Coarse adjustment of motive air at the 

eductor

 

The settings of the air volume and the motive air 

at the eductor affect each other. Coarse adjust-
ment should be carried out at the same time 
during pre-purge.

p

FG

p

atm

p

FG

0

p

FG

8

7

9

Loosen 
the screw 
2 turns.

 

Measure the negative flue gas pressure p

FG

 

against atmospheric pressure p

atm

.

 0 

 Set the required negative flue gas pressure on 

the motive air restrictor. Use the values from the 
eductor diagram, see www.docuthek.com.

Pressure switch

 

If the burner is equipped with an air flow detector 
set ECO/E, the switching point should be set to 
approx. 80% of the pressure differential for the 
combustion air.

 

Set the DW set for monitoring the flue gas flow 
to the required pressure shown in the enclosed 
documentation.

Preparing the gas pressure measurement
  

  Connect all measuring devices to the burner for 

later adjustment. 

 

Leave the gas supply closed.

  

  Read off the differential pressure for the required 

gas flow rate from the enclosed flow rate curve.

  

 p1: gas pressure upstream of the measuring 

orifice, p2: gas pressure downstream of the 
measuring orifice. Measuring range: select ap-
prox. 15 mbar.

 

Gas measuring nipple 

G

, outside dia. = 9 mm 

(0.35").

G

p

1

p

2

4

5

Loosen 
the screws 
2 turns.

Commissioning

Igniting and adjusting the burner

 WARNING

Ensure adequate ventilation of the furnace chamber 
before each burner start!
Risk of burning! Outflowing flue gases and burner 
components are hot.
Wear ear defenders to protect yourself from harm-
ful noise. 

 

When heating up for the first time, vapours may 

be emitted from gaskets or paint coatings, for 
example, which may cause unpleasant odours.

  

  All valves of the installation must be checked for 

tightness before ignition.

Coarse adjustment with the furnace cold

 

Coarse adjustment of the air volumes, see 
page 7 (Preparing commissioning).

  

 Limit the maximum gas volume.

 

Open the restrictor around halfway.

  

 Open the gas supply.

 4 

 Ignite the burner.

 

The safety time of the automatic burner control 

unit starts to elapse.

 5 

 Check and adjust the gas and air pressures.

 6 

  If no flame is formed, reset the automatic burner 

control unit, purge the combustion chamber and 
ignite the burner again.

 

CAUTION

Pre-purge the furnace chamber or radiant tube 
with air (5 x volume) before every ignition attempt.

 

The burner ignites and proceeds to normal op-

eration.

 

 If no flame is formed after repeating steps 

5

 and 

6

 multiple times – see page 15 (Assistance in 

the event of malfunction).

 7 

  Check the differential pressures ∆p

gas

 and ∆p

air

 

and the negative flue gas pressure p

FG

, and set 

them to their desired values.

 

The gas, air and motive air settings affect each 

other. We recommend reading these pressures 
at the same time.

 

Check the settings by conducting a flue gas 
analysis (in the flue gas connector in the case of 
an indirect heating system or in the furnace in the 
case of a direct heating system). Ensure that the 
furnace pressure is positive for a direct heating 
system to avoid falsification of the measurements 
by infiltrated air.

Содержание 03251385

Страница 1: ... may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Contents Operating instructions D GB GB 1 03251385 Translation from the German Self recuperative burner ECOMAX Self recuperative burner ECOMAX 1 Contents 1 Safety 1 Checking the usage 2 ...

Страница 2: ...with VAH Burner with customized orifices Burner construction stage X for nnn kW Burner without orifices 1 to 99 Burner head identifier X A B Construction stage The following features differ from the standard version K Additional cooling air connection for increased furnace cooling A Electrode made of Kanthal APM T NPT connections S SICAFLEX spacer W Air connection without intermediate flange Z Spe...

Страница 3: ... than the outside diameter of the FGT Do not stress the FGT with forces from the furnace lining Wrap the FGT in a fibre blanket before installing the burner Complete the fibre wrapping to match the ap erture in the furnace wall Depending on the fur nace lining and the type of expected movements in the furnace wall the annular void must be at least 25 mm Use a larger annular void if neces sary Wrap...

Страница 4: ...ing operation damage to the protec tive oxide layer on the surface of the radiant tube can cause corrosion and thus reduce the service life We recommend that someone be inside the furnace chamber to receive the radiant tube Note for detailed information refer to SER C operating instructions 1 2 Depending on the installation situation a flue gas guide tube FGT set SER C may be required With metalli...

Страница 5: ...X 0 R Rp 1 Rp 1 ECOMAX 1 R Rp 1 Rp 1 ECOMAX 2 R Rp 1 Rp 1 ECOMAX 3 R Rp 2 Rp 1 ECOMAX 4 R Rp 2 Rp 2 ECOMAX 5 R 1 Rp 2 Rp 2 ECOMAX 6 R 1 Rp 3 N A On the ECOMAX L for LCV gas connections may differ depending on the project specifications Install flexible tubes or bellows units to prevent mechanical stress or transmission of vibration Ensure that the gaskets are undamaged DANGER Risk of explosion Ens...

Страница 6: ...NGER Electric shocks can be fatal Before working on possible live components ensure the unit is discon nected from the power supply The flame is monitored by a combined flame rod spark electrode as standard on the burner ECOMAX Flame control with a UV sensor is necessary if a furnace temperature of 1050 C is exceeded for direct heating or 950 C for indirect heating In this case we recommend a UV s...

