 WARNING

–   The grid operator is responsible for the safe 

remote shut-down and restart of the diaphragm 
gas meter.

–   The integrated valve does not assume the func-

tions of a safety shut-off valve.

 

Should the diaphragm gas meter BK be ordered 
with a valve, but without control electronics to 
be complemented by a third party, the technical 
data of the control interface is to be requested 
from Elster GmbH and observed.

 

The manufacturer of the control electronics is 

responsible for creating the conditions required 
for safe operation of the valve. Instructions on 
commissioning and operation are to be taken 
from the operating instructions for the control 
electronics.

 

... with valve variant Ve

 

Notes on the function can be found in the operat-
ing instructions of the electronic index. Technical 
data, see page 9 (Technical data).

... with valve variant Vs (Smart Valve)

 WARNING

–   Depending on national regulations, a limited 

and technically safe gas flow rate in the cus-
tomer’s open consumer piping is allowed, see 
page 9 (Technical data).

–   Assessment of the non-critical gas flow rate with 

regard to amount and duration, which occurs 
when the valve is released, is to be carried out 
by the grid operator.

–   The minimum operating pressure on the inlet 

must not be undershot, see page 9 (Techni-
cal data). Otherwise, when the valve is r
eleased 
and if the customer’s consumer piping is open 
at the same time, the valve may be completely 
opened.

“Smart Valve” valve function

 

The “Smart Valve” is switched remotely by the data 

management system. The valve first switches to 
the “Released” position. From the “Released” posi-
tion, the valve automatically switches to the “Open” 
position, if the downstream installation is tight.

Released

 

The “Smart Valve” opens an internal bypass and 

releases a minimum gas flow into the customer’s 
closed consumer piping. Pressure equalization 
takes place between the inlet and outlet side 
of the valve.

Open

 

Following pressure equalization, the valve auto-
matically opens by spring force and fully releases 
the gas supply. If consumers of the customer are 
open, pressure equalization cannot occur and 
the valve remains in the “Released” position and 
continues to release only the minimum gas flow 
rate of the bypass.

Closed

 

The valve and the bypass are closed in the event 

of remote shut-down.

 

All valve positions are kept when de-energized.

Maintenance/Removal

Gas meters BK-G1.6 to 25 from Elster are mainte-
nance-free (constraints for BK-G...E... and BK-G...B).

 

When used for custody transfer measurements, 

recalibration must be carried out in accordance 
with national directives.

 

If the screw unions are loosened for maintenance 
work or retesting, replace the seals.

 

After the gas meter has been removed, immedi-

ately close the connectors with protective caps 
in order to prevent ingress of dirt particles.

 

For meters with electronic indexes (BK-G...E... 
and BK-G...B), it may be necessary to change 
the battery, see “Operating instructions for op-
erators and installers” for the corresponding 
electronic index.

 WARNING

A certain amount of gas may remain in the gas 

meter. Taking into consideration the risk of explo-
sion, it is important to adopt safety measures, e.g.:

–   Following removal of the gas meter, purge it 

thoroughly with inert gas.

–   For transporting the gas meter with gas residue, 

use a vehicle with an open or a ventilated load-
ing area.

–   The indexes must not be opened in an explo-

sion-hazard area even for maintenance and 
repair. Opening of the service cover on the 
electronic index, e.g. to change the battery, 
is permitted – see “Operating instructions for 
operators and installers” for the corresponding 
electronic index.

–   Meters which are installed in a potentially ex-

plosive atmosphere may only be cleaned using 
a damp cloth to avoid static electricity charge.

Accessories

We recommend using Elster GmbH accessories only.

Pulse transmitters of the IN-Z6x series

 

Also for devices which are marked with 

 

IN-Z6

 (Part No. 32319615)

Retrofit kit with connection cable – 
Order No. 72910109
Retrofit kit without connection cable – 
Order No. 72910114

IN-Z6

 (Part No. 32319616)

Shipping unit – Order No. 32447303

IN-Z6 

(Part No. 32319617)

Retrofit kit – Order No. 72910110
Retrofit kit with cable socket – Order No. 72910112

Содержание BK-G1.6A

Страница 1: ...ified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 07 17 The following chapters have been changed Checking the usage Commissioning Accessories Technical data Declarations of conformity ATEX legend Logistics Contents Operating instructions D GB GB 1 1...

