Honeywell C7632A Скачать руководство пользователя страница 1

PRODUCT DATA

63-2615-07

C7632A,B 

Sensor and Controller

CARBON DIOXIDE SENSOR

APPLICATION

The C7632 Sensor and Controller is a stand-alone carbon 

dioxide (CO

2

) sensor for use in determining ventilation 

necessity with heating ventilation and air conditioning 

(HVAC) controllers. The C7632 measures the CO

2

 

concentration in the ventilated space or duct. The C7632 is 

used in HVAC systems to control the amount of fresh 

outdoor air supplied to maintain acceptable levels of CO

2

 in 

the space.

FEATURES

• Non-Dispersion-Infrared (NDIR) technology used to 

measure carbon dioxide gas.

• Special plated sensor provides long-term calibration 

stability.

• Device provides voltage output based on CO

2

 levels.

• Used for CO

2

 based ventilation control.

• Automatic Background Calibration (ABC) algorithm 

based on long-term evaluation reduces required 

typical zero-drift check maintenance.

• Fixed 0 to 10 Vdc from 0 to 2000 ppm. No 

adjustments are necessary.

• Compatible with Honeywell Excel 10, 15, 5000, and 

any controller requiring 0-10 Vdc input.

SPECIFICATIONS

Models: 

C7632 Sensor and Controller. A stand-alone car-

bon dioxide (CO

2

) sensor with one 0-10 Vdc analog out-

put.

C7632A: Wall mount model.

C7632B: Duct mount model.

Dimensions:

C7632A: See Fig. 1.

C7632B: See Fig. 2.

Ambient Ratings:

Temperature:

Operating: +32°F to +122°F (0°C to +50°C).

Storage: -4°F to +158°F (-20°C to +70°C).

Relative Humidity (non-condensing): 0 to 95 percent.

Automatic Background Calibration (ABC) default: 

On.

Electrical Ratings:

Power Supply: 24 Vac ±20%, 50/60 Hz (Class 2).

Maximum Power Consumption:

Average: 1W.

Peak: 2W.

Peak Current (at 20 ms): 300 mA.

Linear Analog Output: 0-10 Vdc.

Mounting:

C7632A: Vertical surface with standard single-gang junction 

box.

C7632B: Sheet metal duct with a sampling tube.

CO

2

 Pressure Dependence: 

1.6% change in reading per 

1 kPa deviation from 100 kPa.

Output: 

Analog: 0-10 Vdc, 0-2000 ppm (fixed).

Sensor Performance Ratings:

Response Time: 1 min.

Carbon Dioxide Sensor:

Operation: Non-dispersive infrared (NDIR).

Sampling: Diffusion.

Range: 0 to 2000 ppm (fixed).

Annual Drift: ±10 ppm (nominal).

Accuracy: ±(30 ppm+2%) at normal temperature/pres-

sure.

Calibrated at the factory.

Uses automatic background calibration. No calibration 

required for the life of the product.

Meets CEC Title 24 requirement of ±75ppm accuracy at 

600ppm and 1000ppm ambient levels.

For proper CO2 operation, install only in spaces that see 

at least 4 hours of continuous unoccupied time per 

week.

C7632A

C7632B

Содержание C7632A

Страница 1: ... sensor with one 0 10 Vdc analog out put C7632A Wall mount model C7632B Duct mount model Dimensions C7632A See Fig 1 C7632B See Fig 2 Ambient Ratings Temperature Operating 32 F to 122 F 0 C to 50 C Storage 4 F to 158 F 20 C to 70 C Relative Humidity non condensing 0 to 95 percent Automatic Background Calibration ABC default On Electrical Ratings Power Supply 24 Vac 20 50 60 Hz Class 2 Maximum Powe...

Страница 2: ...fter installation is complete check out product operation as provided in these instructions IMPORTANT All wiring must agree with applicable codes ordinances and regulations CAUTION Health Hazard Improper use can create dangerous situations Use in application for sensing carbon dioxide only For life safety applications this device can function only as a secondary or lesser device CAUTION Electrical...

Страница 3: ...IMPORTANT Ensure largest tab at tube control end is at the top 2 Insert tube into duct attach using screws and wash ers IMPORTANT Leakage into the duct or the C7632 box cover from the room will skew the sensor readings Ensure the box cover and duct seal completely 3 Place o ring on tube end mount the control to the tube Fig 4 Junction box mounting C7632A Fig 5 Duct mounting C7632B WIRING FIG 6 CAU...

Страница 4: ... NOTE The device should now provide accurate out put 4 Check the output signal See Checkout section 5 Reinstall the device Background Calibration 1 Remove the sensor cover and set it aside 2 Ventilate the area and reduce occupancy to lower the CO2 levels 3 Maintain a reasonable proximity from the sensor to avoid breathing on it thus skewing calibration accu racy 4 Keep the sensor in this environme...