BCU 370 · Edition 01.19
21
Function
3 .2 .2 Quick start, butterfly valve
waits in the Ignition position
Parameter 06 = 0, parameter 28 = 0
Quick start is the same as normal
start, except that pre-purge is
dispensed with. The burner starts
quicker. This results in improved
control quality, since there is no
dead time, the energy is used better
and no cold air is fed to the com-
bustion chamber.
The BCU 370 only carries out a
quick start if the last shut-down
was a controlled shut-down. No
more than 24 hours may have
elapsed and the BCU must have
been switched on.
In contrast to the “normal start-up”,
in the case of a quick start, program
steps
A1
,
P1
and
A2
will be omit-
ted.
If there is no pilot burner, program
steps
06
und
07
will also be omit-
ted.
▼
H0
05
06
07
08
00
00
H0
02
01
H8
08
P9
A1
A2
04
03
Start-up with
ϑ
signal
Waiting time t
W
Fan run up time t
GV
(P20)
Switch-on delay time t
E
running (P22)
Start-up position/standby
Start-up position/standby
Controlled shut-down
via
ϑ
signal
Flame proving period t
FS1
running for burner/pilot burner (P13)
Flame proving period t
FS2
running for main burner (P15)
Safety time t
SA2
running for main burner (P14),
V3 opens
Controller enabler signal delay time t
RF
(P29)
Controller enable signal
Post-purge time t
PN
running (P19)
If parameter P27 = 0:
V2 is switched off
Butterfly valve moves to Open position
Butterfly valve moves to Ignition position
Safety time t
SA1
running for
burner/pilot burner (P12),
V1 and V2 open
Pre-ignition time t
VZ
running (P21)
Ignition activated