background image

C7061M MINIATURE DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR

65-0304—05

4

Because it is necessary for the UV sensing tube to actually see 

the flame, it is best to locate the detector as close to the flame 

as physical arrangement, temperature, and other restrictions 

permit. These restrictions are described in detail in the 

following paragraphs.

Determine Location

Before beginning the actual installation, determine the best 

location for mounting the detector. Carefully consider the 

factors discussed in this section before deciding on the 

location.

Temperature

Install the C7061 where the ambient temperature (outside the 

case) stays within the ambient operating temperature ratings.

To keep the C7061 below its maximum rating, it may be 

necessary to add additional insulation between the wall of the 

combustion chamber and the detector. A shield or screen can 

be added to reflect radiated heat away from the detector. If the 

detector continues to get too hot, cooling is necessary. Refer to 

the Sight Pipe Ventilation section.

Vibration

The detector withstands normal burner vibration. If the C7061 

is subject to excessive vibration, use a special 123539 

Antivibration Mount. If you use this mount, install it before you 

position and sight the detector.

Clearance

Make sure there is enough room to easily mount the sight pipe, 

detector, and all required fittings, and to remove the detector 

for troubleshooting and servicing.

Radiation Sources (Other than 

Flame)

Examples of radiation sources (other than flame) that could 

actuate the detection system:

1.

Ultraviolet Sources:

a. Hot refractory above 2500°F (1371°C).

b. Spark:

c. Ignition transformers.

d. Welding arcs.

e. Lightning.

f. Gas lasers.

g. Sun lamps.

h. Germicidal lamps.

2.

Gamma Ray and X-ray Sources:

a. Diffraction analyzers.

b. Electron microscopes.

c. Radiographic X-ray machines.

d. High voltage vacuum switches.

e. High voltage condensers.

f. Radioisotopes.

Except under unusual circumstances, none of these sources 

except hot refractory and ignition spark would be present in or 

near the combustion chamber.

The detector can respond to hot refractory above 2300°F 

(1260°C) if the refractory surface represents a significant 

percentage of the detector field of view. If the temperature of 

the hot refractory causes the flame relay (in the flame 

safeguard control) to pull in, re-aim the sight pipe so the 

detector views a cooler area of the refractory.

Ignition spark is an intense source of ultraviolet radiation. 

When installing the detector, make sure it does not respond to 

ignition spark by following the Ignition Spark Response Test 

listed on page 9.

Single Burner Requirements

The detector must have an unobstructed view of a steady part 

of the flame it is supervising. This requires a proper sighting 

angle and minimized ultraviolet radiation attenuation effects. 

However, when supervising only one burner, sighting 

requirements are simplified.

Sighting Angle

The first 30 percent of a flame closest to the burner nozzle (the 

flame root) emits the most ultraviolet energy. Also, if the 

detector sights the flame at an angle instead of 

perpendicularly, it views more flame depth. Therefore, the best 

sighting angle is nearly parallel to the axis of the flame, 

permitting the detector to view a large portion of the first 30 

percent of the flame closest to the burner nozzle, as illustrated 

in Fig. 2.

Low angle sighting permits the detector to view a greater depth 

of flame, thus reducing the effects of instabilities in the flame 

pattern. Also, the environment near the burner nozzle is 

usually cleaner than at any other part of the combustion 

chamber. This provides a clearer line of sight and can keep the 

viewing window cleaner, thus reducing the maintenance 

required.

Fig. 2. Detector sighting angle.

NOTE: When possible, it is desirable to tilt the detector 

and sight pipe downward to prevent the buildup 

of soot in the pipe or on the viewing window.

In most installations, the detector needs to respond to the pilot 

flame alone, then the pilot and main burner flame together, and 

finally the main burner flame alone. The detector must meet all 

sighting requirements that apply:

• Pilot flame alone—the smallest pilot flame that can be 

detected must be capable of reliably igniting the main 

burner.

• Pilot and main burner flame together—the detector must 

sight the junction of both flames.

• Main burner flame alone—the detector must sight the most 

stable part of the flame for all firing rates.

