31-00559-01
27
Figure 4.10.
Motor, Line Power and Ground Wiring for Enclosure Types B and C
Using Conduit.
4.7 AC Line Input Connection
•
Size wiring based upon the input current of the adjustable frequency drive. For
maximum wire sizes, see Chapter 8.1 Electrical Data.
•
Comply with local and national electrical codes for cable sizes.
Procedure
Step 1.
Connect 3-phase AC input power wiring to terminals L1, L2, and L3 (R, S
and T on Frame D) (see Figure 4.11 and Figure 4.12).
Step 2.
Depending on the configuration of the equipment, input power will be
connected to the line power input terminals or the input disconnect.
Step 3.
Ground the cable in accordance with grounding instructions provided in
Chapter 4.3 Grounding.
Step 4.
When supplied from an isolated line power source (IT line power or
floating delta) or TT/TN-S line power with a grounded leg (grounded
delta), ensure that 14-50 RFI Filter is set to OFF to avoid damage to the
intermediate circuit and to reduce ground capacity currents in
accordance with IEC 61800-3.
130BB477.10
91
L1
92
L2
93
L3
96
U
97
V
99
W
88
DC+
89
DC-
91
R-
9
R+
95
99
Содержание 3G SmartVFD HVFD3D2A0020
Страница 1: ...3G SmartVFD Installation and User Guide ...
Страница 5: ...iv 31 00559 01 ...
Страница 15: ...10 31 00559 01 ...
Страница 19: ...14 31 00559 01 ...
Страница 23: ...18 31 00559 01 ...
Страница 53: ...48 31 00559 01 ...
Страница 83: ...78 31 00559 01 ...
Страница 109: ...103 31 00559 01 ...
Страница 125: ...119 31 00559 01 ...
Страница 126: ......
Страница 127: ... Honeywell 715 Peachtree Street NE Atlanta GA 30308 buildings honeywell com 31 00559 01 08 22 ...