F1 Res 44 Horizontal Side Wall

Details below are taken from data supplied by the head manufacturer.

Up to 4.9 x 6.1 metres coverage from 1 head

Temperature Range

68°C or  79°C

Escutcheon  F2

Installation Data

RRP

Thread

K

Maximum

Maximum

40.00

$   

Size

Factor

Pressure

Ambient

Plus GST

mm

kPa

Temperature

 38°C
 66°C

Minimum Spacing of 4.3 Metres

Ceiling to

LPM

Pressure

Deflector

kPa

45.4

52

53

71

60.6

92

68.1

116

72

129

87.1

189

53

71

60.6

92

64.4

104

75.7

143

87.1

189

Features

1 Residential
2 Quick Response
3 3mm Glass bulb
4 Pressure Rated 1200 kPa

5 Tested to 3445 kPa

6 Tread Size 1/2" NPT

7 Minimum Density of 2.03 LPM per square metre

Listings & Approval

1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus)
2. NYC MEA 258-93-E

4.9 x 6.1

101 - 152mm

152 - 305mm

4.9 x 5.5

4.9 x 5.5

3.6 x 3.6
4.3 x 4.3
4.9 x 4.9

4.3 x 4.3
4.9 x 4.9

5.5 x 5.5
4.9 x 6.1

Sprinkler Length

62 mm

Max Spacing

15mm

63

1200

3.6 x 3.6

Product Description

The F1 Res Horizontal Sidewall sprinklers (Figs.1 and 2) are equally attractive when above ceiling piping
cannot is used.
The 3mm glass-bulb pendent sprinklers, with a K-Factor of 63, permit the efficient use of residential
water supplies for sprinkler coverage in residential fire protection design.
The low flow F1 Res sprinklers are specially engineered for fast thermal response to meet the
sensitive fire protection application needs of the latest residential market standards 
(UL 1626 Standard effective 7/12/02).
Upon fire conditions, rising heat causes a sprinkler’s heat-sensitive glass-bulb to shatter, releasing the
waterway for water flow onto the deflector, evenly distributing the discharged water to control a fire.