Hochiki America Corporation
7051 Village Drive, Suite 100 • Buena Park, CA 90621-2268
Phone: 714/522-2246 • Fax: 714/522-2268
Technical Support: 800/845-6692 or [email protected]
08/2001
DESCRIPTION
STANDARD FEATURES
OPERATION
1. Pull out the measuring unit drawer to expose the
meters and AC plug connector.
2. Remove the AC cord. Connect one end to the AC
plug connector and the other end to a 120VAC
electrical outlet.
3. Turn the AC source switch on. The circulating fan
starts.
4. Allow five minutes for warm-up to ensure stability
of the testing circuits.
5. Open the top cover and locate the wire leads and
clip.
6. If you are using a detector base, connect the wire
leads to this base and mount the base to the
wooden installation plate provided.
Terminal Markings: Source cable (not used)
Signal line (+)
Common line (-)
Configuring the TSA-B110
7. Use the photo/ion change-over switch to
choose the type of detector (ION or PHOTO) which
is to be tested.
8. Use the voltage adjustment knob to adjust the
voltage to agree with the rated voltage of the detec-
tor being tested (for SLK-12 use 17.0 VDC).
9. Use the densitometer “0” adjustment knob to
set the pointer to zero (0).
Continued on back.
TSA-B110 SMOKE DETECTOR SENSITIVITY TESTER
Specifications subject to change without notice.
SPECIFICATIONS
The Hochiki America TSA-B110 Smoke Detector Sen-
sitivity Tester is designed for efficient and accurate test-
ing of the sensitivity of smoke detectors. For ease of
use in field applications the tester is easy to transport
and compact. Two densitometer circuits allow the TSA-
B110 Smoke Detector Sensitivity Tester to test both
ionization and photoelectric smoke detectors.
The TSA-B110 Smoke Detector Sensitivity Tester is a
sensitive piece of electronic equipment. The unit must
be used in a temperature range of 50°F to 86°F. Sudden
jarring or dropping of the TSA-B110 may damage the
unit. Operation will be affected if proper care is not
taken.
•
Tests the sensitivity of Hochiki's previous model
photoelectric and ionization smoke detectors.
•
Lightweight and portable for easy use in the field.
•
Obscuration/sensitivity testing similar to that of a
UL 268 Smoke Box.
•
Voltage Adjustment Knob easily changes tester
voltage to the rated voltage of the detector.
•
Indicator lamp automatically lights at completion
of testing.
Rated Voltage
120 V AC, 50/60 Hz
Source Voltage
108V - 132V AC
Smoke Generating
Material
SM-101-P Punk Stick
Operating Temperature
Range
50°F to 86°F
Dimensions
15.74" x 11.02" x 7.87"
Weight
13 Lbs.
firealarmresources.com
Fike Part Number 69-016