Figure 02-6 Schematic diagram of frequency level detection
02.27
UP/DOWN terminal modification rate
0.0Hz
~
99.9Hz/s
1.0
The function code is the frequency modification rate when setting the UP/DOWN terminal as frequency set , that is, the UP/DOWN terminal is short-circuited with the
GND terminal for 1s, and the frequency changes.
02.28
Input terminal pulse trigger mode setting (DI1
~
DI5)
0
~
1FH
0
0: indicates the electrical level trigger mode
1: indicates the pulse trigger mode
Note:
DI1
~
DI5 correspond to 1H, 2H, 4H, 8H and 10H in hexadecimal.
02.29
Input terminal valid logic setting (DI1
~
DI5)
0
~
1FH
0
0: indicates positive logic, that is, the DI terminal is connected to GND and GND is valid, and the disconnection is invalid
1: It means anti-logic, that is, DI terminal is not connected to the GND terminal and GND is invalid, and the disconnection is valid
Note:
DI1
~
DI5 correspond to 1H, 2H, 4H, 8H and 10H in hexadecimal.
02.30
DI1 filter coefficient
0
~
9999
5
02.31
DI2 filter coefficient
0
~
9999
5
02.32
DI3 filter coefficient
0
~
9999
5
02.33
DI4 filter coefficient
0
~
9999
5
02.34
DI5filter coefficient
0
~
9999
5
Used to set the sensitivity of the input terminal. If the digital input terminal is susceptible to interference and causes misoperation, this parameter can be increased
to enhance the anti-interference ability, but the sensitivity of the input terminal will be reduced if the setting is too large.
1: represents 2ms scanning time unit
03 group -PID parameters
03.00
PID function setting
0000
~
2122
1010