INSTALLATION INSTRUCTIONS FOR CLIM CURRENT LOOP INPUT MODULE 

The information contained in this installation instruction is a quick reference guide. For detailed system information refer to the panel 

manufacturers’ installation manual. This instruction is generic and will not address. 

GENERAL DESCRIPTION: 

 

NOTE: 

When installing fire alarm system devices, avoid placing devices or wiring close to potential Radio Frequency or Electro-Magnetic 

noise sources. Avoid running SLC circuit in the same conduit as power lines. Utilize twisted pair and shielded wire in environment 

where excessive noise is expected. 

 

NOTE:  An average of 6.75mA (communication current) per loop of SLC device, must be factored into the panel battery backup 
calculations. 

SPECIFICATIONS 

SLC Applied Voltage 
 

Maximum     39 VDC 
Nominal        33 VDC 

SLC Current Consumption 

Maximum      

400µA  Surge Current: 30mA (in 5ms), Alarm & No Input: 30mA(in 20ms) 

Nominal           400µA (Typical)

Full Scale Input Range 

0 mA   to   +25 mA 
Normal Input Range:   +4 mA   to   +20 mA 

Input Impedance 

250 

 

 

Visual Indicator (status LED) 

Bi-color LED  -  Green and Red
Color and Mode  -  selected and programmed by Control Panel software 

Operating Temperature Range 

0°C (32°F) ~ 49°C (120°F) 
 

Storage Temperature 

-30°C (-22°F) ~ 70°C (158°F) 
 

Max Relative Humidity 

Up to 90

%

 RH non-condensing 

Environment 

Indoor use only 

Dimensions 

4.2"W X 4.7"H X 0.85"D 

Weight Approximately 

3.0 

ounces 

 
 
 
 

This instruction applies to the 4 to 20mA Current Loop Input Module (CLIM) which is to be 

connected to a DCP Signaling Line Circuit (SLC). The module allows analog panel to 

interface or monitor sensor or detection device which transmits its output data as 4 to 20ma 

output current. Examples of typical applications are temperature sensor, pressure sensor, 

liquid level sensor and carbon monoxide transducer. 

MOUNTING REQUIREMENTS: 

The CLIM Current Loop Input Module is mounted as shown in Figure 3 on page 2 of this 
instruction. 

WIRING: 

NOTE:  All wiring must conform to local codes, ordinances and regulations. 
1)

 

Install module wiring in accordance with the job drawings and appropriate wiring 
diagram (see Figure 2) 

2)

 

Secure the module to a U.L. listed electrical box (supplied by installer) as shown in 
Figure 3. 

3)

 

The address must be set on the CLIM before the cover plate is attached (see Fig. 1) 

CAUTION! 

To ensure proper operation connect 
this module to a compatible Fire 
Control Panel only. Refer to panel 
instructions for proper connection 
and compatibility.  

CAUTION! 

If this module will be installed in an 
existing operation system, inform 
the operator and local authority that 
the system will be temporarily out of 
service. Disconnect power to the 
control panel before installing the 
module.

STATUS LED 

FIGURE 1. 

EXPLODED VIEW OF ADDRESS 

PROGRAMMING PLUG AND CONNECTOR 

TO PROGRAMMER 

TCH-B100 P/N 0700-01330

PLUG IS 

NON-POLARIZED 

HOCHIKI AMERICA CORPORATION 

7051 VILLAGE DRIVE, SUITE 100 

BUENA PARK, CA 90621-2268 

DWG.#  HA-06-136

(PG  1 of 2, 3/13) 