BACNET® FIXED FUNCTION THERMOSTAT

3

31-00099—01

Table 3. Heat Pump Applications

Table 4. Air Conditioning Unit Applications

Application

# 0

# 1

# 2

# 3

# 10

Fan

On/Off or VFD

On/Off or VFD

On/Off or VFD

On/Off or VFD

3 speed or VFD

Compressor

Yes

Yes

Yes

Yes

Yes

Reversing Valve

Yes

Yes

Yes

Yes

Yes

Air or Water 
Sourced

Air

Water

Air

Water

Air

Auxiliary Electric
Heater.

One Stage

One Stage

Two Stage

Two Stage

One Stage

Economizer

Three Point

Floating or

Analog

Three Point

Floating or

Analog

Analog

Analog

Analog

Space Sensor (10K
Type II Thermistor)

Optional

Optional

Optional

Optional

Optional

OAT Sensor (10K
Type II Thermistor)

Optional

Optional

Optional

Optional

Optional

Supply Air Temp
Sensor (10K Type II
Thermistor)

Required for

Economizer

Control

Required for

Economizer

Control

Required for

Economizer

Control

Required for

Economizer

Control

Required for

Economizer

Control

Occupancy
Detection

Optional Via Door, Window Sensors or PIR

Condensate Alarm

Optional

Optional

Optional

Optional

Optional

Application

# 4

# 5

Fan

On/Off or VFD

On/Off or VFD

Compressor

One

Two

Auxiliary Electric Heater

One Stage

Two Stages

Economizer

Three Point Floating or Analog

Space Sensor 
(10K Type II Thermistor)

Optional

Optional

OAT Sensor 
(10K Type II Thermistor)

Optional

Optional

Supply Air Temp Sensor
(10K Type II Thermistor)

Required for

Economizer

Control

Required for

Economizer

Control

Occupancy Detection

Optional Via Door, Window Sensors or PIR

Condensate Alarm

Optional

Optional

Содержание BACnet

Страница 1: ...rm No 31 00096 BACnet Fixed Function Thermostat WEBs AX Configuration Wizard Guide Form No 31 00097 BACnet Fixed Function Thermostat System Engineering Guide Form No 31 00098 TABLE OF CONTENTS Quick Lookup Application Selection Tables 2 Fan Coil Unit 4 Pipe Applications 2 Fan Coil Unit 2 Pipe Applications 2 Heat Pump Applications 3 Air Conditioning Unit Applications 3 Application 0 Heat Pump Air t...

Страница 2: ...for Economizer Control Required for Economizer Control Required for Economizer Control Required for Economizer Control Optional Occupancy Detection Optional via Standby Switch Optional Via Door Window Sensors or PIR Optional Via Door Window Sensors or PIR Optional Via Door Window Sensors or PIR Optional Via Door Window Sensors or PIR Condensate Alarm Optional No No No No Application 11 12 13 14 15...

Страница 3: ...tional Optional Optional Optional Supply Air Temp Sensor 10K Type II Thermistor Required for Economizer Control Required for Economizer Control Required for Economizer Control Required for Economizer Control Required for Economizer Control Occupancy Detection Optional Via Door Window Sensors or PIR Condensate Alarm Optional Optional Optional Optional Optional Application 4 5 Fan On Off or VFD On O...

Страница 4: ...as a sensor set the following parameters SINGLE STAGE ELECTRIC HEAT Inputs AI 0 Space Sensor or Outside Air Sensor optional AI 2 Supply Air Sensor optional required for economizer control BI 1 PIR Door Window Sensor optional BI 2 Condensate Sensor optional Outputs BO 0 Fan BO 1 Heat Pump Compressor BO 2 Reversing Valve BO 3 Electric Heat optional BO 4 Economizer Open optional for floating control ...

Страница 5: ...re is water flow To configure AI 0 as a sensor set the following parameters SINGLE STAGE ELECTRIC HEAT Inputs AI 0 Space Sensor or Outside Air Sensor optional AI 2 Supply Air Sensor optional required for economizer control BI 1 PIR Door Window Sensor optional BI 2 Condensate Sensor optional Outputs BO 0 Fan BO 1 Heat Pump Compressor BO 2 Reversing Valve BO 3 Electric Heat optional BO 4 Economizer ...

Страница 6: ...ctric heat is enabled when heating demand is 75 To configure AI 0 as a sensor set the following parameters TWO STAGES ELECTRIC HEAT Inputs AI 0 Space Sensor or Outside Air Sensor optional AI 2 Supply Air Sensor optional required for economizer control BI 1 PIR Door Window Sensor optional BI 2 Condensate Sensor optional Outputs BO 0 Fan BO 1 Heat Pump Compressor BO 2 Reversing Valve BO 3 Electric H...

Страница 7: ...g demand is 75 Set BV 31 to active by the BMS to indicate that there is water flow To configure AI 0 as a sensor set the following parameters TWO STAGES ELECTRIC HEAT Inputs AI 0 Space Sensor or Outside Air Sensor optional AI 2 Supply Air Sensor optional required for economizer control BI 1 PIR Door Window Sensor optional BI 2 Condensate Sensor optional Outputs BO 0 Fan BO 1 Heat Pump Compressor B...

Страница 8: ...65 To configure AI 0 as a sensor set the following parameters COMPRESSOR SINGLE STAGE ELECTRIC HEAT Inputs AI 0 Space Sensor or Outside Air Sensor optional AI 2 Supply Air Sensor optional required for economizer control BI 1 PIR Door Window Sensor optional BI 2 Condensate Sensor optional Outputs BO 0 Fan BO 1 Compressor BO 2 Not used BO 3 Electric Heat optional BO 4 Economizer Open optional for fl...

Страница 9: ... Set BV 31 to active by the BMS to indicate that there is water flow To configure AI 0 as a sensor set the following parameters TWO STAGE COMPRESSOR TWO STAGE ELECTRIC HEAT Inputs AI 0 Space Sensor or Outside Air Sensor optional AI 2 Supply Air Sensor optional required for economizer control BI 1 PIR Door Window Sensor optional BI 2 Condensate Sensor optional Outputs BO 0 Fan BO 1 Compressor Stage...

Страница 10: ... BV 12 BV 53 Use a 10K Type II Thermistor Sensor for AI 0 and AI 2 Inputs To configure AI 0 as a sensor set the following parameters THREE POINT FLOATING COOLING AND HEATING Inputs AI 0 Space Sensor or Outside Air Sensor optional AI 2 Supply Air Sensor optional required for economizer control BI 1 PIR Door Window Sensor optional BI 2 Condensate Alarm optional Outputs BO 0 Fan BO 1 Cooling Valve Op...

Страница 11: ...Use a 10K Type II Thermistor Sensor for AI 2 Input If the BACnet FF detects that the door or window contact is open during occupancy for a period longer than what is defined in the standby delay AV 20 it will put the unit into standby mode DOOR SENSOR THREE POINT FLOATING COOLING AND HEATING Inputs AI 2 Supply Air Sensor optional required for Economizer control BI 0 PIR Motion Sensor optional BI 1...

Страница 12: ...y air temperature BV 15 Humidity control can be enabled for un occupancy BV 12 BV 53 Use a 10K Type II Thermistor Sensor for AI 2 Input If the BACnet FF detects that the door or window contact is open during occupancy for a period longer than what is defined in the standby delay AV 20 it will put the unit into standby mode DOOR SENSOR LOW MEDIUM HIGH SPEED FAN TWO POSITION COOLING AND HEATING Inpu...

Страница 13: ...demand exceeds 75 Humidity control can be enabled for un occupancy BV 12 BV 53 Use a 10K Type II Thermistor Sensor for AI 2 Input If the BACnet FF detects that the door or window contact is open during occupancy for a period longer than what is defined in the standby delay AV 20 it will put the unit into standby mode DOOR SENSOR LOW MEDIUM HIGH SPEED FAN TWO POSITION COOLING AND HEATING WITH AUXIL...

Страница 14: ...53 Use a 10K Type II Thermistor Sensor for AI 2 Input If the BACnet FF detects that the door or window contact is open during occupancy for a period longer than what is defined in the standby delay AV 20 it will put the unit into standby mode To configure AI 0 as a sensor set the following parameters SINGLE STAGE ELECTRIC HEAT AND 3 SPEED FAN Inputs AI 0 Space Sensor or Outside Air Sensor optional...

Страница 15: ...10K Type II Thermistor Sensor for AI 2 Input If the BACnet FF detects that the door or window contact is open during occupancy for a period longer than what is defined in the standby delay AV 20 it will put the unit into standby mode LOW MEDIUM HIGH SPEED FAN THREE POINT FLOATING OR ANALOG COOLING OR HEATING REMOTE SPACE TEMPERATURE SENSOR Inputs AI 2 Space Temp Sensor optional BI 0 Motion Detecto...

Страница 16: ...nabled for un occupancy BV 53 If the BACnet FF detects that the door or window contact is open during occupancy for a period longer than what is defined in the standby delay AV 20 it will put the unit into standby mode DOOR SENSOR LOW MEDIUM HIGH SPEED FAN THREE POINT FLOATING OR ANALOG COOLING OR HEATING Inputs BI 0 Motion Detector PIR optional BI 1 Door Window Sensor optional BI 2 Main Door Sens...

