System Programming
Tx Info Menu
Alarm A, B and C Menus
Since the display screens are identical for each of the Alarms, they
have been combined into one section for the purpose of this manual.
However, each Alarm must be configured separately according to your
specifications.
This option allows you to set minimum and maximum alarm levels for
alarms A, B and C. What this does is set a tolerance range within
which no actions are taken. However, if gas concentrations should go
over the set maximum level, an alarm will be triggered. The alarm will
not be shut off and reset until gas concentrations fall below the
minimum level defined.
•
Use the keypad arrows to move the cursor arrow to either MIN or
MAX
•
Press Enter to select the field for modification
•
Use the keypad up or down arrows to increase or decrease the
value
•
Press Enter to validate the value.
1. Tx Info
001
-Alarm A-
MIN
MAX
0.00%
0.00%
1. Tx Info
001
-Alarm A-
MIN
MAX
0.00%
0.00%
Содержание 301C
Страница 1: ...Centrale Controller Manuel de l utilisateur 301C User Manual ERP 510324 4 07 ...
Страница 2: ......
Страница 3: ...Controller Unit 301C User Manual ERP 510324 4 07 ...
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 14: ......
Страница 108: ......
Страница 110: ......
Страница 114: ......
Страница 115: ...Centrale 301C Manuel de l utilisateur ERP 510324 4 07 ...
Страница 116: ......
Страница 118: ......
Страница 120: ......
Страница 122: ......
Страница 126: ......
Страница 210: ......
Страница 220: ......
Страница 226: ......
Страница 228: ......
Страница 232: ......