TRAINING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Rise Voice 

     Evacuation System

 

VoiceNET

firealarmresources.com

Содержание VoiceNET

Страница 1: ...T R A I N I N G High Rise Voice Evacuation System VoiceNET firealarmresources com...

Страница 2: ...B Speaker Lines 1 6 4 Four Class A Speaker Lines 1 6 5 Four Dual Class B Speaker Lines 1 6 6 DP25 P Internal View 1 6 7 FPI and Phone Connection Details 1 6 8 AMI and Amplifier Connection Details 1 6...

Страница 3: ...ries 4 6 1 FO Fiber Optic Transceiver 4 6 2 ISO Serial Port Isolator 4 6 3 LLC LED Annunciator Card 4 6 4 ZA Class A Adapter 4 6 5 ZAB Dual Class B Adapter 4 6 6 BA Backup Amplifier Switcher 4 6 7 Cab...

Страница 4: ...safety agencies The Hochiki FNV system provides this voice evacuation function and much more Evacuating a high rise building poses major challenges Elevators are needed for fire department use and hu...

Страница 5: ...r relocation procedures and emergencies Building management and fire brigades can monitor and control emergency response even before the professionals arrive The FNV system includes capacity for 6 cha...

Страница 6: ...R E E F F I I R R E E F F I I R R E E TB1 TB3 TB2 TB1 TB3 TB2 TB1 TB3 TB2 TB1 TB3 TB2 Voice Evacuation Speaker Circuits Fire Phone Fire Phone FNV DP Distributed Panel FNV DP Distributed Panel F F I I...

Страница 7: ...loor 5th Floor 3rd Floor 6th Floor 7th Floor 8th Floor 9th Floor 10th Floor 11th Floor S P FNV DP S S P S S P S S P S S P FNV DP S S P S S P S S P S Hochiki FNV High Rise Multiplex 11 Floor Typical Ri...

Страница 8: ...FNV MP32 Master Panel Front Panel View PAGING CONTROL SYSTEM RESET PAGE ALL CALL FAULT SILENCE 1 5 1 firealarmresources com...

Страница 9: ...TB3 TB3 TB4 TB4 TB5 TB5 P1 P1 P2 P2 P3 P3 P4 P4 J1 J1 1 1 2 2 3 3 LED3 LED2 LED1 TB1 P4 P3 P1 P2 P5 P5 DCC ASC PWR 2A 3 1 2 2 1 TB2 TB3 TB1 3 2 1 FNV MP32 Master Panel Internal View DCC ASC SSC fireal...

Страница 10: ...FNV MP32 P Master Panel Front Panel View PAGING CONTROL SYSTEM RESET PAGE ALL CALL FAULT SILENCE 1 5 2 firealarmresources com...

Страница 11: ...32 P Internal View TB1 P4 P3 P1 P2 P5 P5 ASC PWR 2A 3 1 2 2 1 TB2 TB3 TB1 3 2 1 TB1 TB1 TB2 TB2 TB3 TB3 TB4 TB4 TB5 TB5 P1 P1 P2 P2 P3 P3 P4 P4 J1 J1 1 1 2 2 3 3 LED3 LED2 LED1 DCC DCC ASC SSC I O Car...

Страница 12: ...M RESET PAGE ALL CALL FAULT SILENCE PAGING CONTROL SYSTEM RESET PAGE ALL CALL FAULT SILENCE PAGING CONTROL SYSTEM RESET PAGE ALL CALL FAULT SILENCE Min Max Panel Configurations PAGING CONTROL SYSTEM R...

Страница 13: ...PAGING CONTROL SYSTEM RESET PAGE ALL CALL FAULT SILENCE FNV MP272 P firealarmresources com...

Страница 14: ...1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 MESSAGE GAIN MIC GAIN FAULT NORMAL ALARM YEL GRN RED J2 1 2 3 J1 P2 S1 SN1 DCC TB1 TB2 TB3 TB4 TB5 P1 P2 P3 P4 J1 1 2 3 LED3 LED2 LED1 DCC MBR TB2 TB3 TB4 TB5 T...

Страница 15: ...I M B K 1 4 3 2 1 EOLR EOLR F F I I R R E E F F I I R R E E F F I I R R E E F F I I R R E E Standard Life Safety Speakers Strobes connected and powered separately E O L E O L 4 CLASS B OUTPUTS One AMI...

Страница 16: ...d Life Safety Speakers Strobes connected and powered separately E O L E O L E O L M B K 2 EIGHT CLASS B SPEAKER LINES 1 2 3 4 5 6 7 8 F F I I R R E E F F I I R R E E F F I I R R E E F F I I R R E E F...

Страница 17: ...AKER LINES F F I I R R E E F F I I R R E E F F I I R R E E F F I I R R E E EOL EOL EOLR EOLR E O L E O L F F I I R R E E F F I I R R E E F F I I R R E E F F I I R R E E Standard Life Safety Speakers S...

Страница 18: ...ORMAL ALARM YEL GRN RED J2 1 2 3 J1 P2 S1 SN1 DCC TB1 TB2 P1 P2 P3 P4 J1 1 2 3 LED3 LED2 LED1 DCC MBR TB2 TB3 TB4 TB5 TB6 TB7 TB8 1 2 3 4 TB1 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1...

Страница 19: ...r Limited 1 2 3 4 FNV DP25 P Phone Connection Detail Fire Phone Handset Jack Fire Phone Handset Jack Fire Phone Handset Jack Fire Phone Handset Jack 10K 1 2W EOLR 10K 1 2W EOLR Fire Phone Loop Fire Ph...

Страница 20: ...2 1 2 3 J1 P2 S1 SN1 DCC TB1 TB2 P1 P2 P3 P4 J1 1 2 3 LED1 DCC MBR TB2 TB3 TB4 TB5 TB6 TB7 TB8 1 2 3 4 TB1 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 A M I F P I 1 F P I 2 M B K 1...

Страница 21: ...A M I A M I NOTE Ribbon cables connecting to AMI and FPI boards are illustrated on separate sheet Please check ribbon cable positioning BEFORE inserting these boards J7 10 pin ribbon 1 6 8 firealarmre...

Страница 22: ...f cabinet To second amplifier module right side of cabinet TB1 TB3 TB2 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 MESSAGE GAIN MIC GAIN FAULT NORMAL ALARM YEL GRN RED J2 1 2 3 J1 P2 S1 SN...

Страница 23: ...shown by the orientation of the red stripe at both ends of the ribbon cable Second FPI in system connects to MBR Slot P4 Ribbon cable 24 connects to FPO card as shown Observe polarity as shown by the...

Страница 24: ...MBK MBK MBK First MBK First MBK Second MBK 1 6 9 firealarmresources com...

Страница 25: ...facing the right side of MBR Second FPI if used installs in next slot to the left MBK First MBK installs in second slot in from the left on MBR note heavy connectors with white base Make sure that po...

Страница 26: ...TB3 TB4 TB5 TB6 TB7 TB8 1 2 3 4 TB1 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 DCC TB1 TB2 TB3 TB4 TB5 P1 P2 P3 P4 J1 1 2 3 LED3 LED2 LED1 P3 LED1 P2 MFP OUT TO FIRST DISTRIBUTED...

Страница 27: ...3 4 1 2 3 4 1 2 3 4 1 2 3 4 TB1 TB2 TB3 TB4 TB5 P1 P2 P3 P4 J1 1 2 3 LED3 LED2 LED1 P3 LED1 P2 P1 MFP MASTER PANEL DISTRIBUTED PANEL NetComm Loop Wiring Style 7 Redundant Communication Bus Primary Com...

Страница 28: ...I R R E E F F I I R R E E F F I I R R E E A single channel DP only requires a single amplifier It may be sized with 25 50 or 100W modules The amplifier size determines the maximum load per circuit It...

Страница 29: ...I I R R E E F F I I R R E E F F I I R R E E A dual channel DP requires two amplifiers It may be sized with 25 50 or 100W modules The amplifier size determines the maximum load per circuit It is now a...

Страница 30: ...NOTES firealarmresources com...

Страница 31: ...arm by Zone In many high rise applications and certainly where buildings exceed 10 or 12 stories evacuation of the entire building is impractical Therefore the system needs to generate alarm and evac...

Страница 32: ...system driving 4 floors from a Distributed Panel DP the maximum load will be 3 out of the 4 circuits on one amplifier If the circuits are uniformly loaded that would be a max load of 8Watts W with 25...

Страница 33: ...size channel and fire phone option FNV DP50 P designates a panel with 50W dual channel capacity and fire phones By dropping the P suffix fire phones are eliminated Standard configuration is 4 Class B...

Страница 34: ...io 4 Spkr Zones 4 Fire Phone Circuits Mother Board Relays FNV MBK 2 Fire Phone Interface FNV FPI 1 Fire Phone Output Card FNV FPO 1 Telephone Jack SG Plate FNV FJ 38 Portable Handset Telephone Cabinet...

Страница 35: ...peaker Circuit 6 Speaker Circuit 5 Firephone Circuit Penthouse Firephone Circuit 8 Firephone Circuit 7 Firephone Circuit 6 Firephone Circuit 5 Firephone Circuit 4 _____ _____ _____ _____ _____ _____ _...

Страница 36: ...Panel FNV MP80 P 1 Master Panel 80 Switch Control w Master Fire Phone Distributed Panel FNV DP50 P 4 Dist Panel 50W Dual Channel Audio 4 Spkr Zones 4 Fire Phone Circuits Mother Board Relays FNV MBK 4...

Страница 37: ...CIRCUIT 8 SPEAKER CIRCUIT 1 SPEAKER CIRCUIT 8 FIREPHONE CIRCUIT 1 FIREPHONE CIRCUIT 12 FIREPHONE CIRCUIT 1 FIREPHONE CIRCUIT 8 FIREPHONE CIRCUIT 1 FIREPHONE CIRCUIT 8 FIREPHONE CIRCUIT 1 FIREPHONE CIR...

Страница 38: ...Dist Panel 50W Single Channel Audio 4 Spkr Zones 4 Fire Phone Circuits Mother Board Relays FNV MBK 2 100W Back Up Module FNV 100E 1 Back Up Relay Card FNV BA 3 Telephone Jack SG Plate FNV FJ 6 Portabl...

Страница 39: ...it 11 Speaker Circuit 10 Speaker Circuit 9 Firephone Circuit 4 Firephone Circuit 3 _____ _____ _____ _____ _____ _____ _____ _____ _________ _________ Speaker Circuit 20 Speaker Circuit 19 Speaker Cir...

Страница 40: ...NOTES firealarmresources com...

Страница 41: ...2 0 FNV Voice Evacuation Programming Guide EFFECTIVE July 2002 Contents Subject to Change Without Notice firealarmresources com...

Страница 42: ...Most of these commands are for special applications Most systems contain the basic programming of Paging Fire Fighter phone and Evac Completing a Configuration Form allows the factory to program and t...

Страница 43: ...VAC 9 SIGNAL SILENCE 9 ALARM RESTORE 9 SPECIAL GROUPING 10 GROUP 230 10 GROUP 240 10 DISTRIBUTED PANEL PROGRAMMING 11 GET ID 11 SET AMI 11 SET MBR 11 SET FPI 11 SET OI 11 GF ENABLE 11 GF DISABLE 11 CL...

Страница 44: ...FAULT REPORT 17 PRINT FAULT REPORT 17 PRINT FAULT LOG 17 Activity Report Example 17 MASTER CLEAR ALL 17 REMOTE CLEAR ALL 17 PROGRAM SAVE 17 LIST MODES 18 List Modes Example 18 MASTER LIST ACCESSORIES...

Страница 45: ...will open called PHONE NUMBER go to Connect using line Choose DIRECT to COM 1 Or whatever com port your laptop uses for serial communication 11 Click OK 12 COM 1 Properties box will open under PORT SE...

Страница 46: ...ERMINAL o Connect the Communication cable from your Computer to the ASC input connector P2 Com 1 in the FNV Master panel o Power up the Hochiki Voice System o You should see the Master panel DCC seria...

Страница 47: ...will enable the system operator to answer a call in from a Fire Fighter Phone Circuit or Warden Station of a Distributed Panel programmed as FIRE PHONE 101 There may be only one phone circuit assigned...

Страница 48: ...to the same Group Number Programming this switch for Group EVAC will only activate the speaker circuits also programmed to follow the same Group Number and does not use Floor Above Floor Below GENERA...

Страница 49: ...el to send the selected Tone or Message to any area Must be used in conjunction with Play Point command to select output zone SET INPUT 4 PLAY MESSAGE Input 4 when activated plays a pre determined mes...

Страница 50: ...this zone is put into Alarm It will also not respond to Page All Call Commonly used where Stairwells are only paged manually and should remain silent otherwise and in elevator cabs Use Page point outs...

Страница 51: ...st amplifier in the system SET MBR Sets the Distributed Panels MBR outputs speakers REMOTE 3 SET MBR 1 PAGE 1 Distributed Panel 3 1 st speaker circuit will turn on for Page 1 SET FPI Sets the Distribu...

Страница 52: ...utput is a Paging Point Zone REMOTE 1 SET AMI 1 PAGE 2 GROUP 1 AMI card output may control an amplifier or group of amplifiers as a single Page point LOCAL EVAC PAGE AMI output is programmed to activa...

Страница 53: ...ted Panels 1 st NAC circuit will activate on EVAC 1 Will only silence on Alarm Restore or Reset EVAC MBR output when same Point is in Alarm silence able Use only with strobe option input on MBR REMOTE...

Страница 54: ...Points if Page 3 is in Alarm Page 4 and Page 5 follow SET ALERT BY ZONE Default Setting The Alert Signal will NOT be broadcast to all floors not in Alarm No Alert signal is transmitted SET ALERT BY ZO...

Страница 55: ...sure from an II Card SET BELL EVAC In standby NAC circuit will supervise the FNV system for any Fault condition On polarity reversal FNV system will broadcast the Evac tone message only to those Page...

Страница 56: ...viewing of all system activity on the screen HyperTerminal Times out after 30 minutes FDE Example Activity Report Time Date Type Item Condition Point Output Function Status Condition Remote DP NO Act...

Страница 57: ...e Restored MASTER CLEAR ALL Master Panel Clear MASTER CLEAR ALL Clears all Master Panels program information If extensive changes are made to the master panel it is recommended that its memory be comp...

Страница 58: ...EW YORK MODE OFF SET INPUTS NON LATCHED SET DISABLE FACP SUPERVISION SET MESSAGE PRIORITY OFF SET MASS MODE OFF SET BELL SUPERVISORY SET SMOKE CONTROL ENABLE OFF SET SIGNAL RESOUND DISABLE Ok MASTER L...

Страница 59: ...han 20 Seconds MP MF Mic Fault MMC microphone missing or faulted BI Bus Interface primary comm bus fault SI Secondary Bus Interface secondary comm bus faulted SF Switch Scan Card Fault SSC fault DF Fa...

Страница 60: ...he Floor of Incidence and to the Floor Above Following this a Inquiry Tone Chime plays for 15 seconds to the entire building This sequence repeats until there is a silence or reset of the Fire Alarm C...

Страница 61: ...e will be generated EVAC The EVAC command is the actual Alarm Tone or Message that has been predetermined for the system what floor it is being sent to is determined by the PAGE number that has been t...

Страница 62: ...remote 4 set ami 1 auto 1 remote 4 set ami 2 auto 2 _____________________________ Program on 1111 remote 5 set mbr 1 page 17 group 1 remote 5 set mbr 2 page 17 group 1 remote 5 set mbr 3 page 18 group...

Страница 63: ..._________________________ ___________________________________________________________________ ___________________________________________________________________ ______________________________________...

Страница 64: ...er Circuit loads are unevenly distributed please fill out the following Wattage List Ckt Floor Wattage Ckt Floor Wattage 1 21 2 22 3 23 4 24 5 25 6 26 7 27 8 28 9 29 10 30 11 31 12 32 13 33 14 34 15 3...

Страница 65: ..._________________ If other than Standard Message is required please specify Dual channel only ALERT Tone ________________________________ Default is Chime Message _____________________________ Default...

Страница 66: ...one M Message F D Fan Damper AOR Function and number must be specified for each switch in the Master Panel Paging circuit numbers must follow building floors from the bottom up as these s are used for...

Страница 67: ...ption 1 1 9 2 2 10 3 3 11 4 4 12 5 5 13 6 6 14 7 7 15 8 8 16 Fire Phones are limited to 1 circuit per switch Multiple speaker circuits may be assigned to a single switch Total Load _______ ______ Max...

Страница 68: ...single channel system DPs may be configured with one or two amplifiers In single Amp DPs FNV DPS50 for example Total Load and Max Load are the same The sum of all speaker circuit loads together determ...

Страница 69: ...firealarmresources com...

Страница 70: ...sion indication and control is provided on the microphone subpanel via switches and a simplified alphanumeric display The two main switches are System Reset and System Trouble Silence The microphone s...

Страница 71: ...mA NetComm Bus Type RS 485 Frequency 1 024 MHz Impedance 120 Ohms Maximum Cable Length 4 000 feet 26 AWG between panels 50 000 feet in the overall system Recommended Cable Category 5 Low Capacitance U...

Страница 72: ...d for each Fire Phone loop in the Remote panels and is seperately addressed by switches in the Master panel Power Operating Voltage Provided by DCC Operating Current 2 mA 4 4 6 MBR Mother Board Remote...

Страница 73: ...e ganged for a total of 128 Input points per base IOI Power Operating Voltage Provided by DCC Operating Current 18 mA base 2 mA additional per 16 points One IOI is used at the Master panel for connect...

Страница 74: ...emote that also has an Alarm zone active will disable the remaining Alert zones in that Remote panel while paging takes place When a Fire Phone Handset is jacked in the LED for that Fire Phone loop wi...

Страница 75: ...5 from the FACP and power and serial data connections to FNV are on TB1 All wiring is power limited and board can be snaptrack or standoff mounting 4 6 3 FNV LLC LED Annunciator Card The FNV LLC is ut...

Страница 76: ...d fault indication Snaptrack or standoff mounting 4 6 9 FNV FJ Fireman s Phone Jack The FNV FJ is a fireman s phone jack station to be located at strategic places in a building for two way communicati...

Страница 77: ...cable on the handset 4 6 14 FNV AOR Area of Refuge Station The FNV AOR is a call in and voice communication station for use with the FNV system The station consists of a speaker microphone lighted sw...

Страница 78: ...ious page and attached Instructions and Layout Drawing MBK boards are shipped mounted FPI s are only included with panels with firephone circuits PLUG BOARDS in CAREFULLY They can only go one way 8 Co...

Страница 79: ...When finished power down all panels and continue in same manner with DP s adding one at a time looping comm loop back to MP each time a new panel is added 16 Power down all panels remove wiring and r...

Страница 80: ...port of an emergency Proceed calmly to the nearest exit and leave the building immediately Do not use the elevators use stairwells where necessary All handicapped occupants shall use the building evac...

Страница 81: ...UP 19 In the ASCII sending box Send lines end with line feeds should be left BLANK Echo typed characters locally should be left BLANK Line delays set to 1000 milliseconds Character delay set to 10 mil...

Страница 82: ...ace to operate system without batteries connected to Master Panel Hochiki FNV System Master Panel Battery Supervision Effective 2 18 02 Jumper J1 disable Ground Fault Supervision in the Master Panel O...

Страница 83: ...facing the right side of MBR Second FPI if used installs in next slot to the left MBK First MBK installs in second slot in from the left on MBR note heavy connectors with white base Make sure that po...

Страница 84: ...I A M I A M I NOTE Ribbon cables connecting to AMI and FPI boards are illustrated on separate sheet Please check ribbon cable positioning BEFORE inserting these boards J7 10 pin ribbon firealarmresou...

Страница 85: ...MBK MBK MBK First MBK First MBK Second MBK firealarmresources com...

Страница 86: ...f cabinet To second amplifier module right side of cabinet TB1 TB3 TB2 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 MESSAGE GAIN MIC GAIN FAULT NORMAL ALARM YEL GRN RED J2 1 2 3 J1 P2 S1 SN...

Страница 87: ...shown by the orientation of the red stripe at both ends of the ribbon cable Second FPI in system connects to MBR Slot P4 Ribbon cable 24 connects to FPO card as shown Observe polarity as shown by the...

Страница 88: ...FROM LAST DEVICE MASTER PANEL DISTRIBUTED PANEL P1 NetComm Loop Wiring Style 4 TB1 TB2 TB3 TB4 TB5 P1 P2 P3 P4 J1 1 2 3 LED3 LED2 LED1 DCC ASC TB1 P4 P3 P1 P2 P5 P5 MBR TB2 TB3 TB4 TB5 TB6 TB7 TB8 1...

Страница 89: ...witch 26 play message 20 set switch 27 play message 22 set switch 28 all call set switch 29 signal silence set switch 30 alarm restore set floor above set floor below set alert non fire floors Set inp...

Страница 90: ...UAL EVAC ZONE 1 FIRE PHONE ZONE 2 FIRE PHONE ZONE 3 FIRE PHONE ZONE 4 MANUAL EVAC ZONE 5 MANUAL EVAC ZONE 2 MANUAL EVAC ZONE 6 MANUAL EVAC ZONE 3 MANUAL EVAC ZONE 7 MANUAL EVAC ZONE 4 MANUAL EVAC STAI...

Страница 91: ...Alarm Polarity Shown 10 11 9 8 7 6 5 4 3 2 1 10 11 9 8 7 6 5 4 3 2 1 Common Common Evac 1 Spare Evac 2 Spare Evac 3 Spare Evac 4 Spare Evac 5 Spare Evac 6 Spare Evac 7 Spare Evac 20 Spare FACP SIGNAL...

Страница 92: ...Controller Board Class B Speaker Circuits Standby polarity shown 12V Battery 12V Battery 12V Battery 12V Battery red red black black TB1 1 2 3 4 5 6 7 8 TB3 1 2 3 4 5 6 7 8 MESSAGE GAIN MIC GAIN FAULT...

Страница 93: ...firealarmresources com...

Страница 94: ...Twisted Pair 18 AWG or 16AWG The jacket adds strength and abrasion resistance and reduces the chance of induction from other cables nearby CAT 5 UTP can be used but the usual 4 pairs in CAT 5 are not...

Страница 95: ...ECTION ONLY MASTER OR REMOTE PANEL 2 WIRE 485 DATA IN 2 WIRE 485 DATA OUT DATA STREAM IS RECREATED BY EACH PANEL Sync 1 0 1 0 128 Bits 1 024MHz 976nS 488nS 488nS Manchester encoded Primary rate 1 024M...

Страница 96: ...and vice versa which completely scrambles the data When an HFNV panel is powered down for service be sure to use a coupler so the incoming fiber transmits directly to the outgoing fiber or other panel...

Страница 97: ...ed in the Temporal ANSI pattern Single frequencies can be absorbed and reflected in unusual ways by building walls and furnishings and are heard differently by different people at different ages Hence...

Страница 98: ...7051 Village Drive Suite 100 Buena Park CA 90621 2268 800 845 6692 Technical Support firealarmresources com...