Honeywell C7735A1000 Скачать руководство пользователя страница 1

INSTALLATION INSTRUCTIONS

69-1521EFS-01

C7735A1000 Duct Air

Temperature Sensor

APPLICATION

The C7735A1000 Duct Air Temperature Sensor (DATS) 

is a duct-mounted temperature probe used to sense 

discharge air temperature in zoning applications for high 

and low temperature limit protection.  Alternatively, it is 

used with certain Honeywell thermostats for delta-T 

diagnostics and IAQ control.  For more on these 

applications, please see the installation instructions for 

those products.

Fig. 1. C7735A dimensions in in. (mm).

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazard-

ous condition. 

2.

Check the ratings given in the instructions and on 

the product to make sure the product is suitable for 

your application. 

3.

Installer must be a trained, experienced service 

technician.

4.

After completing installation, use these instructions 

to check out the product operation.

IMPORTANT

Do not locate the DATS probe in a duct near the 

heat exchanger or strip heat, which can cause 

false temperature readings.

1.

Assemble the DATS by attaching the metal sensor 

probe to the plastic cap. Insert the plate of the 

probe into the two tabs on the inside bottom of the 

cap. Then rotate the plate clockwise until it clicks 

into the single top tab.

2.

Locate the DATS on the supply trunk between the 

bypass damper and the evaporator coil and/or heat 

exchanger. If a bypass damper is not used, locate 

the DATS between the zone dampers and the 

evaporator coil and/or heat exchanger. See Fig. 2.

Fig. 2. DATS mounting location.

3.

Drill a 1/4 in. hole in the duct at the location 

selected for the sensor.

4.

Attach wire using wire nuts and push them into the 

cover, then insert the probe into the hole drilled in 

step 2.

5.

Secure the DATS to the side of the duct, through 

the two mounting holes, with the screws supplied.

IMPORTANT

Use 18-22 gauge thermostat wire for shorter 

runs. For longer runs or when wiring near volt-

age, use shielded cable.

6.

Run wire to zone panel or thermostat. See zone 

panel or thermostat installation instructions.

M33115

2-7/16 (62)

1-1/32

(26)

3-15/16 (100)

2-7/16

(62)

ZONE DAMPERS

BY PASS DAMPER

PLACE SENSOR 

INTHIS AREA.

DO NOT

PLACE

SENSOR IN

THIS AREA.

M14877A

EVAPORATOR COIL

HEAT EXCHANGER

BLOWER

Содержание C7735A1000

Страница 1: ...heat which can cause false temperature readings 1 Assemble the DATS by attaching the metal sensor probe to the plastic cap Insert the plate of the probe into the two tabs on the inside bottom of the cap Then rotate the plate clockwise until it clicks into the single top tab 2 Locate the DATS on the supply trunk between the bypass damper and the evaporator coil and or heat exchanger If a bypass dam...

Страница 2: ... 6311 97 6164 98 6022 99 5883 100 5748 101 5617 102 5488 103 5363 104 5242 105 5123 106 5008 107 4895 108 4786 109 4679 110 4575 111 4473 112 4374 113 4278 114 4183 115 4092 116 4002 117 3915 Temperature F Resistance 118 3830 119 3747 120 3666 121 3587 122 3510 123 3435 124 3362 125 3290 126 3221 127 3153 128 3086 129 3021 130 2958 131 2896 132 2836 133 2777 134 2720 135 2664 136 2609 137 2555 138...

Страница 3: ...ant la sonde en métal au capuchon en plastique Insérer la plaque de la sonde dans les deux languettes à l intérieur du bas du capuchon Faire ensuite tourner la plaque dans le sens horaire jusqu à ce qu elle s enclenche dans la languette supérieure unique 2 Placer le capteur de température d air de gaine sur le bloc d alimentation entre le registre de dérivation et le serpentin d évaporation et ou ...

Страница 4: ... 92 6937 93 6774 94 6615 95 6461 96 6311 97 6164 98 6022 99 5883 100 5748 101 5617 102 5488 103 5363 104 5242 105 5123 106 5008 107 4895 108 4786 109 4679 110 4575 111 4473 112 4374 113 4278 114 4183 115 4092 116 4002 117 3915 Température F Résistance 118 3830 119 3747 120 3666 121 3587 122 3510 123 3435 124 3362 125 3290 126 3221 127 3153 128 3086 129 3021 130 2958 131 2896 132 2836 133 2777 134 ...

Страница 5: ... sonda detectora de metal a la tapa plástica Inserte la placa de la sonda en las dos pestañas en la parte inferior interna de la tapa Luego gire la placa en el sentido de las manecillas del reloj hasta que haga clic en la pestaña sencilla superior 2 Ubique el DATS en el circuito de suministro entre el regulador desviador y el serpentín del evaporador y o el intercambiador de calor Si no se utiliza...

Страница 6: ...08 4786 109 4679 110 4575 111 4473 112 4374 113 4278 114 4183 115 4092 116 4002 117 3915 Temperatura F Resistencia 118 3830 119 3747 120 3666 121 3587 122 3510 123 3435 124 3362 125 3290 126 3221 127 3153 128 3086 129 3021 130 2958 131 2896 132 2836 133 2777 134 2720 135 2664 136 2609 137 2555 138 2503 139 2452 140 2402 141 2353 142 2306 143 2259 144 2214 145 2170 146 2126 147 2084 148 2043 149 20...

Страница 7: ...SENSOR DE TEMPERATURA DE AIRE DEL CONDUCTO C7735A1000 7 69 1521EFS 01 ...

Страница 8: ...y control desenlace Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com Marca Registrada en los Estados Unidos 2011 Honeywell International Inc todos Los Derechos Reservados 69 1521EFS 01 M S 10 11 Impreso en Estados Unidos ...

Отзывы: