USER GUIDE
FALCON
113
EN2Z-0962GE51 R0715
TIME PROGRAMS
Schedules and Calendars
Time programs comprise schedules and calendars.
Schedules
Schedules are daily and weekly time programs.
Whenever you want, you can use schedules to enter the setpoint or status for any
datapoint.
Schedules are assigned to plants. Each plant of a controller can have multiple
schedules assigned and each schedule can command datapoints of that plant.
Each schedule specifies a list of datapoint properties to command (switchpoints) on
a weekly basis. The week program defines the normal daily activity of the system by
specifying which switchpoints are to be commanded each day of the week. The
week program applies to a definable time period. There is only one week program
per schedule.
Schedules offer 16 write priorities that define the priority for writing to the present
value of output and value datapoints. Note, that only the priorities 9 to 16 are
allowed in the controller.
Besides the week program, specific programs called exceptions can be created.
Exceptions have higher priority than the week program and will overwrite the week
program for a definable time period. Exceptions can have four different time periods:
•
Specific Date
e.g. Christmas Eve or 5.5., the whole of May, or the whole year of 2004
•
Date Range
e.g. Summer holidays from 29.7-7.9.2004
•
Recurring Event
e.g. every last Friday of every month
•
Calendar Reference
A project-wide calendar provides dates, e.g. regional holidays and
public/religious festivals or any other particular date. The time period can be a
specific date, a date range or a recurring event.
Calendars
Calendars are assigned to a whole project. They contain exception days or periods,
e.g. Christmas, holidays.
If controller schedules are referring to the same calendar(s), project wide scheduling
is possible for these controllers, because calendar dates are executed in each
controller of the project, which has references to the calendar. Changes in multiple
particular controller schedules can be quickly made by simply changing the
referenced calendar(s).
Switchpoints / Switched Properties
By default, the property ´present value` is assigned to a datapoint. Hence, when
switching a datapoint, the present value of the datapoint is switched. This is the
standard case. In addition, in enhanced case, multiple datapoints and or other
properties than the present value can be switched.
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...