Страница 17: ...trol can be enabled for un occupancy BV 53 Use a 10K Type II Thermistor sensor for the strap on water supply temperature DOOR SENSOR LOW MEDIUM HIGH SPEED FAN THREE POINT FLOATING OR ANALOG COOLING OR HEATING AND ELECTRIC HEATER Inputs BI 0 Motion Detector PIR optional BI 1 Door Window Sensor optional AI 2 Supply Water Temperature Sensor Outputs BO 0 Fan Low Speed BO 1 Fan Medium Speed BO 2 Fan Hi...

Страница 18: ... set at 2 Humidity control can be enabled for un occupancy BV 53 Use a 10K Type II Thermistor sensor for the strap on water supply temperature WATER TEMP SENSOR LOW MEDIUM HIGH SPEED FAN TWO POSITION OR ANALOG COOLING OR HEATING Inputs BI 0 Motion Detector PIR optional BI 1 Door Window Sensor optional AI 2 Supply Water Temperature Sensor Outputs BO 0 Fan Low Speed BO 1 Fan Medium Speed BO 2 Fan Hi...

Страница 19: ... speed deadband set at 2 Humidity control can be enabled for un occupancy BV 53 AV 23 is used to determine if the water temperature sensor AV 15 sourced from the BMS is to be utilized 0 No 1 cooling 2 heating LOW MEDIUM HIGH SPEED FAN 2 POSITION OR ANALOG COOLING OR HEATING Inputs BI 0 Motion Detector PIR optional BI 1 Door Window Sensor optional BI 2 Main Door Sensor optional Outputs BO 0 Fan Low...

Страница 20: ... 2 Humidity control can be enabled for un occupancy BV 53 Use a 10K Type II Thermistor sensor for the strap on water supply temperature LOW MEDIUM HIGH SPEED FAN 2 POSITION OR ANALOG COOLING OR HEATING AND ELECTRIC HEAT Inputs BI 0 Motion Detector PIR optional BI 1 Door Window Sensor optional AI 2 Supply Water Temperature Sensor Outputs BO 0 Fan Low Speed BO 1 Fan Medium Speed BO 2 Fan High Speed ...

Страница 21: ...the supply air temperature BV 15 Humidity control can be enabled for un occupancy BV 12 BV 53 Use a 10K Type II Thermistor Sensor for AI 2 Input To configure AI 2 as a sensor set the following parameters PIR SENSOR ANALOG COOLING AND HEATING THREE POINT FLOATING ECONOMIZER Inputs AI 2 Space Temperature Sensor Optional or could be a Supply Air Temperature Sensor required for economizer control BI 0...

Страница 22: ...POSITION THREE POINT FLOATING OR ANALOG COOLING OR HEATING VALVE ELECTRIC HEATER ON OFF OR VFD FAN Inputs BI 1 PIR Door Window Sensor optional AI 0 Supply Air Temperature AI 2 Supply Water Temperature Sensor Outputs BO 0 Fan On Off BO 1 Not Used BO 2 Cooling Heating Valve 2 Position Open Close BO 3 Cooling Heating Valve Open 3 Point Floating BO 4 Cooling Heating Valve Close 3 Point Floating BO 5 A...

Страница 23: ...ll CC AV 26 12 1 to 1440 AC HP Compressor Cycle Time mins 0 3 10 C0 AV 27 3 AC HP Compressor Minimum On Runtime mins 0 3 10 CF AV 18 3 AC HP Compressor Minimum Off Runtime mins 0 3 10 Hc AV 28 3 1 to 1440 Heating Stages Cycle Time mins if set to 0 or less this will disable heating 0 5 9 10 13 16 18 h0 AV 29 1 Heating Stages Minimum runtime mins 0 5 9 10 13 16 18 hF AV 80 60 Heating Stages Minimum ...

Страница 24: ...HP Comressor App 10 AV 41 Heat Signal Proportional Gain AV 87 Runtime Cooling Stage 1 AV 42 Heating Signal Integral Gain AV 88 Runtime Cooling Stage 2 AV 43 Cool Signal Proportional Gain BV 21 Reverse Valve Action 1 cool AV 44 Cooling Signal Integral Gain BV 22 1 Cooling Locked Out AV 57 Calc Compr Off time sec BV 27 1 Heating Locked Out AV 58 Calc Compr Cycle time sec BV 6 HP Fun Request AV 59 Ca...

Страница 25: ...BACNET FIXED FUNCTION THERMOSTAT 25 31 00099 01 ...

Страница 26: ...BACNET FIXED FUNCTION THERMOSTAT 31 00099 01 26 ...

Страница 27: ...BACNET FIXED FUNCTION THERMOSTAT 27 31 00099 01 ...

Страница 28: ...utomation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2016 Honeywell International Inc 31 00099 01 M S 05 16 Printed in United States ...

Отзывы: