BCU 370 · Edition 01.19
57
Parameters
4 .6 .3 Quick start starts in . . .
Parameter 28
Only active if parameter 06 = 0 (Pre-purge) and param-
eter 25 = 1 (Valve control) are set.
Determines whether on quick start, the butterfly valve
rests in the Ignition position or in the Closed position
during standby.
In the Closed position, the amount of combustion air
which enters the combustion chamber is minimized.
Parameter 28 = 0: the BCU sets the butterfly valve to
the Ignition position for quick start after controlled
shut-down. Once the start-up signal (
ϑ
) has been ap-
plied, the BCU initiates burner ignition immediately af-
ter the fan run-up time (parameter 20) and the waiting
time.
Parameter 28 = 1: the BCU sets the butterfly valve to
the Closed position for quick start after controlled shut-
down. Once the start-up signal (
ϑ
) has been applied,
the BCU moves the actuator to the Ignition position via
the Open position and ignites the burner after the fan
run-up time (parameter 20) and the waiting time. The
time between activating the start-up signal (
ϑ
) and
burner start is determined by the running time of the
actuator of the butterfly valve.