Honeywell C7600B Скачать руководство пользователя страница 1

PRODUCT DATA

® U.S. Registered Trademark
© 2004 Honeywell International Inc.
 All Rights Reserved 

63-2166—8

C7600B, H7655A

Solid State Humidity Sensors

APPLICATION

C7600B, H7655A Solid State Humidity Sensors senses the 

relative humidity level of an area and is used with any 

controller capable of processing a 0-10 Vdc or 2-10 Vdc 

signal.

FEATURES

• Long-lasting solid state sensing element is accurate 

and stable over time.

• Enclosed in rugged, wall-mounted plastic case.
• Vents on top and sides of cover allow air flow to 

humidity sensing element.

• Compact size and lightweight construction provide 

easy mounting.

• C7600B provides 2-10 Vdc output directly proportional 

to relative humidity and can be used with the H775 

Humidity Controller.

• H7655A provides 0-10 Vdc output directly proportional 

to relative humidity and can be used with the T7350 

Temperature/Humidity Controller.

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not 

include normal manufacturing tolerances. Therefore, 

an individual unit may not exactly match the listed 

specifications. Also, this product is tested and 

calibrated under closely controlled conditions and 

some minor differences in performance can be 

expected if those conditions are changed.

Models: 

C7600B, H7655A Solid State Humidity Sensors. 

Provide a dc voltage output in direct proportion to the 

change in relative humidity.

Dimensions: 

See Fig. 1.

Case: 

Rugged, lightweight, compact plastic, easy to install.

Electrical Ratings:

Input: 16-40 Vdc or 16-30 Vac.

Output:

C7600B: 2-10 Vdc voltage signal; increases from 2 to 10 

Vdc as humidity increases. Output voltage is directly 

proportional to relative humidity increase. See Fig. 2.

H7665A: 0-10 Vdc voltage signal; increases from 0 to 10 

Vdc as humidity increases. Output voltage is directly 

proportional to relative humidity increase. See Fig. 3.

Maximum Power Consumption: 0.3 VA.

Mounting: 

Wall mount (directly to wall or standard outlet box).

Ambient Temperature Ranges:

Operating: 32°F to 125°F (0°C to 52°C).

Shipping: -40°F to +150°F (-40°C to +66°C).

Содержание C7600B

Страница 1: ...ons given in this publication do not include normal manufacturing tolerances Therefore an individual unit may not exactly match the listed specifications Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed Models C7600B H7655A Solid State Humidity Sensors Provide a dc voltage output...

Страница 2: ...rvice Offices in all principal cities of the world Manufacturing in Australia Canada Finland France Germany Japan Mexico Netherlands Spain Taiwan United Kingdom U S A SPECIFICATIONS continued from page 1 Humidity Range 10 to 90 percent RH noncondensing Humidity Accuracy From 30 to 70 RH 5 percent RH From 10 to 90 RH 7 percent RH Fig 1 C7600B H7665A dimensions in in mm Fig 2 C7600B nominal output v...

Страница 3: ...ten the sensor on the wall or outlet box with screws through the wallplate mounting holes See Fig 4 6 Replace the cover and tighten the cover locking screw Fig 4 Mounting the sensor on an outlet box Operation C7600B The sensor provides a 2 to 10 Vdc output signal directly proportional to the humidity of the air where the unit is mounted H7665A The sensor provides a 0 to 10 Vdc output signal direct...

Страница 4: ... MEANS AND OVERLOAD PROTECTION AS REQUIRED ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD HEAT COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY INSTALLED JUMPER USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS HC AND HP PROVIDE 24 VAC TO THE HUMIDITY SENSOR 1 M22529 2 3 2 3 4 5 5 RC X T7350 SUBBASE W1 G T7770 REMOTE SENSOR Y1 W3 Y4 Y3 W2 Y2 AUX RH T5 T6 T7 T4 T3 DISCHARGE AIR SENSOR OU...