GENERAL DESCRIPTION:
Remote Programming Cable
(All Modules except DCP-FRCME-S
and DCP-FRCME-P)
Remote Programming Cable
(DCP-FRCME-S)
Programming Buttons
Display
TCH-B100-NS PROGRAMMER OPERATING INSTRUCTIONS
PROGRAMMING BUTTONS
ADDRESS SETTING:
To Remote
Programming Jack
NOTE: PRIOR TO PROGRAMMING ENSURE BATTERY IS CONNECTED.
Remote Programming
Jack
Power on. Automatically reads the address of a sensor. Subsequent
operations will advance the device address by ten.
Power off. Advances the device address by one.
Stores the displayed addresss to the device and is used to read sensor
analog levels.
Analog Photoelectric Smoke Sensor
Analog Ionization Smoke Sensor
Analog Heat Sensor
DCP Fast Response Contact Module (Terminal Block)
DCP Fast Response Contact Monitor
DCP Signal Output Module
DCP Dual Relay Module
TCH-B100-NS is designed for use with the following products:
ALG-V/ALG-EA
AIE-EA
ATG-EA
FRCME-S
FRCME-4
SOM
R2M
CZM
1.
2.
3.
4.
Install sensor onto programmer, ensuring that sensor protrusions align with programmer grooves.
Press the left gray button to switch programmer on. A battery check message will appear followed by
the devices address ( un-programmed sensors will read address 127).
Set the required address by incrementing the left and right gray buttons (the display will show three red
flashing dots if the address being programmed is different from the device's current address).
When the desired address is present press the red button to store that address. The three red dots on
the display will no longer be present.
LEFT GRAY BUTTON
RIGHT GRAY BUTTON
RED BUTTON
DCP Conventional Zone Module
DWG # HA-06-082
Page 1 of 2, 10-03
PART # 1700-09906
HOCHIKI AMERICA CORPORATION
7051 Village Drive, Suite 100
Buena Park, CA 90621-2268.
DCP Dual Input Monitor Module
DIMM
Remote Programming Cable
(DCP-FRCME-P)
DCP Fast Response Contact Module (Flying Leads; No Terminal Block)
FRCME-P