background image

C7061M MINIATURE DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR

7

65-0304—05

Fig. 5. C7061 mounting positions.

To mount a C7061M (see Fig. 6):

1.

Hold the unit securely with one hand to prevent it from 

rotating.

2.

Tighten the mounting nut approximately 4 turns with the 

other hand until the unit is held securely in place.

3.

Make sure the unit is properly aligned in the vertical 

plane when viewed from the front.

Fig. 6. Mounting C7061M Detector.

NOTES:

1.

Be sure the C7061M is properly aligned vertically 

when seen from the front. If not, the shutter may 

be damaged or malfunction.

2.

File any burrs or protrusions from the monitoring 

pipe. If the packing in the mounting nut is dam-

aged, any chance of leakage may be caused.

3.

Do not use a tool such as a pipe wrench when 

tightening the mounting nut. Excessive torque by a 

tool could damage the packing and compromise 

the seal.

4.

Do not adjust the mounting pose by forcibly hold-

ing the unit or wiring pipe. Failure to do so may 

damage the packing and compromise the seal.

WIRING

CAUTION

Equipment damage hazard.

Improper wiring can permanently damage amplifier.

When using the C7061 and the R7861 Dynamic 

Self-Check Amplifier, be careful not to short the white 

shutter leadwires together (by wiring incorrectly, leaving 

an incorrect jumper wire, or stripping the insulation too 

much so the bare leadwires can touch).

NOTICE

Per industry standards, a conduit seal or a cable type that 

is sealed is required to be installed in a device that can 

result in flammable gas or flammable liquid flow through a 

conduit or cable to an electrical ignition source in the 

event of a seal leakage or diaphragm failure.

1.

All wiring must comply with applicable local electrical 

codes, ordinances, and regulations. Use NEC Class 1 

wiring.

2.

Keep the flame signal leadwires as short as possible 

from the flame detector to the terminal strip or wiring 

subbase. Capacitance increases with leadwire length, 

reducing the signal strength. The maximum permissible 

leadwire length depends on the type of leadwire and 

conduit type and diameter. 

The ultimate limiting factor in 

flame signal leadwire length is the signal voltage.

 Refer 

to Table 1.

3.

The C7061M1008 detector has color-coded plastic-insu-

lated, no. 18 leadwires, 8 ft (2.4m) long, rated for 221°F 

(105°C). 

These wires must be run in a conduit. 

The 

C7061M1016 has a Brad Harrison® Type 41310 connec-

tor.

4.

If the leadwires are not long enough to reach the termi-

nal strip or wiring subbase, make the required splices in 

a junction box.

5.

If splicing is necessary, use moisture-resistant no. 14 

wire suitable for at least 167°F (75°C) if the detector is 

used with a flame safeguard primary control, or at least 

194°F (90°C) if used with a flame safeguard 

programming control.

6.

For high temperature installations,

 use Honeywell 

specification no. R1298020 wire or equivalent for the F 

leadwire. This wire is rated up to 400°F (204°C) for 

continuous duty. It is tested for operation up to 600 volts 

and for breakdown up to 7500 volts. For the other 

leadwires, use moisture-resistant no. 14 wire selected for 

a temperature rating above the maximum operating 

temperature.

7.

Refer to Fig. 7 for wiring connections.

M29117A

UPPER

LIMIT 90º

HORIZONTAL

PLANE

90º

45º

LOWER

LIMIT 45º

VERTICAL

PLANE

MOUNTING

PIPE

MOUNTING

NUT

VERTICAL PLANE

MOUNTING

DO NOT TILT

DO NOT MOUNT

HORIZONTALLY

DO NOT MOUNT

UPSIDE-DOWN

M29118A

Содержание C7061M

Страница 1: ...ing tube is field replaceable Threaded conduit fitting and color coded leadwires allow rapid electrical installation C7061M1016 uses Molex Woodhead 1R5006A20A120 formerly Brad Harrison Type 41310 connector Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications 4 F 20 C to 175 F 80 C ambient temperature Incorporates UV sensor tube checking...

Страница 2: ... unit that delivers the necessary voltages to operate the tube and shutter Ambient Operating Temperature Ratings Outside the Case 4 F to 175 F 20 C to 80 C using part no 129464N UV Sensing Tube Storage Temperature Ratings 4 F to 158 F 20 C to 70 C Housing Violet plastic cover Housing protection is IP66 Similar to Nema 4 indoor outdoor protection rain tight dust tight hose directed water pro tectio...

Страница 3: ...nditions could result 2 All wiring must be NEC Class 1 line voltage 3 The C7061 is powered from the Flame Safeguard unit that delivers the necessary voltages to operate the sensing tube and shutter 4 Sight the detector so it does not respond to ignition spark 5 On multiburner installations each detector must respond only to the flame of the burner it is supervising 6 Do not connect more than two C...

Страница 4: ...field of view If the temperature of the hot refractory causes the flame relay in the flame safeguard control to pull in re aim the sight pipe so the detector views a cooler area of the refractory Ignition spark is an intense source of ultraviolet radiation When installing the detector make sure it does not respond to ignition spark by following the Ignition Spark Response Test listed on page 9 Sin...

Страница 5: ...e defined as locating all flame detectors so that each detector responds only to the flame of the burner it is supervising In multiple burner systems not every detector can be positioned so its line of sight does not intercept flames from other burners For example this situation occurs in front fired boiler furnaces having more than one row of burners or in multilevel opposed fired furnaces where ...

Страница 6: ...tilate the sight pipe to cool the detector or to clear a viewing path through UV radiation attenuating material For a negative pressure combustion chamber drilling a few holes in the section of the sight pipe outside of the combustion chamber allows air at atmospheric pressure to flow through the sight pipe and into the chamber A perforated pipe nipple between the sight pipe and the detector can a...

Страница 7: ...on source in the event of a seal leakage or diaphragm failure 1 All wiring must comply with applicable local electrical codes ordinances and regulations Use NEC Class 1 wiring 2 Keep the flame signal leadwires as short as possible from the flame detector to the terminal strip or wiring subbase Capacitance increases with leadwire length reducing the signal strength The maximum permissible leadwire ...

Страница 8: ...the sighting position of the detector for optimum flame signal It is suggested that a volt ohm meter with a minimum sensitivity of one megohm volt and a zero to five or ten Vdc scale be used for R7861 Amplifier flame signal measurements Measure the flame signal as illustrated in Fig 8 Be careful to make the proper connections of positive red meter lead to positive control jack and negative black m...

Страница 9: ...iew Continue adjustments until the flame signal due to ignition spark is less than the flame signal values indicated in step 2 Response to other Ultraviolet Radiation Sources Some sources of artificial light produce small amounts of ultraviolet radiation Under certain conditions an ultraviolet detector responds as if it is sensing a flame Do not use an artificial light source to check the response...

Страница 10: ...e the plug in amplifier Then recheck the flame signal 7 Replace the ultraviolet sensing tube see Service on page 10 Then recheck the flame signal 8 Remove detector from the sight pipe and sight it on a UV source and note the flame LED on the 7800 Series device 9 If you cannot yet obtain a meter reading replace the detector IMPORTANT At the completion of Troubleshooting be sure to perform the Adjus...

Страница 11: ...f ultraviolet rays with an orifice ring or the like If there is too much ultraviolet radiation it can penetrate the tube unit even when the shutter is closed causing faulty operation Inspection and Adjustment After replacing the UV sensing tube perform a pilot turndown test an ignition spark response test and a safety shutoff test to verify proper functioning of the tube unit IMPORTANT Do not put ...

Страница 12: ...AME DETECTOR Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 65 0304 05 M S Rev 07 13 Printed in United States ...

Отзывы: