C7355A ROOM IAQ MONITOR
31-00434—01
8
MANAGING INDICATOR
LIGHTS
About Indicator Lights
Indicator lights are configured for data points to indicate
the conditions that may require control. C7355A helps to
view and manage the data points alarm. It also groups the
indicators into High, Medium and Low categories. You can
view the indicators on the C7355A detector light ring.
Indicator Lights Notification Signs
The indicator light notification has different color codes to
indicate the severity of the concentration. The following
table describes the available signs with color codes of the
indicator lights pages.
The indicator lights are controlled by one minute average
value of PM2.5, and change the color depending on the
concentration. See Table 3 for concentration level.
DIP switches control the Indicator Lights OFF, Three-color
Indicator Lights, and Green Indicator Lights ON. Please
see Fig. 14 and Table 3.
62/1200 PM2.5 24-hour moving
average measurement
x10
4 R
1
UINT16
1
0–10000
corresponding to
0–1000.0
μ
g/m
3
63/1201 PM10 24-hour moving
average measurement
x10
4 R
1
UINT16
1 0–10000
corresponding to
0–1000.0
μ
g/m
3
66/1204 CO
2
24-hour moving
average measurement
x1
4 R
1
UINT16
0 0–5000
corresponding to
0–5,000 ppm
67/1205 TVOC 24-hour moving
average measurement
x1000
4 R
1
UINT16
3 0–3575
corresponding to
0–4.000 mg/m
3
Starting
Register
Decimal
Data Description
Function
Read/
Write
Quantity of
Registers
(2Bytes/16bit) Format Decimals
Data Range,
Data Description
Default
Table 2. Indicator Lights For One Parameter.
Alarm light
Description
High
PM2.5 >75
μ
g/m
3
Medium
PM2.5 is between 35 and
75
μ
g/m
3
Low
PM2.5 <35
μ
g/m
3