background image

INSTALLATION INSTRUCTIONS

60-2024-06

SIL

3

Capable

C7007A, C7008A, C7009A Flame 

Rod Holder & Flame Rod 

Assemblies  

The small size of these devices enable their application to 

flame detection in installations where space is limited. The 

holder and flame rod assemblies facilitate flame proving on 

gas burners or gas-ignited oil burners which are controlled by 

electronic flame safeguard systems. 

• The C7007A, C7008A, and C7009A may be used with 

flame safeguard controls utilizing the rectification principle 

of flame detection. 

• The C7007A is a small, sturdy holder for a 3/16 inch [4.8 

mm] diameter flame rod (flame rod ordered separately). 

• The holder is externally threaded (1/2-14 NPT) for pipe 

mounting. 

• A collet chuck and setscrew position a flame rod securely. 

If additional support of the flame rod is required, the 

C7007A extension assembly is internally threaded (1/8-27 

NPT) to accept a 1/8 inch iron support pipe. 

• The C7008A is a miniature flame rod assembly with a 

threaded (external 1/4-18 NPT) base, snap-on cover, and 

flame rod. 

• The C7008A can be used without the cover and a 

coverless model is available. 

• The C7008A is available with several lengths of flame rod. 

One end of the flame rod is threaded for insertion into the 

C7008A and the other end may be cut to an exact size. 

• The C7009A is a smaller diameter flame rod assembly with 

an externally threaded (1/8-27 NPT) base and readily 

accessible Rajah electrical connection. 

• The C7009A has a 12 inch (305mm) flame rod which one 

end is threaded and the other capable of being cut to an 

exact size. 

IMPORTANT 

The specifications given in this publication do not 

include normal manufacturing tolerances. Therefore, 

this unit may not match the listed specifications 

exactly. Also, this product is tested and calibrated 

under closely controlled conditions, and some minor 

differences in performance can be expected if those 

conditions are changed. 

SPECIFICATIONS

Tradeline Models:

C7008A Flame Rod Assembly, straight pattern, with cover 

(can be used with or without cover).

FLAME RODS

C7008A1174, 12 inch [305 mm] Kanthal A1 C7008A1182, 24 

inch [610 mm] Kanthal A1 see also, Accessories.

DIMENSIONS: 

See Fig. 2.

ELECTRICAL CONNECTION: 

Rajah male with companion connector.

MOUNTING: 

Equipped with external 1/4-18 NPT threads. 

STANDARD MODELS

C7007A Flame Rod Holder.

C7008A Flame Rod Assembly: 

Miniature flame rod assembly.

C7009A Flame Rod Assembly: small diameter flame rod 

assembly.

MOUNTING MEANS:

C7007A-external 1/2-14 NPT for pipe mounting.

C7008A-external 1/4-18 NPT for pipe mounting.

C7009A-external 1/8-27 NPT for pipe mounting.

FLAME ROD:

C7007A-Not furnished, refer to ACCESSORIES.

C7008A-Kanthal in 6, 12, 18, 24 inch [152, 305, 457, 610 mm] 

lengths.

C7009A-Kanthal in 12 inch [305 mm] lengths.

Содержание C7007A

Страница 1: ...ut to an exact size The C7009A is a smaller diameter flame rod assembly with an externally threaded 1 8 27 NPT base and readily accessible Rajah electrical connection The C7009A has a 12 inch 305mm flame rod which one end is threaded and the other capable of being cut to an exact size IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances Therefore th...

Страница 2: ...up to 500 F 260 C for intermittent use Tested to 15 000 V R1298020 Cable For flame detector F lead wire installations in a high temper ature environment Rated up to 400 F 204 C for continu ous duty Tested for operation up to 600 V and breakdown up to 7500 V Fig 1 Dimensions in inches mm of C7007A flame rod holder Fig 2 Dimensions in inches mm of C7008A flame rod assembly Fig 3 Dimensions in inches...

Страница 3: ...e flame rod will be vertical or at least angled downward A rod so installed is less likely to sag at high temperatures NOTE For extra electrode support couple a length of 1 8 inch iron pipe to the extension assembly which is already threaded internal 1 8 27 NPT C7007A only 5 The unit may also be installed so the flame rod is hori zontal or angled upward but extra support is needed for rods over 12...

Страница 4: ...times greater than the area of the portion of the flame rod in contact with the flame The ratio of ground to flame contact area with a raw gas pilot is usually less than a factor of four In situations where the ground area available is inadequate the ground area must be increased There are three proven methods for providing an adequate grounding surface area a the bomb fin assembly b grounding rod...

Страница 5: ...microammeter with a zero to 25 microampere scale A meter connector plug part no 196146 provided with the W136A is used to adapt the W136A to the flame current jack on the flame safeguard control The W136A Meter probes are connected to the two ends of the connector plug red to red black to black The plug end of the connector inserts directly into the flame current jack of the flame safeguard contro...

Страница 6: ...C7007A C7008A C7009A FLAME ROD HOLDER FLAME ROD ASSEMBLIES 60 2024 06 6 Fig 12 Measuring 7800 SERIES controls flame signal voltage NEGATIVE METER LEAD POSITIVE METER LEAD ONE MEGOHM VOLT METER M7382 ...

Страница 7: ...C7007A C7008A C7009A FLAME ROD HOLDER FLAME ROD ASSEMBLIES 7 60 2024 06 ...

Страница 8: ...ROD ASSEMBLIES Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 60 2024 06 M S Rev 06 11 Printed in U S A ...

Отзывы: