OM-284833 Page 19
5-9. Positioning Jumper Links
Tools Needed:
3/8 in.
Check input voltage available at
site.
1
Jumper Links Access Door
Open door.
2
Jumper Link Label
Check label
−
only one is on unit.
3
Input Voltage Jumper Links
Move jumper links to match input
voltage.
Close and secure access door.
284705-A / 804911-A
2
208 VOLTS
240 VOLTS
284705-A
3
1
Philips Screw Driver #1
5-10. Electrical Service Guide
Elec Serv 2020-02
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for an individual branch circuit sized for the rated output and duty cycle of one welding power source.
In individual branch circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than
the rating of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11,
and 630.12.
60 Hz
1-Phase
Rated Supply Voltage (V)
208
240
Rated Maximum Supply Current
I
1max
(A)
62.6
55.7
Maximum Effective Supply Current
I
1eff
(A)
46.3
40
Maximum Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
70
60
Normal Operating Fuses
3
80
70
Maximum Recommended Supply Conductor Length In Feet (Meters)
4
79 (24)
105 (32)
Raceway Installation
Minimum Supply Conductor Size In AWG (mm
2
)
5
8 (10)
8 (10)
Minimum Grounding Conductor Size In AWG (mm
2)
5
8 (10)
8 (10)
Reference: 2020 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Maximum total length of copper input conductors in entire installation, raceway and/or flexible cord.
5 Raceway conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per
NEC Table 310.15(B)(16) and is based on allowable ampacities of insulated copper conductors having a temperature rating of 75
°
C (167
°
F) with not
more than three single current
−
carrying conductors in a raceway.
Содержание IronMan 240
Страница 4: ......
Страница 26: ... A complete Parts List is available at www HobartWelders com OM 284833 Page 22 5 13 Weld Parameters ...
Страница 27: ... A complete Parts List is available at www HobartWelders com OM 284833 Page 23 284702 B ...
Страница 32: ...OM 284833 Page 28 SECTION 8 ELECTRICAL DIAGRAM Figure 8 1 Welding Power Source Circuit Diagram ...
Страница 33: ...OM 284833 Page 29 284828 A ...