
ON or ACTIVE
running
REVERSE
INACTIVE
ON or ACTIVE
not running
REVERSE
ACTIVE
OFF or INACTIVE
running
Property
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
Equivalent
By default, the present value is selected as property of a reference input point in
CARE.
Read Access Level
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
x
Equivalent
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...