background image

 

I

I

n

n

t

t

e

e

l

l

l

l

i

i

P

P

a

a

t

t

h

h

T

T

M

M

 

 

S

S

e

e

r

r

i

i

e

e

s

s

 

 

C

C

D

D

M

M

A

A

 

 

C

C

o

o

m

m

m

m

u

u

n

n

i

i

c

c

a

a

t

t

o

o

r

r

 

 

C

C

D

D

M

M

A

A

-

-

X

X

 

 

s

s

u

u

p

p

p

p

o

o

r

r

t

t

s

s

 

 

t

t

w

w

o

o

-

-

w

w

a

a

y

y

 

 

v

v

o

o

i

i

c

c

e

e

 

 

 

 

I

I

n

n

s

s

t

t

a

a

l

l

l

l

a

a

t

t

i

i

o

o

n

n

 

 

a

a

n

n

d

d

 

 

S

S

e

e

t

t

u

u

p

p

 

 

G

G

u

u

i

i

d

d

e

e

 

 

 

 
 

 

 
 
 
 
 
 

 

 

800-18819  4/15  Rev. A  
 

Содержание CDMA-X

Страница 1: ...Se er ri ie es s C CD DM MA A C Co om mm mu un ni ic ca at to or r C CD DM MA A X X s su up pp po or rt ts s t tw wo o w wa ay y v vo oi ic ce e I In ns st ta al ll la at ti io on n a an nd d S Se et tu up p G Gu ui id de e 800 18819 4 15 Rev A ...

Страница 2: ...720P Programming Tool 7 Programming Conventions 8 Using the Control Panel 8 Programming for ECP Mode 8 Programming for 4204 and Two 4204 Emulation Modes 8 4204 Emulation Mode Options 8 Programming Options 9 ECP Status Codes 14 Exiting the Programming Mode 14 Setting Factory Defaults 15 Registering the Communicator 15 Registering through the AlarmNet Direct Website 15 Remote Services 15 Registering...

Страница 3: ...atus messages via CDMA network Internal antenna provides additional security Simple programming using the 7720P programming tool or via the AlarmNet Direct website Uses 2 way ECP communication with the control panel Sends reports in Contact ID format Supports remote control of alarm system via Remote Services feature Allows uploading and downloading of control panel data via CDMA network Fully pow...

Страница 4: ...t gov groups STM cavp documents aes aesval html and search for Certificate number 979 Remote Services Features NOTE Remote Access and Multi Mode have not been evaluated by compliance agency Honeywell offers secure web based services that enable users to remotely monitor and control their security system These web services enable users to Monitor and control their security system from a website Rec...

Страница 5: ...s service click on Dealer Signup from the login screen to set up your dealer account You will be instructed how to proceed upon completing the sign up form Only one sign up per dealer is required Once an initial user is established additional logins may be created by that user Log in and follow the on screen prompts At this time only activate the communicator so signal strength may be checked DO N...

Страница 6: ...ntrol panel cabinet 2 Open the communicator cover Remove the external antenna port cap attached to the plastic trim as necessary and snap it into the external antenna cable port at the top of the enclosure 3 Remove the bottom knockout on the enclosure for the threaded mount Then install the threaded mount so it snaps into the plastic retaining tabs Mount the communicator assembly on the cabinet s ...

Страница 7: ...udio Verification System 2 Connect one end of the audio cable 5 pin connector to the audio connector located on the PC board in the communicator 3 Route the audio cable to the connector on the AVS Base Unit and connect the cable 4 pin connector 4 Ensure the audio cable ends are secured with tie wraps to reduce strain NOTE For compliance agency CDMA X and AVS must be located in the same room or wit...

Страница 8: ...ng to the control panel A control panel knockout that is presently used can be utilized however DO NOT utilize a control panel knockout that is being used for primary power 6 Refer to the installation guide for the control panel and complete the ECP cable wiring 7 Secure the wiring with ties as necessary Programming the Module The CDMA X requires an AlarmNet account For new installations please ob...

Страница 9: ...hift function press the shift key then press the appropriate key The following table lists each normal and shift key function 7720P Normal and Shift Key shift LED lit Functions KEY NORMAL KEY FUNCTION SHIFT KEY FUNCTION BS ESC BS Press to delete entry ESC Press to quit program mode also can reset programming defaults Scroll down programming Scroll up programming N Y N Press for NO answer Y Press f...

Страница 10: ...ode Denied The default programming values for each prompt are shown in parentheses in the PROMPTS column Further the Programming Options table next page shows all the prompts for this programming mode Depending on your answers unnecessary prompts will be bypassed and you will advance to the next appropriate prompt Programming for 4204 and Two 4204 Emulation Modes In this mode the communicator emul...

Страница 11: ... position for the respective zone e g alarm on zone 2 5155 5555 7 restore 5355 5555 7 A supervision fault trouble message is automatically sent if the communicator detects no activity on its connection to the control panel The message is 5555 5515 5 restore message is 5555 5535 5 Programming Options PROMPTS ENTRY OPTIONS DESCRIPTION 1 Strt Prog Mode Y N _ Y N Enters programming mode 2 Enter Passwo...

Страница 12: ...rced so the user can be notified of up to four events or choose 2 4204 Sourced so the user can be notified of up to eight system events The 4204 relay events used to trigger email notifications are defined on the Honeywell Total Connect website and must correspond to outputs relays programmed in the control panel through Output Device programming The Multi Mode address selected at prompt 11 in the...

Страница 13: ...s controlled by the dealer via the web based programming tool on the AlarmNet Direct website 18 Keypad Address 28 _ 01 30 NOTE This prompt will only appear if the Remote Access feature has been enabled Must be programmed if using the Remote Access feature Enter the appropriate device address 19 Supervision 24 Hours _ 24 Hour None 30 Day The AlarmNet network must hear at least one supervisory messa...

Страница 14: ...e zone 2 4204 Mode If any zone is programmed for report only if armed zone 8 cannot be used NOTE Connect an open close arm disarm trigger or relay output from the control panel to the open close zone 24 Restore Zn1 Y N Y only 4204 2 4204 Y N Enables restore reporting for zone 1 25 Delay Zn1 secs 00 only 4204 2 4204 01 15 00 no delay Defines the reporting delay in seconds for zone 1 26 Rpt Zn1 ONLY...

Страница 15: ...r zone 5 38 Rpt Zn5 ONLY if Armed N only 2 4204 Y N Reports alarms on zone 5 ONLY if the conditional zone zone 4 in 4204 mode or zone 8 in 2 4204 mode is triggered armed If N always reports alarms on zone 5 39 Restore Zn6 Y N Y only 2 4204 Y N Enables restore reporting for zone 6 40 Delay Zn6 secs 00 only 2 4204 01 15 00 no delay Defines the reporting delay in seconds for zone 6 41 Rpt Zn6 ONLY if...

Страница 16: ... be displayed The control panel will display a fault message if any of the events listed below occur Module lost communications with the control panel Module lost contact with AlarmNet Module is not registered account not activated Module shutdown In addition the Contact ID codes for some of these conditions are reported by the control panel and sent by AlarmNet to the central station Exiting the ...

Страница 17: ...tation as E339 803 The description may read Trouble Exp Mod Reset If registration is not validated within 90 seconds the communicator times out and the REG green LED will be lit solid Registering through the AlarmNet Direct Website To register the communicator via the website go to https services alarmnet com AlarmNetDirect Log in and follow the on screen prompts If you are not signed up for this ...

Страница 18: ...ion is complete press the Shift plus the up arrow on the 7720P The registration message is sent and the unit waits for the acknowledgment Registration SUCCESS If this is a new installation and the city central station and customer numbers have been correctly entered the communicator is registered and this message is displayed The communicator is now in full service and available for alarm reportin...

Страница 19: ... the central station including a city code CSID and subscriber ID When Instructed to do so triple click the TEST MESSAGE REGISTRATION switch Diagnostic Commands The 7720P programming tool can be used to view the connectivity settings and options To invoke diagnostic commands such as A B C etc the shift key MUST used For example shift A displays the software revision Module Identification Displays ...

Страница 20: ...o Access Network 1X or IS 95A Ec I0 Ratio of channel power to traffic power roughly equivalent to noise ratio A number closer to zero is better Very Good Good Fair 0 1 2 3 4 5 6 7 8 9 10 11 Poor High Noise 11 12 13 14 15 16 17 17 19 20 Press the space key to get to the next screen Press the backspace key to go to the previous field SID NID xxxx xxxxx Status Display Screen 3 SID System Identificati...

Страница 21: ...g PIN 0 Force Server Update Y N Force Upload of Configuration File to Server Pressing Y will force the device to upload its entire configuration file to the server Pressing N cancels the operation NOTE If the communicator is not initialized when you enter this command the following screen will be displayed Cannot Upload Try Later _ Wait for the SIGNAL green LED to light indicating the communicator...

Страница 22: ...anced Console Protocol is a proprietary bus used in Honeywell control panels to communicate with keypads and peripheral devices It uses four wires power ground data in data out IMEI International Mobile Equipment Identity number LRR Long Range Radio an older term now referred to as communicator A broader term communications module or communications device may also be used MAC ID Media Access Code ...

Страница 23: ...OW BLINK In unison with green LED Registration in progress PERIODIC BLINK Module has been deactivated in roaming coverage FAULT red ON No contact with network OFF Normal SLOW BLINK Loss of communication with the panel ECP fault FAST BLINK No network contact AND loss of communication with the control panel PERIODIC FLASH Module has been deactivated in roaming coverage SIGNAL STRENGTH green ON Minim...

Страница 24: ...vision receiver away from the receiver control Move the antenna leads away from any wire runs to the receiver control Plug the receiver control into a different outlet so that it and the radio or television receiver are on different branch circuits Consult the dealer or an experienced radio TV technician for help FCC STATEMENT This device complies with Part 15 of the FCC Rules Operation is subject...

Отзывы: