For channels set as Inputs
1. Choose an
Input Action
.
2.
Input Action Message
is automatically set based on the selected
Input Action
. If desired, a custom
Input Action
Message
can be entered.
3. Check the
Output Delay
Bypass box if activation of this circuit should immediately activate its associated outputs,
even if those outputs have configured delays. For UL compliance, this field must be checked.
4. Set the
Input Delay
in seconds, up to 180 seconds. Input activation will prevent the panel's response for specified
time period when the input is activated. No activation will occur if the input state is reset to normal before time period
expires. For UL compliance, this field must be set to 0.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 | March 2021 | MAN-1420HA
Page 20
Configuration