AQUATROL ZONE SYNCHRONIZING BOILER RESET CONTROLS

69-1979—04

6

TROUBLESHOOTING

Power Disruption 

The AQ251’s system and thermostat (zone settings) 

parameters are stored in non-volatile memory and are 

updated as they change. 

When a power disruption or loss of power occurs, the system 

configuration is retained in memory. 

When power is restored, the AQ251 Control Panel enters 

auto-detection mode, reads its previously-stored settings, and 

initializes all AQUATROL network components according to 

their saved parameters.

POWER DISRUPTION GREATER THAN 4 HOURS

If a power disruption lasts for more than 4 hours, the AQ251 

will have discharged its internal super capacitor, and the 

DATE and TIME OF DAY settings will need to be reset.

Upon restart, the AQ251 displays its clock settings as: YEAR 

= 2008, MONTH = JAN, DATE = 1. The message PLS SET 

DAY/TIME displays. This displayed message continues until 

the DATE and TIME OF DAY are updated.

NOTE: If the power failure parameter is set to Backlight 

(USER MENU > PREFERENCES/TIME), the LCD 

backlight flashes repeatedly, along with the mes-

sage.

The AQ251 remains permanently in OCCUPIED (or Comfort) 

mode until the DAY and TIME OF DAY are updated.

System Status and Error Codes

System status alerts and error messages display on the 

System Status Page. These messages are shown in Table 2. 

Table 2. LCD Status Notices and Error Messages.

LCD Display

Parameter

Meaning

A/C MIN. OFF TIME

n/a

The A/C compressor is disabled, because the minimum OFF time has not yet elapsed.

A/C MIN. ON TIME

n/a

The A/C compressor is active and the minimum ON time has not yet elapsed.

AUX IN EM. SHUT

n/a

Auxiliary Input's Emergency Shut Down is active.

BOILER:

EM SHUT

Boiler is disabled, because the AQ251 is in Emergency Shut Down mode.

FRZ PROT

Boiler freeze protection activated:

Communication between Control Module and Zoning Module has been lost for more 

than 1 minute

or

Boiler supply temperature is less than 50°F (10°C)

HEAT DHW

Boiler is active to serve DHW.

HEATING

Boiler is active to serve zones.

IDLE

Boiler is not active.

INIT

Boiler contacts (terminals 22 and 23) on the AQ1520, which are connected to the 

boiler's T-T terminals, have been shorted and the boiler is beginning its firing sequence.

INST PURG

Boiler is active while the AQ251 is conducting the PURGE operation in the Installer 

Setup.

NSTALL

Boiler is in ready mode during Installer Setup.

PMP EXER

Boiler is disabled while the AQ251 is exercising all pumps and valves connected to the 

AQUATROL network.

POST PURG Boiler is active with Post Purge operation and is sending the purged water to the Boiler 

(Primary) loop.

PURGE DHW Boiler is active with Post Purge operation and is sending the purged water to the DHW 

tank.

CALL FOR COOL

n/a

At least one zone with a programmable thermostat requires cooling.

CALL FOR DHW

n/a

The DHW requires heat.

CALL FOR HEAT

n/a

At least one zone requires heat.

CWSD ACTIVE

n/a

Zone calls for cooling are not served because CWSD (Cold Weather Shutdown) is in 

progress.

DHW DISABLE

n/a

DHW call is not served because it is disabled.

LOST ZONE A-1

         …
LOST ZONE D-16

n/a

Lost communication with a zone (A-1 to A-16, B-1 to B-16, C-1 to C-16, or D-1 to D-16).

NO DHW PROBE

n/a

No DHW sensor connected or it is defective.

NO OUTDOOR PROBE

n/a

No outdoor sensor connected or it is defective.

Содержание AQ251

Страница 1: ... experienced licensed service technicians should service this Control Panel The front cover of the AQ251 Control Panel should not be removed as this will expose the user to potentially dangerous line voltage 120V electricity Congratulations The AQUATROL AQ251 installed on your heating system is the most powerful yet user friendly hydronic heating control system available on the market for resident...

Страница 2: ...umber the displayed value will decrease increase by pressing these buttons When holding the or button for more than a second the values automatically decrease increase at a faster pace similar to setting the time on a digital clock radio If the menu item is an option pressing these buttons scrolls through the list of available options one at a time Fig 1 LCD Dot Matrix Display Layout Model Functio...

Страница 3: ...tback schedule you must use the or button to change the time 2 The OK button when pressed defaults the time setting to midnight If the active menu item leads to a further sub menu pressing the OK button displays the sub menu options on the LCD Scroll through this sub menu to position the indicator arrow beside the desired menu item to input or modify Choose one of the options provided or input the...

Страница 4: ...for both the AQ251 control s LCD and the zone thermostats The time display in 12 hour e g 7 00 PM or 24 hour format e g 19 00 Date and time of day allows building owner to reset day and time of day in the event of a power outage of more than 4 hours refer to Troubleshooting section The Home Page display view Simple or Detail The factory default is Detail The LCD Backlight illuminated permanently O...

Страница 5: ...ur programs have been set select the COPY TO ALL DAYS option This displays the prompt COPY TO ALL DAYS ARE YOU SURE Select Yes by positioning the indicator arrow at YES and press the OK button Next the same list of days as EDIT DAILY described in step 1 displays except that all days now show the times for the WAKE LEAVE RETRN and SLEEP programs that you set in the EDIT ALL DAYS menu If you do not ...

Страница 6: ...ve and the minimum ON time has not yet elapsed AUX IN EM SHUT n a Auxiliary Input s Emergency Shut Down is active BOILER EM SHUT Boiler is disabled because the AQ251 is in Emergency Shut Down mode FRZ PROT Boiler freeze protection activated Communication between Control Module and Zoning Module has been lost for more than 1 minute or Boiler supply temperature is less than 50 F 10 C HEAT DHW Boiler...

Страница 7: ...ntractor quickly identify the lost zone and fix its wiring to re establish communication with the Control Module NO RETURN PROBE n a No return sensor connected or it is defective NO SUPPLY PROBE n a No supply sensor connected or it is defective SHORT CYCLE PROT n a There is a call for heat but less than two minutes have elapsed since the last firing of the boiler prevents short cycling VALVE INIT ...

Страница 8: ...CLE PROT VALVE INIT WATER READY WWSD ACTIVE SYSTEM STATUS 1 ZONE A 1 ROOM TEMP FLOOR TEMP SETPOINT 70 FLOOR SETPT 70 HEAT COOL STATUS SETBACK 7 SETPOINT MAX 100 SETPOINT MIN 41 FLOOR LIM HI 100 FLOOR LIM LO 41 SETPOINT VACANCY HEAT 41 SETPOINT VACANCY COOL 100 CHANGEOVER 2 KEYBOARD UNLOCK ZONE SETTINGS All or Single 2 ARE YOU SURE NO YES MON WAKE 6 00A MON LEAVE 8 00A MON RETRN 4 30P MON SLEEP 10 ...

Отзывы: