APPLICATION

The Series 2000 C7031, C7041 Electronic Temperature 

Sensors are designed for use with electronic controllers in 

domestic or commercial heating and cooling systems.

FEATURES

• C7031D, C7041D for immersion mounting sense water 

temperature.

• C7031G, C7041F sense outdoor air temperature and 

are weatherproof for outdoor use (knockouts allow for 

1/2 in. conduit connection).

• C7031J, C7041J,R sense average duct air temperature.
• C7031B, C7041B,C sense duct air temperature.
• C7041K with strap-on mounting senses water 

temperature.

• C7041P senses air temperature.
• Solid state components not affected by dust or dirt.

SPECIFICATIONS

Compatability: 

Use Series 2000 C7031, C7041 Temperature 

Sensors with Excel 10, 15, 80, 100, and 500 controllers. 

Series 2000 C7031B,D,G,J sensors are compatible with 

various Honeywell controllers. The C7031G2014 is 

compatible with the T7350 Commercial Thermostat.

Dimensions: 

See Fig. 1 through 9.

Sensor Accuracy: 

±0.36°F at 77°F (±0.2°C at 25°C) for 20K 

ohm NTC sensors.

Accessories:

32006523-001 20K Probe: to allow replacement of old style 

C7031D1062-1 with non-threaded well.

50001774-001 Stainless Steel 304 Well Assembly: 1/2 in. 

external and internal NPT threading. Use with C7031D/

C7041D.

50001775-001 Well Adapter: Used with C7031D/C7041D to 

allow threading sensor into previously-installed Series 1000 

32005960-001 Well.

C7031B,

C7041B,C

C7031G, 

C7041F

C7041P

C7041R

C7041K

C7031D, 

C7041D

C7031J, 

C7041J

Contents

Application ........................................................................

1

Features ...........................................................................

1

Specifications ...................................................................

1

Ordering Information  ........................................................

2

Installation ........................................................................

5

Wiring ...............................................................................

8

Operation and Checkout  ..................................................

8

Содержание C7031B

Страница 1: ...SPECIFICATIONS Compatability Use Series 2000 C7031 C7041 Temperature Sensors with Excel 10 15 80 100 and 500 controllers Series 2000 C7031B D G J sensors are compatible with various Honeywell controllers The C7031G2014 is compatible with the T7350 Commercial Thermostat Dimensions See Fig 1 through 9 Sensor Accuracy 0 36 F at 77 F 0 2 C at 25 C for 20K ohm NTC sensors Accessories 32006523 001 20K P...

Страница 2: ...rol Sensitivity in ohms per degree F per degree C for element operating range e Nonlinear resistance decreases as temperature increases Model Control Application Element Insertion Length Element Operating Range Element Max Ambient Temperature Sensor Resistance in Ohms Sensitivityd C7031B Duct discharge air 6 in 152 mm 40 to 250 F 40 C to 121 C 250 F 121 C 1097 at 77 25 C b 2 1 3 9 C7031D Hot or ch...

Страница 3: ... 1 11 16 43 4 3 16 107 3 4 19 4 70 1 11 16 43 C7031B 5 11 16 145 C7041B 11 5 8 295 C7041C 17 5 8 448 M27010 1 13 16 46 7 16 12 1 8 NPSM 3 3 7 8 99 3 4 19 3 8 10 1 26 4 102 FITS 1 2 NPT TAPPED HOLE M27052 1 2 NPSM INTERNALLY THREADED 1 26 11 16 18 5 8 16 M22821 5 16 8 SPACER SENSOR 1 26 7 8 22 3 16 4 3 8 IN 16 THREAD 2 3 32 53 4 3 16 106 1 5 32 29 2 19 64 58 1 8 INCH NPSM STRAIGHT THREADS SINGLE GA...

Страница 4: ...in mm Fig 7 C7041R dimensions in in mm 2 5 16 59 1 11 16 43 4 3 16 107 1 4 6 4 70 1 11 16 43 6 11 16 170 M22596 5 127 1 2 NPSM 13 2 5 16 59 15 16 23 1 11 16 43 4 3 16 107 3 4 19 4 70 1 11 16 43 M22818 1 13 16 46 7 16 12 1 8 NPSM 3 3 7 8 99 DEPENDING ON THE MODEL THE ELEMENT LENGTH IS EITHER 12 FT 366 CM OR 24 FT 732 CM 1 1 ...

Страница 5: ... the C7041 Temperature Sensor The following procedures include outdoor duct immersion well and strap on applications Also refer to the instructions for the electronic control Outdoor Mounting C7031G C7041F The C7031G and C7041F sense outdoor air temperature Mount this control where it can sense average outdoor air temperature Normally the north side of a building provides a suitable location NOTE ...

Страница 6: ...ll one C7031J C7041J just upstream from the cold deck zone dampers and the other C7031J C7041J upstream from the hot deck zone dampers Position the thermistors to sense the average deck temperature Fig 11 Duct cross section showing method of installing C7031J C7041J in a multizone system C7041R MOUNTING 1 Install two supports inside the duct to hold the averaging element 2 Cut a 7 8 in 22 mm hole ...

Страница 7: ...The C7041K Sensor mounts on metal pipes from 1 5 8 inch to five inches in diameter using the straps supplied Clean the surface of the pipe where the sensor makes contact before mounting remove insulation from the pipe at the point of installation if necessary Thermal compound is recommended with the strap on C7041K Sensor Locate the sensor on the discharge pipe within 3 feet 0 9m of the boiler See...

Страница 8: ... shield only to grounded controller case CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation IMPORTANT 1 All wiring must agree with applicable codes ordinances and regulations 2 Do not mount sensor in incorrect environment 3 Wire according to the applicable controller instructions OPERATION AND CHECKOUT ...