Страница 7: ... switched on and off several times check the entire system DANGER Risk of explosion Fill the gas line to the burner carefully and correctly with gas and vent it safely into the open air do not discharge the test volume into the furnace chamber Determining the gas and combustion air flow rates Qgas PB Hi Qair Qgas λ Lmin Qgas Gas flow rate in m3 h ft3 h PB Burner capacity in kW BTU h Hi Gas heating...

Страница 8: ...sis of the maximum furnace temperature and burner capacity If the gas flue extraction rate is 80 90 at maximum furnace temperature a negative fur nace pressure will generally be avoided even at a furnace temperature reduced by 400 500 C In the case of heavily leaking furnaces flue gas extraction must be reduced where necessary to avoid pulling in cold air due to negative pressure in the furnace ch...

Страница 9: ...lue gases and burner components are hot Wear ear defenders to protect yourself from harm ful noise When heating up for the first time vapours may be emitted from gaskets or paint coatings for example which may cause unpleasant odours 1 All valves of the installation must be checked for tightness before ignition Coarse adjustment with the furnace cold Coarse adjustment of the air volumes see page 7...

Страница 10: ...sure in the furnace chamber reduce the flue gas extraction rate to avoid infiltrated air Blocking and recording the settings 13 Produce a measurement report 14 Remove the measuring devices and close off the pressure taps tighten the grub screws 15 Block and seal the adjusting elements 16 Induce a flame failure e g by pulling the terminal boot off the flame rod The flame detector must close the gas...

Страница 11: ...ixing device gas lance and insulator for dirt wear and thermal damage and cracks clean or replace if necessary Checking and replacing the spark electrode flame rod 15 20 L 1 3 4 Ensure that the electrode length does not change 16 Remove dirt from electrode or insulator 17 Replace the electrode if the tip 4 or insulator 3 is damaged The electrode rod can also be replaced on its own Before changing ...

Страница 12: ...The electrode must always be positioned at the top left 3 4 3 8 mm 23 Fully tighten the union nut Replacing the combustion chamber on ECOMAX 4 5 15 17 18 16 21 20 19 Press the retaining star against the spring Guide the feet through the openings provided for them Slowly allow the star to be pressed against the ceramic component Release the feet by turning them Press the ce ramic com po nent agains...

Страница 13: ...OMAX C CAUTION Risk of breakage The air guide tube and recu perator in the ECOMAX C are made of ceramic material 1 4 2 3 5 5 Check the recuperator If any ceramic components are damaged they must be replaced To check the body insulation carefully and replace the recuperator remove the burner and suspend it vertically e g on two beams 8 6 7 9 11 10 Checking the insulation If the insulation is worn o...

Страница 14: ...nt it falling over The gas insert must be removed to avoid breaking the ceramic combustion chamber when placing the burner We recommend that the body insulation be re placed when fitting a new recuperator b a 9 7 5 6 8 10 11 12 Place the new recuperator vertical and secure it to prevent it falling over b a 9 7 5 6 8 10 11 12 Hold the body insulation together e g using adhe sive tape Tighten the nu...

Страница 15: ...ANGER Electric shocks can be fatal Before working on possible live components ensure the unit is discon nected from the power supply Risk of injury Burner heads have sharp edges Fault clearance must only be undertaken by author ized trained personnel If no fault is detected when checking the burner proceed to the automatic burner control unit and check for faults in accordance with the relevant op...

Страница 16: ...just ing cock Excessive restriction may cause soot formation Burner performs a fault lock out after burn ing faultlessly in normal operation Incorrect gas and air flow rate settings Check the gas and air pressures Automatic burner control unit signals a fault Check the ionization cable Check the ionization current The ionization cur rent must be at least 5 µA stable signal Mixing device or swirl p...

Страница 17: ...vacuum moulded pulp Available on request in different sizes suitable for the SER C radiant tube and ECOMAX burner sizes Segmented flame tube SICAFLEX Segmented ceramic flame tubes to guide hot flue gases in radiant tubes Material SiSiC The SICAFLEX is not supplied with the ECOMAX and must be ordered separately Purge air cooling air nozzles Nozzles to limit the volume of purge air in order to achie...

Страница 18: ...lue 5 per 1000 m above MSL WARNING Information pursuant to REACH Regulation No 1907 2006 Article 33 Insulation contains refractory ceramic fibres RCF aluminium silicate wool ASW RCF ASW are listed in the Candidate List of the European REACH Regulation No 1907 2006 Information on the safe handling of products containing ceramic fibres can be found in the safety data sheets Safety data sheets are av...

Страница 19: ...n technischen Unterlagen gemäß Anhang VII B wurden erstellt und werden der zuständigen nationalen Behörde auf Verlangen in elektronischer Form übermittelt The relevant technical documentation has been compiled in accordance with part B of Annex VII and will be sent to the relevant national authorities on request as a digital file Die unvollständige Maschine darf erst dann in Betrieb genommen werde...

Страница 20: ... office agent The addresses are available on the Internet or from Elster GmbH We reserve the right to make technical modifications in the interests of progress Elster GmbH Strotheweg 1 D 49504 Lotte Büren Tel 49 541 1214 0 Fax 49 541 1214 370 hts lotte honeywell com www kromschroeder com Contact ...

Отзывы: