INSTALLATION INSTRUCTIONS

Place Bar Code Here

62-0211-01

C7021P / C7023P / C7041P 

Button Probe Sensors

10K OHM NTC TYPE II / TYPE III & 20K OHM NTC

MODEL SELECTION

The button probe sensor is available in the following 
models to meet most application needs:

• C7021P2004: 10K Ohm NTC Type II
• C7023P2004: 10K Ohm NTC Type III
• C7041P2004: 20K NTC Ohm

MORE INFORMATION

To see the complete line of Honeywell sensors, 
download the Sensor Product Overview brochure 
(63-9285) from customer.honeywell.com.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition.

2.

Check ratings given in instructions and on the 
product to ensure the product is suitable for your 
application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

Mounting

The Button Probe Sensor design simplifies mounting into 
a variety of standard structural materials. See Fig. 1 for 
dimensions.

The locking nut can be used to secure the probe. 
See Fig. 2.

The plastic spacer helps insulate the probe from drywall, 
wood, or other material in which the probe is mounted. 
See Fig. 3. The spacer is sized to fit snugly into 1/2 in. 
metal conduit. See Fig. 4.

NOTES:

The plastic spacer is threaded for easy 
installation.

Use of both the locking nut and spacer 
requires cutting spacer to shorter length.

Mounting Recommendations

Determine the proper location based upon the following:
— Mount the probe to an inside wall approximately 54 in. 

(1372 mm) from the floor (or in the specified location) 
to allow exposure to the average zone temperature.

— Do not mount the probe to an outside wall, a wall 

containing water pipes, or near air ducts.

— Avoid locations exposed to register discharge air, or 

radiation from lights, appliances, or the sun.