Страница 2: ...C A E B Mechanical index Chekker mechanical index Absolute ENCODER index Electronic index Indication of volume at base conditions T Te TB TeB Temperature conversion mechanical electronic mechanical electronic temperature conversion and pressure correction electronic temperature conversion and pressure correction Part designations 1 3 5 7 6 2 4 1 Diaphragm gas meter BK 2 Index with index plate 3 Co...

Страница 3: ...the index variant can be found at the bottom of the type label or on the index cover next to the serial number S N EI6 tm tg tb M 0102 15 ATEX 1550 X Further information can be found in the supplemen tary operating instructions of the relevant index Diaphragm gas meters with integrated valve DE 07 MI002 PTB001 S N 002545632734 class 1 5 NG 47001BM0443 DIN EN 1359 2007 BK G VALVE Vx M 0102 m3 Valve...

Страница 4: ...serve the following to ensure that neither persons nor the gas meter are damaged during installation and operation Note the max allowable operating pres sure pmax and measuring range Qmax see page 2 Type label Index plate Note the permitted ambient temperature tm and gas temperature tg see page 2 Type label Index plate or page 9 Technical data The gas meters are certified for mechanical environmen...

Страница 5: ...w arrow The gas meter must not be in contact with ma sonry or other parts Ensure that there is sufficient installation space Ensure unobstructed view of the index The seal faces on the screw unions must be clean and damage free Ensure that the seal is correctly seated Co axial meters The seal must be centred over the internal dia meter When using an elastomer seal always use a pressure ring shape ...

Страница 6: ...e installation and tightness test are com plete see page 6 Tightness test protect the pressure test point against external access with the sealing sleeve and the seal Pressure test point on outlet connector optional BS4161 compliant pressure test nipple Use a 10 mm spanner to release tighten the test point screw The test nipple is secured to prevent it turning with the screw Opening the test nippl...

Страница 7: ...lectrical circuits of pulse transmitters IN Z61 and IN Z64 are consid ered to be grounded at voltages 10 V if the plug connector housings are connected to the ground potential The intrinsically safe electrical circuits of pulse transmitters IN Z61 IN Z62 and IN Z65 are to be considered as non grounded BK G A with Absolute ENCODER index AE1 Z6 Interface description for gas meters with ENCODER index...

Страница 8: ...g force and fully releases the gas supply If consumers of the customer are open pressure equalization cannot occur and the valve remains in the Released position and continues to release only the minimum gas flow rate of the bypass Closed The valve and the bypass are closed in the event of remote shut down All valve positions are kept when de energized Maintenance Removal Gas meters BK G1 6 to 25 ...

Страница 9: ...e required error limits If no gas temperature tg is specified on the index plate the following applies tg tm The specified centre temperature tsp of the BK G E series and BK G B meters is not stated on the index plate but can be called up in the display using the menu Diaphragm gas meters BK with pressure test point Pressure test point 24 olive fitting to EN ISO 8434 1 L6 x M12 x 1 5 St Diaphragm ...

Страница 10: ... F NL I SK RUS E RO SRB Declarations of conformity Scans of all valid Declarations of conformity see www docuthek com Elster Instromet Diaphragm gas meters BK G M BK G C BK G MT BK G CT without ATEX declaration ...

Страница 11: ...GB 11 D GB Diaphragm gas meters BK G M BK G C BK G MT BK G CT with ATEX declaration ...

Страница 12: ...GB 12 GB F NL I SK RUS E RO SRB Diaphragm gas meters BK G M BK G C BK G MT BK G CT with RFID passive tag and ATEX declaration ...

Страница 13: ...GB 13 D GB Diaphragm gas meters BK G A BK G AT ...

Страница 14: ... for Zone 2 c Constructional safety explosion protec tion type IIB IIA Explosion group for gases TX No intrinsic heating T1 Temperature class maximum allowable surface temperature 450 C T4 Temperature class maximum allowable surface temperature 135 C T6 Temperature class maximum allowable surface temperature 85 C Gc Equipment protection level for Zone 2 Ta Ambient temperature Logistics Transport D...

Отзывы: