APPLICATION

The Series 2000 C7021, C7023, C7031 and C7041 Electronic 

Temperature Sensors are designed for use with electronic 

controllers in domestic or commercial heating and cooling 

systems.

FEATURES

• C7021D, C7023D, C7031D, C7041D for immersion 

mounting sense water temperature.

• C7021F, C7023F, C7031G, C7041F sense outdoor air 

temperature and are weatherproof for outdoor use 

(knockouts allow for 1/2 in. conduit connection).

• C7021J/R, C7023J/R, C7031J, C7041J/R sense average 

duct air temperature.

• C7021B/C, C7023B/C, C7031B, C7041B/C sense duct 

air temperature.

• C7021K, C7023K, C7041K with strap-on mounting 

senses water temperature.

• C7021N, C7023N, C7041N probe senses water or air 

temperature. 

• C7021P, C7023P, C7041P senses air temperature.
• Solid state components not affected by dust or dirt.

C7021F 

C7023F 

C7031G 

C7041F

C7021P 

C7023P 

C7041P

C7021R 

C7023R 

C7041R

C7021K 

C7023K 

C7041K

C7021D 

C7023D 

C7031D 

C7041D

C7021J 

C7023J 

C7031J 

C7041J

C7021B/C 

C7023B/C 

C7031B 

C7041B/C

C7021N 

C7023N 

C7041N

Contents

Application......................................................................... 1

Features ............................................................................ 1

Specifications .................................................................... 2

Installation ......................................................................... 8

Wiring ................................................................................11

Operation and Checkout ...................................................11

Содержание C7021B

Страница 1: ...t connection C7021J R C7023J R C7031J C7041J R sense average duct air temperature C7021B C C7023B C C7031B C7041B C sense duct air temperature C7021K C7023K C7041K with strap on mounting senses water temperature C7021N C7023N C7041N probe senses water or air temperature C7021P C7023P C7041P senses air temperature Solid state components not affected by dust or dirt C7021F C7023F C7031G C7041F C7021...

Страница 2: ... 2000 C7023 temperature sensors are compatible with WEBs AX I O modules Dimensions See Fig 1 through Fig 11 Sensor Accuracy 0 36 F at 77 F 0 2 C at 25 C for 20K ohm NTC sensors and 10K ohm NTC Type II and Type III sensors Accessories 32006523 001 20K Probe to allow replacement of old style C7031D1062 1 with non threaded well 50001774 001 Stainless Steel 304 Well Assembly 1 2 in external and intern...

Страница 3: ...C7031G 2014d Outdoor air 40 to 120 F 40 to 49 C 120 F 49 C 3484 at 77 F 25 C c 2 1 3 9 C7031J Duct discharge air averaging sensor with 4 elements 12 ft 3 7m 40 to 180 F 4 to 82 C 250 F 121 C 1097 at 77 25 C c 2 1 3 9 C7041B Duct discharge air 6 in 152 mm or 12 in 305 mm 40 to 250 F 40 to 121 C 250 F 121 C 20K Ohms NTC at 77 F 25 C e C7041C Duct discharge air 18 in 457 mm C7041D Hot or chilled wate...

Страница 4: ... F per degree C for element operating range b Order immersion well separately 50001774 001 c Resistance increases as temperature increases d Use with T7350 Commercial Thermostat e Nonlinear resistance decreases as temperature increases f Not equipped with well temperature sensed at surface of pipe ...

Страница 5: ...8 At 59 F 15 C 15 712 15 137 1 059 32 427 At 68 F 20 C 12 493 12 268 1 078 25 370 At 77 F 25 C 10 000 10 000 1 097 20 000 At 86 F 30 C 8 057 8 196 1 117 15 856 At 95 F 35 C 6 531 6 754 1 136 12 654 2 5 16 59 15 16 23 1 11 16 43 4 3 16 107 3 4 19 4 102 1 11 16 43 C7031B 5 11 16 145 C7021B C7023B C7041B 11 5 8 295 C7021B C7023B C7041C 17 5 8 448 M27010A 1 13 16 46 7 16 12 1 8 NPSM 3 3 7 8 99 1 26 11...

Страница 6: ... C7021D C7023D C7041D uses the 50001774 001 Well Assembly See Fig 4 for dimensions Fig 6 50001774 001 Immersion Well dimensions in in mm 2 1 4 57 3 4 19 1 25 5 127 7 8 22 8 5 16 211 M22132 3 5 8 91 2 5 16 59 1 11 16 43 4 3 16 107 1 4 6 4 70 1 11 16 43 6 11 16 170 M22596 5 127 1 2 NPSM 13 3 4 19 3 8 10 1 26 4 102 FITS 1 2 NPT TAPPED HOLE M27052 1 2 NPSM INTERNALLY THREADED ...

Страница 7: ...1 16 43 4 3 16 107 3 4 19 4 70 1 11 16 43 M22818 1 13 16 46 7 16 12 1 8 NPSM 3 3 7 8 99 DEPENDING ON THE MODEL THE ELEMENT LENGTH IS EITHER 12 FT 366 CM OR 24 FT 732 CM 1 1 2 5 16 59 4 3 16 107 4 70 1 11 16 43 7 1 8 182 9 16 14 1 1 2 38 1 1 2 38 2 5 16 59 M22134 1 1 4 32 5 127 MAXIMUM PIPE DIAMETER SHOWN MINIMUM PIPE DIAMETER 1 5 8 41 1 1 4 3 16 107 COPPER PLATE FOAM PAD ...

Страница 8: ...1F sense outdoor air temperature Mount this control where it can sense average outdoor air temperature Normally the north side of a building provides a suitable location NOTE These sensors are weatherproof for outdoor use Knockouts allow for 1 2 in conduit connection 1 Remove and set aside the wiring box cover 2 Mount the sensor to standard 1 2 in conduit NOTE Mount sensor so that the element poin...

Страница 9: ...hold the averaging element 2 Cut a 7 8 in 22 mm hole in the side of the duct 3 Insert the averaging element into the duct through the hole 4 Fasten the terminal box to the outside of the duct and thread the element through the hole and into the duct 5 Use plastic wire ties to fasten the element to the supports Seal the hole around the element with a rubber grommet 6 Secure the end of the element t...

Страница 10: ...g the system The C7021K C7023K C7041K Sensor mounts on metal pipes from 1 5 8 inch to five inches in diameter using the straps supplied Clean the surface of the pipe where the sensor makes contact before mounting remove insulation from the pipe at the point of installation if necessary Thermal compound is recommended with the strap on C7021K C7023K C7041K Sensor Locate the sensor on the discharge ...

Страница 11: ...ry Disconnect power supply before installation IMPORTANT 1 All wiring must agree with applicable codes ordinances and regulations 2 Do not mount sensor in incorrect environment 3 Wire according to the applicable controller instructions OPERATION AND CHECKOUT Operation The C7041 Temperature Sensors are designed for use with XL500 XL100 XL50 XL15 XL10 and Honeywell LCBS Controllers or any controller...

Страница 12: ... Inc 63 2590 05 M S Rev 08 11 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modific...

Отзывы: