MINI ZONE MONITOR INSTALLATION INSTRUCTIONS 
 

 

Function

 

 

The CHQ-MZ is a loop powered module that provides a single fully monitored input for the connection of either up to 
six Hochiki conventional smoke or heat detectors, one Hochiki Beam detector or any number of conventional call 
points, the unit also contains an output for remote fire indication.  The CHQ-MZ/DIN is the DIN Rail mounted version. 

 

Specification 

Order code  

CHQ-MZ* / CHQ-MZ/OEM* / CHQ-MZ/DIN* 

Transmission method  

Digital communication using ESP 

Loop:-Operating voltage 

17 - 31 VDC  

          Quiescent current  

260

µ

          Current consumption whilst polling  

22 mA 

±

 20 %  

E.O.L device 

TE-RH-E (polarity conscious) 

Zone voltage 

15.3V - 17.1V 

Zone resistance  

50

 (Max) 

Zone capacitance  

0.3

µ

F (Max) 

Detectors per zone 

Number of conventional detectors per zone 

 

DCA, DFB, DFE – No limit 

 

SLG, SLK, SLR, SIF, SIH, SIJ, DCC, DCD, DFJ – 6 max 

 

SPB-ET or SRA-ET– Only one and no other detectors 

 

HF-24 – Only one and no other detectors 

 

Conventional Call Points – No limit 

Weights and Dimensions         CHQ-MZ 

120g, L=160 x W=110 x H=92mm 

                                                 CHQ-
MZ/OEM 

75g, L=147 x W=90 x H=23mm 

                                                 CHQ-MZ/DIN  106g, L=120 x W=23 x H=108mm 
Colour and enclosure material CHQ-MZ 
                                                 CHQ-
MZ/OEM 
                                                 CHQ-MZ/DIN 

Grey, ABS (IP67 rated), c/w OEM module 
White, ABS 
Green ABS 

 *  Fire alarm control panel compatibility required for these products.

  

Note:- The End of Line device (part number TE-RH-E) is supplied with the unit. 

 

 

Connection Details 

 

 

Fig. 1 

 