M29115A

UNBURNT FUEL

GOOD

DEPTH OF FLAME IS LONG WHEN THE

MONITORING DIRECTION INTERSECTS 

THE FLAME AXIS AT ACUTE ANGLE

BURNER

BAD

DEPTH OF FLAME IS SHORT

Содержание C7061M

Страница 1: ...ing tube is field replaceable Threaded conduit fitting and color coded leadwires allow rapid electrical installation C7061M1016 uses Molex Woodhead 1R5006A20A120 formerly Brad Harrison Type 41310 connector Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications 4 F 20 C to 175 F 80 C ambient temperature Incorporates UV sensor tube checking...

Страница 2: ... unit that delivers the necessary voltages to operate the tube and shutter Ambient Operating Temperature Ratings Outside the Case 4 F to 175 F 20 C to 80 C using part no 129464N UV Sensing Tube Storage Temperature Ratings 4 F to 158 F 20 C to 70 C Housing Violet plastic cover Housing protection is IP66 Similar to Nema 4 indoor outdoor protection rain tight dust tight hose directed water pro tectio...

Страница 3: ...nditions could result 2 All wiring must be NEC Class 1 line voltage 3 The C7061 is powered from the Flame Safeguard unit that delivers the necessary voltages to operate the sensing tube and shutter 4 Sight the detector so it does not respond to ignition spark 5 On multiburner installations each detector must respond only to the flame of the burner it is supervising 6 Do not connect more than two C...

Страница 4: ...field of view If the temperature of the hot refractory causes the flame relay in the flame safeguard control to pull in re aim the sight pipe so the detector views a cooler area of the refractory Ignition spark is an intense source of ultraviolet radiation When installing the detector make sure it does not respond to ignition spark by following the Ignition Spark Response Test listed on page 9 Sin...

Страница 5: ...e defined as locating all flame detectors so that each detector responds only to the flame of the burner it is supervising In multiple burner systems not every detector can be positioned so its line of sight does not intercept flames from other burners For example this situation occurs in front fired boiler furnaces having more than one row of burners or in multilevel opposed fired furnaces where ...

Страница 6: ...tilate the sight pipe to cool the detector or to clear a viewing path through UV radiation attenuating material For a negative pressure combustion chamber drilling a few holes in the section of the sight pipe outside of the combustion chamber allows air at atmospheric pressure to flow through the sight pipe and into the chamber A perforated pipe nipple between the sight pipe and the detector can a...

Страница 7: ...on source in the event of a seal leakage or diaphragm failure 1 All wiring must comply with applicable local electrical codes ordinances and regulations Use NEC Class 1 wiring 2 Keep the flame signal leadwires as short as possible from the flame detector to the terminal strip or wiring subbase Capacitance increases with leadwire length reducing the signal strength The maximum permissible leadwire ...

Страница 8: ...the sighting position of the detector for optimum flame signal It is suggested that a volt ohm meter with a minimum sensitivity of one megohm volt and a zero to five or ten Vdc scale be used for R7861 Amplifier flame signal measurements Measure the flame signal as illustrated in Fig 8 Be careful to make the proper connections of positive red meter lead to positive control jack and negative black m...

Страница 9: ...iew Continue adjustments until the flame signal due to ignition spark is less than the flame signal values indicated in step 2 Response to other Ultraviolet Radiation Sources Some sources of artificial light produce small amounts of ultraviolet radiation Under certain conditions an ultraviolet detector responds as if it is sensing a flame Do not use an artificial light source to check the response...

Страница 10: ...e the plug in amplifier Then recheck the flame signal 7 Replace the ultraviolet sensing tube see Service on page 10 Then recheck the flame signal 8 Remove detector from the sight pipe and sight it on a UV source and note the flame LED on the 7800 Series device 9 If you cannot yet obtain a meter reading replace the detector IMPORTANT At the completion of Troubleshooting be sure to perform the Adjus...

Страница 11: ...f ultraviolet rays with an orifice ring or the like If there is too much ultraviolet radiation it can penetrate the tube unit even when the shutter is closed causing faulty operation Inspection and Adjustment After replacing the UV sensing tube perform a pilot turndown test an ignition spark response test and a safety shutoff test to verify proper functioning of the tube unit IMPORTANT Do not put ...

Страница 12: ...AME DETECTOR Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 65 0304 05 M S Rev 07 13 Printed in United States ...

Отзывы: